Plan Review Details - Permit 21091137
Plan Review Stops For Permit 21091137
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-01-07 Cont ID  
Sent By rmcdouga Date 2022-01-07 Time 11:10 Rev Time 0.00
Received By rmcdouga Date 2022-01-07 Time 11:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-01-03 Cont ID  
Sent By rmcdouga Date 2022-01-03 Time 09:32 Rev Time 0.00
Received By rmcdouga Date 2022-01-03 Time 09:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-11-02 Cont ID  
Sent By rmcdouga Date 2021-11-02 Time 16:19 Rev Time 0.00
Received By rmcdouga Date 2021-11-02 Time 16:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-01-03 Cont ID  
Sent By ppetty Date 2022-01-03 Time 12:44 Rev Time 0.00
Received By ppetty Date 2022-01-03 Time 11:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-10-14 Cont ID  
Sent By ppetty Date 2021-10-14 Time 10:21 Rev Time 0.00
Received By ppetty Date 2021-10-14 Time 10:21 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2021-10-01 Cont ID  
Sent By shill Date 2021-10-01 Time 09:01 Rev Time 0.00
Received By shill Date 2021-10-01 Time 09:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-07 Cont ID  
Sent By rmcdouga Date 2022-01-07 Time 11:11 Rev Time 0.00
Received By rmcdouga Date 2022-01-07 Time 11:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-03 Cont ID  
Sent By ppetty Date 2022-01-03 Time 12:45 Rev Time 0.00
Received By ppetty Date 2021-12-08 Time 07:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-02 Cont ID  
Sent By rmcdouga Date 2021-11-02 Time 17:13 Rev Time 0.00
Received By rmcdouga Date 2021-09-27 Time 10:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-12-09 Cont ID  
Sent By lcrespo Date 2021-12-09 Time 11:46 Rev Time 0.00
Received By lcrespo Date 2021-12-09 Time 11:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-10-19 Cont ID  
Sent By lcrespo Date 2021-10-19 Time 10:44 Rev Time 0.00
Received By lcrespo Date 2021-10-19 Time 10:44 Sent To  
Notes
2021-10-19 10:52:5010/19/21 1ST POOL PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE SUBMIT TOTAL DYNAMIC HEAD
 CALCULATIONS FOR THE MAXIMUM SYSTEM FLOW. THE MAXIMUM
 FLOW OF THE PUMP FROM ITS PUMP CURVE IS NO LONGER
 ALLOWED TO BE USED IN DETERMINING THE MAXIMUM SYSTEM
 FLOW RATE PER ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9,
 4.4.9.1. THE 2013 EDITION ADDRESSES THE FLOW RATE IN
 GALLONS PER MINUTE (GPM). IT REQUIRES THAT THE MAXIMUM
 SYSTEM FLOW RATE DOES NOT EXCEED THE LISTED MAXIMUM
 FLOW RATE OF THE SUCTION OUTLET FITTING ASSEMBLY (DRAIN
 COVER). THE TDH CALCULATIONS MUST INCLUDE ALL THE
 SYSTEM COMPONENTS INCLUDING SUCTION AND RETURN PIPING,
 FITTINGS, VALVES, HEATER, FILTER, AND CHLORINATOR. ALL
 SYSTEM COMPONENTS EXCEPT THE PUMP.
  
 2. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR
 THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 3. HEATED SWIMMING POOLS AND IN GROUND PERMANENTLY
 INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT
 COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR
 OTHER MEANS PROVEN TO REDUCE HEAT LOSS PER THE 2020
 FBC- ENERGY- SEC. R 403.10.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-01-05 Cont ID  
Sent By rmcdouga Date 2022-01-03 Time 09:43 Rev Time 0.00
Received By rmcdouga Date 2022-01-03 Time 09:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-11-02 Cont ID  
Sent By rmcdouga Date 2021-11-02 Time 16:20 Rev Time 0.00
Received By rmcdouga Date 2021-11-02 Time 16:20 Sent To  
Notes
2021-11-02 16:22:48THE ENGINEER IS SELF-CERTIFYING HIS DIGITAL SIGNATURE.
 THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS REQUIRES
 ENGINEERS TO USE AN APPROVED THIRD PARTY AGENCY TO
 CERTIFY THEIR SIGNATURES.

Review Stop Z ZONING
Rev No 1 Status P Date 2021-10-06 Cont ID  
Sent By rthermid Date 2021-10-06 Time   Rev Time  
Received By rthermid Date 2021-10-06 Time   Sent To I
Notes
***NONE***