Plan Review Details - Permit 21090962
Plan Review Stops For Permit 21090962
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2021-10-28 Cont ID  
Sent By cpuell Date 2021-10-28 Time 12:34 Rev Time 0.00
Received By cpuell Date 2021-10-28 Time 12:34 Sent To  
Notes
2021-10-28 12:35:17A SECOND PERMIT APPLIED FOR 3012 BROADWAY, THIS PERMIT
 IS FOR 3008 BROADWAY ONLY.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-10-19 Cont ID  
Sent By cpuell Date 2021-10-19 Time 16:16 Rev Time 0.00
Received By cpuell Date 2021-10-19 Time 16:16 Sent To  
Notes
2021-10-19 16:18:19PLANS UPLOADED FOR BOTH 3008 AND 3012 BROADWAY, WHICH
 BOTH ARE SEPARATE PROPERTIES. PLEASE CONTACT
 [email protected] TO DISCUSS THE ADDRESS ISSUES OR CALL
 561-805-6659

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-09-21 Cont ID  
Sent By cpuell Date 2021-09-21 Time 16:14 Rev Time 0.00
Received By cpuell Date 2021-09-21 Time 16:14 Sent To  
Notes
2021-09-21 16:17:26TWO BUILDINGS ON PARCEL, WILL THE RERROF BE FOR THE
 EAST OR WEST BUILDING OR BOTH, PLEASE RESPOND TO
 [email protected] OR CALL 561-805-6659

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-11-15 Cont ID  
Sent By jbrooks Date 2021-11-15 Time 12:15 Rev Time 0.00
Received By jbrooks Date 2021-11-15 Time 07:52 Sent To  
Notes
2021-11-15 12:15:27JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
  
 1. FBC B 107.2.1 FBC R 301 FAC9N-3. SUBMITTED
 MIAMI-DADE COUNTY NOA NO. 18-0109.09 SELECTED SYSTEM
 TYPE D(1) FASTENING #1 WITH A MAXIMUM DESIGN PRESSURE
 -67.5 OR FASTENING #2 WITH A MAXIMUM DESIGN PRESSURE
 -52.5 ON PAGE #6 DO NOT MEET THE MINIMUM DESIGN
 PRESSURE REQUIREMENT FOR ZONES 2 OR 3 IN AN EXPOSURE C
 CATEGORY AREA AND WILL REQUIRE SIGNED AND SEALED
 ENGINEERED DESIGN PRESSURE CALCULATIONS BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER, REGISTERED ARCHITECT,
 OR REGISTERED ROOF CONSULTANT AS PER LIMITATION #7.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-11-04 Cont ID  
Sent By jbrooks Date 2021-11-04 Time 13:58 Rev Time 0.00
Received By jbrooks Date 2021-11-04 Time 07:49 Sent To  
Notes
2021-11-04 13:58:21JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 PLEASE ADDRESS PREVIOUS COMMENTS BELOW DATED 10/27/2021
 AND RESUBMIT.
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE ON THE
 ROOF DRAWING. FBC AMEND. 107.2.1
 2) SPECIFY THE LOCATIONS AND HEIGHTS OF THE PARAPET
 WALLS ON THE ROOF DRAWING. FBC AMEND. 107.2.1
 3) SHOW THE LOCATIONS OF THE ROOF DRAINS AND/OR
 SCUPPERS ON THE ROOF DRAWING. FBC AMEND. 107.2.1
 4) PROVIDE A FLASHING DETAIL FOR THE PARAPET WALLS. FBC
 AMEND. 107.2.1
 5) THE ROOF REPORT INDICATES THAT THE PREDOMINATE PITCH
 IS 0:12. SECTION 706.1 OF THE FBC EXISTING BUILDING
 REQUIRES ROOFS TO HAVE POSITIVE DRAINAGE. SHOW
 COMPLIANCE ON THE ROOF PLAN.
 6) [THE SYSTEM THAT WAS MARKED ON PAGE 5 OF THE PRODUCT
 APPROVAL CANNOT BE USED. THE DESIGN PRESSURES OF -45
 PSF ARE TOO LOW AND CAN NOT BE INCREASED BY ENHANCED
 FASTENING PER LIMITATION #9.] THE PRODUCT APPROVALS FOR
 THE MULE-HIDE TPO ROOF SYSTEM HAS SEVERAL DIFFERENT
 ASSEMBLIES WITH DIFFERENT FASTENINGS AND DESIGN
 PRESSURES. PLEASE CIRCLE OR HI-LITE THE ONE THAT
 APPLIES TO THIS PROJECT. FBC AMEND. 107.2.1
 7) [SELECT THE FASTENING OPTION FOR THE APPROVED
 ASSEMBLY ON PAGE 6 AND SUBMIT SIGNED AND SEALED
 ENHANCED FASTENING CALCULATIONS AS SPECIFIED IN
 LIMITATION #7 ON PAGE 7 OF THE NOA.] THE MAXIMUM DESIGN
 PRESSURES ARE NOT ADEQUATE FOR THE PERIMETER AND CORNER
 AREAS. CHOOSE ONE THAT ALLOWS ENHANCED FASTENING AND
 SUBMIT SIGNED AND SEALED ENHANCED FASTENING
 CALCULATIONS FROM AN ENGINEER. ARCHITECT OR REGISTERED
 ROOFING CONSULTANT. SEE LIMITATION #7 ON PAGE 7 OF NOA
 NO.18-0109.09.
 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
 9) SOME DOCUMENTS WERE SUBMITTED WITH THE ADDRESS OF
 3012 BROADWAY. THIS PERMIT IS FOR 3008 BROADWAY. SUBMIT
 ONLY DOCUMENTS THAT APPLY TO THIS PERMIT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-10-27 Cont ID  
Sent By rmcdouga Date 2021-10-27 Time 11:00 Rev Time 0.00
Received By rmcdouga Date 2021-10-27 Time 11:00 Sent To  
Notes
2021-10-27 11:00:16PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE ON THE
 ROOF DRAWING. FBC AMEND. 107.2.1
 2) SPECIFY THE LOCATIONS AND HEIGHTS OF THE PARAPET
 WALLS ON THE ROOF DRAWING. FBC AMEND. 107.2.1
 3) SHOW THE LOCATIONS OF THE ROOF DRAINS AND/OR
 SCUPPERS ON THE ROOF DRAWING. FBC AMEND. 107.2.1
 4) PROVIDE A FLASHING DETAIL FOR THE PARPET WALLS. FBC
 AMEND. 107.2.1
 5) THE ROOF REPORT INDICATES THAT THE PREDOMINAT PITCH
 IS 0:12. SECTION 706.1 OF THE FBC EXISTING BUILDING
 REQUIRES ROOFS TO HAVE POSITIVE DRAINAGE. SHOW
 COMPLIANCE ON THE ROOF PLAN.
 6) [THE SYSTEM THAT WAS MARKED ON PAGE 5 OF THE PRODUCT
 APPROVAL CAN NOT BE USED. THE DESIGN PRESSURES OF -45
 PSF ARE TOO LOW AND CAN NOT BE INCREASED BY ENHANCED
 FASTENING PER LIMITATION #9.] THE PRODUCT APPROVALS FOR
 THE MULE-HIDE TPO ROOF SYSTEM HAS SEVERAL DIFFERENT
 ASSEMBLIES WITH DIFFERENT FASTENINGS AND DESIGN
 PRESSURES. PLEASE CIRCLE OR HI-LITE THE ONE THAT
 APPLIES TO THIS PROJECT. FBC AMEND. 107.2.1
 7) [SELECT THE FASTENING OPTION FOR THE APPROVED
 ASSEMBLY ON PAGE 6 AND SUBMIT SIGNED AND SEALED
 ENHANCED FASTENING CALCULATIONS AS SPECIFIED IN
 LIMITATION #7 ON PAGE 7 OF THE NOA.] THE MAXIMUM DESIGN
 PRESSURES ARE NOT ADEQUATE FOR THE PERIMETER AND CORNER
 AREAS. CHOOSE ONE THAT ALLOWS ENHANCED FASTENING AND
 SUBMIT SIGNED AND SEALED ENHANCED FASTENING
 CALCULATIONS FROM AN ENGINEER. ARCHITECT OR REGISTERED
 ROOFING CONSULTANT. SEE LIMITATION #7 ON PAGE 7 OF NOA
 NO.18-0109.09.
 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
 9) SOME DOCUMENTS WERE SUBMITTED WITH THE ADDRESS OF
 3012 BROADWAY. THIS PERMIT IS FOR 3008 BROADWAY. SUBMIT
 ONLY DOCUMENTS THAT APPLY TO THIS PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-30 Cont ID  
Sent By rmcdouga Date 2021-09-30 Time 16:11 Rev Time 0.00
Received By rmcdouga Date 2021-09-30 Time 16:11 Sent To  
Notes
2021-09-30 15:35:44PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE ON THE
 ROOF DRAWING. FBC AMEND. 107.2.1
 2) SPECIFY THE LOCATIONS AND HEIGHTS OF THE PARAPET
 WALLS ON THE ROOF DRAWING. FBC AMEND. 107.2.1
 3) SHOW THE LOCATIONS OF THE ROOF DRAINS AND/OR
 SCUPPERS ON THE ROOF DRAWING. FBC AMEND. 107.2.1
 4) PROVIDE A FLASHING DETAIL FOR THE PARPET WALLS. FBC
 AMEND. 107.2.1
 5) THE ROOF REPORT INDICATES THAT THE PREDOMINAT PITCH
 IS 0:12. SECTION 706.1 OF THE FBC EXISTING BUILDING
 REQUIRES ROOFS TO HAVE POSITIVE DRAINAGE. SHOW
 COMPLIANCE ON THE ROOF PLAN.
 6) SPECIFY THE ROOF DECK TYPE. IS IT WOOD OR
 LIGHTWEIGHT CONCRETE? THE PRODUCT APPROVAL THAT WAS
 SUBMITTED IS FOR LIGHTWEIGHT CONCRETE, POURED GYPSUM OR
 CEMENTITIOUS WOOD FIBER. FBC AMEND. 107.2.1
 7) IF THE EXISTING ROOF DECK IS LIGHTWEIGHT INSULATING
 CONCRETE OR GYPSUM, YOU WILL BE REQUIRED TO SUBMIT A
 MOISTURE TEST AND FASTENER PULL TESTS FOR THE ROOF. FBC
 1504.1
 8) THE PRODUCT APPROVALS FOR THE MULE-HIDE TPO ROOF
 SYSTEM HAS SEVERAL DIFFERENT ASSEMBLIES WITH DIFFERENT
 FASTENINGS AND DESIGN PRESSURES. PLEASE CIRCLE OR
 HI-LITE THE ONE THAT APPLIES TO THIS PROJECT. FBC
 AMEND. 107.2.1
 9) THE MAXIMUM DESIGN PRESSURES ARE NOT ADEQUATE FOR
 THE PERIMETER AND CORNER AREAS. CHOOSE ONE THAT ALLOWS
 ENHANCED FASTENING AND SUBMIT SIGNED AND SEALED
 ENHANCED FASTENING CALCULATIONS FROM AN ENGINEER.
 ARCHITECT OR REGISTERED ROOFING CONSULTANT. SEE
 LIMITATION #7 ON PAGE 7 OF NOA NO.18-0109.09.
 10) DUE TO THE MISSING INFORMATION, ADDITIONAL COMMENTS
 MAY RESULT WHEN THIS INFORMATION IS SUBMITTED. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-11-15 Cont ID  
Sent By jbrooks Date 2021-11-15 Time 12:15 Rev Time 0.00
Received By jbrooks Date 2021-11-10 Time 16:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-11-04 Cont ID  
Sent By jbrooks Date 2021-11-04 Time 13:58 Rev Time 0.00
Received By jbrooks Date 2021-10-28 Time 08:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-27 Cont ID  
Sent By rmcdouga Date 2021-10-27 Time 11:01 Rev Time 0.00
Received By rmcdouga Date 2021-10-19 Time 10:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-30 Cont ID  
Sent By rmcdouga Date 2021-09-30 Time 16:11 Rev Time 0.00
Received By rmcdouga Date 2021-09-28 Time 15:35 Sent To  
Notes
***NONE***