Plan Review Details - Permit 21090948
Plan Review Stops For Permit 21090948
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-11-17 Cont ID  
Sent By rmcphers Date 2021-11-17 Time 14:34 Rev Time 0.00
Received By rmcphers Date 2021-11-17 Time 14:34 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2021-10-22 Cont ID  
Sent By rmcphers Date 2021-10-22 Time 13:23 Rev Time 0.00
Received By rmcphers Date 2021-10-21 Time 15:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-11-17 Cont ID  
Sent By rmcphers Date 2021-11-17 Time 14:34 Rev Time 0.00
Received By rmcphers Date 2021-11-17 Time 13:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-22 Cont ID  
Sent By rmcphers Date 2021-10-22 Time 14:02 Rev Time 0.00
Received By rmcphers Date 2021-10-21 Time 15:01 Sent To  
Notes
2021-10-22 13:44:52GROUND FLOOR ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW WALL AND CEILING FINISHES FIRE
 CLASSIFICATION TO COMPLY WITH FBC TABLE 803.11
  
 2) BUILDING CONSTRUCTION TYPE SHOWN ON DRAWING ALS1.1
 MAY BE INCORRECT - SHOWN IS CONSTRUCTION TYPE IIIB
 WHICH IS LIMITED IN STORIES - HOW MANY STORIES ARE IN
 THE BUILDING - PLEASE RE EVALUATE PER FBC CHAPTER 5
  
 3) PLEASE PROVIDE THE EXTERIOR LOADING RAMP
 CONSTRUCTION DETAILS.
  
 4) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR HEIGHT
 FROM THE FINISHED FLOOR TO THE "REFLECTIVE SURFACE" -
 FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-10-02 Cont ID  
Sent By jleahy Date 2021-10-02 Time 11:35 Rev Time 0.00
Received By jleahy Date 2021-10-02 Time 11:28 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-10-02 Cont ID  
Sent By jleahy Date 2021-10-02 Time 11:36 Rev Time 0.00
Received By jleahy Date 2021-10-02 Time 11:36 Sent To  
Notes
2021-10-02 11:36:46VOICE AND DATA ONLY JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-12-16 Cont ID  
Sent By cwalker Date 2021-12-16 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-11-10 Cont ID  
Sent By pleduc Date 2021-11-10 Time   Rev Time 0.00
Received By pleduc Date 2021-11-10 Time 14:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-09-24 Cont ID  
Sent By pleduc Date 2021-09-24 Time   Rev Time 0.00
Received By pleduc Date 2021-09-23 Time 15:29 Sent To  
Notes
2021-09-23 15:49:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) LIFE SAFETY SHEET - WITHIN THE LOBBY THERE IS AN
 INDICATION OF A TABLE/PLANTER WITH CHAIRS DIRECTLY
 OBSTRUCTING A DOUBLE DOOR WITH AN EXIT SIGN LEADING TO
 THE EXTERIOR PATIO.
  
 PLEASE REVIEW AND CORRECT AND PROVIDE A CLEAR PATH OF
 TRAVEL TO THIS EXIT.
  
  
 2) LIFE SAFETY SHEET - WITHIN THE CAFE, THERE IS AN
 INDICATION OF EXIT SIGN OVER A DOUBLE DOOR LEADING TO
 THE EXTERIOR PATIO.
  
 THERE IS NO DIMENSION PROVIDED BETWEEN THE EXIT DOOR
 AND PROPOSED TABLE AND CHAIR LOCATION.
  
 FOR THE REOCORD AND CODE COMPLIANCE PLEASE PROVIDE THAT
 DIMENSION.
  
  
  
 3) MECHANICAL/KITCHEN EQUIPMENTSHEETS - THE PROPSOED
 HOOD AND SUSPRESSION SYSTEMS SHALL BE SUBMITTED UNDER
 SPEARATE PERMITS & SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-12-06 Cont ID  
Sent By lcrespo Date 2021-12-06 Time 12:25 Rev Time 0.00
Received By lcrespo Date 2021-12-06 Time 12:25 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-10-12 Cont ID  
Sent By pvalenti Date 2021-10-12 Time 08:57 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 14:21 Sent To  
Notes
2021-10-12 08:58:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21090948 505 S FLAGLER DR
  
  
 1ST REVIEW
 GAS COMMENTS: DENIED
  
 1.TABLE 402.4(3) FOR 2 PSI SYSTEM IS INCORRECT.
 402.4(3) IS FOR LESS THAN 2 PSI/PD 3LBS/INITIAL SUPPLY
 PRESSURE 8 INCHES OR GREATER WATER COLUMN. SEE TABLE
 402.4(5) FOR 2 PSI/PD 1 LB.
  
 2.REGARDING 8-11 INCHES H20 SYSTEM, PLEASE CLARIFY WHAT
 IS MEANT BY H20. PLEASE NOTE, TABLE 402.4(2) IS FOR
 SYSTEMS LESS THAN 2 PSI/PD 0.5 INCHES WATER COLUMN.
  
 3.PROVIDE GAS EQUIPMENT SCHEDULE INDICATING BTU FOR
 EACH PIECE OF EQUIPMENT. LIST THE BTU LOAD OF EACH
 APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER
 TO THE 2020 FBC FG SECS.401.8, 402.2, AND TABLES 402.4
 (1) THRU 402.4 (37)
  
 4.PER WPB FBC 107.2.1, INDICATE ON THE PLUMBING FIXTURE
 SCHEDULE THE MANUFACTURER OF THE GWH MODEL LT0540H-N.
 PROVIDE MANUFACTURER?S SPECIFICATION/INSTALLATION
 MANUAL FOR THE SAME.
  
 5.PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54
 AND FBC FG 402.2, AND 301.3. GAS APPLIANCES SHALL BE
 LISTED AND LABELED.
  
 6.THE INSTALLATION MANUALS FOR ALL GAS APPLIANCES /
 EQUIPMENT SHALL BE ONSITE AT THE TIME OF INSPECTION PER
 FBC FG 305.1.
  
 7.PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THE EMERGENCY
 HOOD SHOWING COMPLIANCE WITH NFPA 96-17; 10.4 AND 10.5.
 EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE BELOW
 THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE. IN
 LIEU OF A DETAIL, A NOTE MAY BE PROVIDED ADJACENT TO
 THE GAS RISER DIAGRAM STATING PER NFPA 96-17, SECTIONS
 10.4 AND 10.5, EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE
 SHALL BE BELOW THE CEILING. THE MANUAL SHUT OFF VALVE
 SHALL BE UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL
 VALVE.
  
 8.SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE PRESSURE
 REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER
 FBC FG 410.1.
  
 9. P3.1, KEY NOTE 2 CALLS FOR CONNECTION TO EXISTING
 DOMESTIC WATER. THERE IS A GAS CONNECTION POINT ON THE
 PLAN WHICH IS ALSO NOTED AS KEY NOTE 2. PER WPB FBC
 107.2.1, CLARIFY.
  
 10.THE SAME SYMBOL IS SHOWN ON P3.1 AND P5.1 AT THE GAS
 METER LOCATION AND FOR THE EMERGENCY HOOD SHUT
 OFF/ANSUL VALVE. THE SYMBOL CHART ON P0.1 DOES NOT
 IDENTIFY THAT SYMBOL. PER WPB FBC 107.2.1, PLEASE
 CLARIFY.
  
 11.PER WPB FBC 107.2.1, SPECIFY THE MP REGULATORS.;
 PROVIDE AN INSTALLATION DETAIL FOR THE MP REGULATORS.
 SHOW COMPLIANCE WITH
 ?A)FBC FG 409.4, A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR
 ?B)AND 410.2 AS FOLLOWS:
 .....1)THE MP REGULATOR SHALL BE APPROVED AND SHALL BE
 SUITABLE FOR THE INLET AND OUTLET GAS PRESSURES FOR THE
 APPLICATION.
 .....2)THE MP REGULATOR SHALL MAINTAIN A REDUCED OUTLET
 PRESSURE UNDER LOCK-UP (NO-FLOW) CONDITIONS.
 .....3)THE CAPACITY OF THE MP REGULATOR, DETERMINED BY
 PUBLISHED RATINGS OF ITS MANUFACTURER, SHALL BE
 ADEQUATE TO SUPPLY THE APPLIANCES SERVED.
 .....4)THE MP PRESSURE REGULATOR SHALL BE PROVIDED WITH
 ACCESS. WHERE LOCATED INDOORS, THE REGULATOR SHALL BE
 VENTED TO THE OUTDOORS OR SHALL BE EQUIPPED WITH A
 LEAK-LIMITING DEVICE, IN EITHER CASE COMPLYING WITH
 SECTION 410.3.
 .....5)A TEE FITTING WITH ONE OPENING CAPPED OR PLUGGED
 SHALL BE INSTALLED BETWEEN THE MP REGULATOR AND ITS
 UPSTREAM SHUTOFF VALVE. SUCH TEE FITTING SHALL BE
 POSITIONED TO ALLOW CONNECTION OF A PRESSURE-MEASURING
 INSTRUMENT AND TO SERVE AS A SEDIMENT TRAP.
 .....6)A TEE FITTING WITH ONE OPENING CAPPED OR PLUGGED
 SHALL BE INSTALLED NOT LESS THAN 10 PIPE DIAMETERS
 DOWNSTREAM OF THE MP REGULATOR OUTLET. SUCH TEE FITTING
 SHALL BE POSITIONED TO ALLOW CONNECTION OF A
 PRESSURE-MEASURING INSTRUMENT. THE TEE FITTING IS NOT
 REQUIRED WHERE THE MP REGULATOR SERVES AN APPLIANCE
 THAT HAS A PRESSURE TEST PORT ON THE GAS CONTROL INLET
 SIDE AND THE APPLIANCE IS LOCATED IN THE SAME ROOM AS
 THE MP REGULATOR.
 .....7)WHERE CONNECTED TO RIGID PIPING, A UNION SHALL
 BE INSTALLED WITHIN 1 FOOT (304 MM) OF EITHER SIDE OF
 THE MP REGULATOR.
  
 12.PER WPB FBC 107.2.1, SPECIFY MANUAL GAS SHUT OFF
 VALVES. VALVES SHALL COMPLY WITH FBC FG 409.1.1/TABLE
 409.1.1, LISTED IN ACCORDANCE WITH FBC FG 409.4.
  
 13.PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR THE GAS
 METER/REGULATOR SHOWING VALVE(S) AND UNION(S)
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21090948 505 S FLAGLER DR
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-12-20 Time   Rev Time 0.00
Received By aoliver Date 2021-12-15 Time 06:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-06 Cont ID  
Sent By lcrespo Date 2021-12-06 Time 12:25 Rev Time 0.00
Received By lcrespo Date 2021-11-09 Time 07:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-02 Cont ID  
Sent By lmarchan Date 2021-11-02 Time 07:55 Rev Time 0.00
Received By lmarchan Date 2021-09-22 Time 10:44 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-10-22 Cont ID  
Sent By rmcphers Date 2021-10-22 Time 14:02 Rev Time 0.00
Received By rmcphers Date 2021-10-22 Time 14:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-11-16 Cont ID  
Sent By medwards Date 2021-11-16 Time 07:56 Rev Time 0.00
Received By medwards Date 2021-11-16 Time 07:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-01 Cont ID  
Sent By medwards Date 2021-10-01 Time 15:40 Rev Time 0.00
Received By medwards Date 2021-10-01 Time 15:40 Sent To  
Notes
2021-10-01 15:40:561ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21090948
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A NOTE ON THE DRAWINGS INDICATING
 THAT THE HOODS WILL NEED A SEPARATE PERMIT APPLICATION,
 DRAWINGS AND REVIEW AS THEY WILL NOT BE REVIEWED UNDER
 THIS PERMIT.
  
 2) PLEASE PROVIDE A NOTE ON THE DRAWINGS INDICATING
 THAT THE REFRIGERATION SYSTEMS WILL NEED A SEPARATE
 PERMIT APPLICATION, DRAWINGS AND REVIEW AS THEY WILL
 NOT BE REVIEWED UNDER THIS PERMIT.
  
 3) PLEASE SHOW THAT THE RETURN AIR GRILLES IN THE
 KITCHEN ARE AT LEAST 10 FEET AWAY FROM THE COOKING
 APPLIANCES IN THE KITCHEN. FBC M 601.5 EXCEPTION 1
  
 4) PLEASE SHOW THE FIRE DAMPER AT THE WALL OF THE
 ELECTRICAL ROOM WHERE THE BATH EXHAUST DUCT PENETRATES
 THE RATED WALL. FBC M 607
  
 5) PLEASE MAKE SURE THE CURRENT FBC M 2020 EDITION IS
 REFERENCED IN THE OUTDOOR AIR CALCULATIONS.
  
 6) PLEASE EXPLAIN THE RETURN GRILLE IN THE ELECTRICAL
 ROOM.
  
 7) IT APPEARS THAT EF 1 AND EF 2 ARE IN SINGLE STALL
 BATHROOMS. WHY ARE THEY EACH EXHAUSTING 370 CFM? SHEET
 6.1 FAN SCHEDULE INDICATES THAT THERE EXHAUST 370 CFM.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-12-06 Cont ID  
Sent By lcrespo Date 2021-12-06 Time 12:25 Rev Time 0.00
Received By lcrespo Date 2021-12-06 Time 12:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-10-12 Cont ID  
Sent By pvalenti Date 2021-10-12 Time 08:57 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 14:21 Sent To  
Notes
2021-10-12 08:57:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21090948 505 S FLAGLER DR
  
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR
 GREASE INTERCEPTOR PER WPB FBC 105.1 & 107.2.1.
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR NEW TOILET ROOMS INDICATING THE FOLLOWING:
 ...A)CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1. TO BE CLEAR, THIS NEEDS TO BE
 NOTED ON THE PLAN.
 ...B)THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2. TO BE
 CLEAR, THIS NEEDS TO BE NOTED ON THE PLAN.
 ...C)FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
 ...D)THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
 ...E)MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
  
 2. ALS1.1 PLUMBING FIXTURE CALCULATIONS SHALL BE BASED
 ON 2020 FLORIDA PLUMBING CODE, 7TH EDITION. PER WPB FBC
 107.2.1, PLEASE CORRECT.
  
 3. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON
 THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 4. TOILET RM 104 AND 106. P3-1; SHUT OFF VALVES ARE
 ABOVE A HARD CEILING. PER FBC PL 606.3, PROVIDE CEILING
 ACCESS PANELS.
  
 5. PROVIDE DETAIL FOR DISHWASHER NOTED ON A3.03/DETAIL
 10 IN COFFEE ROOM 110. SEE FBC PL 409.4. THE WASTE
 CONNECTION OF A RESIDENTIAL DISHWASHER SHALL CONNECT
 DIRECTLY TO A WYE BRANCH FITTING ON THE TAILPIECE OF
 THE KITCHEN SINK, DIRECTLY TO THE DISHWASHER CONNECTION
 OF A FOOD WASTE DISPOSER, OR THROUGH AN AIR BREAK TO A
 STANDPIPE. THE WASTE LINE OF A RESIDENTIAL DISHWASHER
 SHALL RISE AND BE SECURELY FASTENED TO THE UNDERSIDE OF
 THE SINK RIM OR COUNTER TOP.
  
 6. PER FBC PL 604.9, A WATER HAMMER ARRESTOR IS
 REQUIRED AT THE DISHWASHER.
  
 7. IN-LINE CHECK VALVES AT WATER CONNECTIONS TO COFFEE
 MAKER, ICE MAKERS ARE NOT BACKFLOW PREVENTERS. PER WPB
 FBC 107.2.1, SPECIFY LEAD FREE BACKFLOW PREVENTERS
 COMPLYING WITH FBC PL 608.1. DUAL CHECK VALVE/ ASSE
 1024 ARE ACCEPTABLE.
  
 8. P0.1 DETAIL FOR TEMPERED AND COLD WATER SUPPLY TO
 PUBLIC LAVATORIES LEONARD 170-LF-BRKT IS A POINT OF USE
 VALVE AND SHALL ONLY SUPPLY ONE LAVATORY. PER WPB FBC
 107.2.1, DELETE NOTE STATING IT CAN SUPPLY UP TO FIVE
 PUBLIC LAVATORIES.
  
 9. P0.1 DETAIL FOR ABOVE CEILING INSTANTANEOUS WATER
 HEATER IS NOT REFLECTED ON THE PLUMBING RISER DIAGRAM
 ON P5.1. PER WPB FBC 107.2.1, CLARIFY AND RECONCILE.
  
 10. PER WPB FBC 107.2.1, INDICATE ON THE PLUMBING
 FIXTURE SCHEDULE THE MANUFACTURER OF THE GWH MODEL
 LT0540H-N. PROVIDE MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL FOR THE SAME.
  
 11. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR SUPPORT OF
 WALL MOUNTED WATER HEATER.
  
 12. RE: P5.1 SANITARY RISER DIAGRAM. FLOOR SINKS AND
 TRENCH DRAIN FIXTURE DRAINS SHALL BE PROVIDED WITH A
 WATER SEAL TRAP PER FBC PL 1002.1 PER WPB FBC 107.2.1,
 PROVIDE TRAPS ON THE SANITARY RISER DIAGRAM.. TRAPS
 SHALL ALL BE VENTED IN ACCORDANCE WITH FBC PL CHAPTER
 9.
  
 13. PER WPB FBC 107.2.1, INDICATE ON THE PLANS HOW THE
 TRAP SEAL FOR THE TRENCH DRAIN TRAPS ARE TO BE
 PROTECTED. SHOW COMPLIANCE WITH ONE OF THE METHODS
 DESCRIBED IN FBC PL 1002.4.1.1 THROUGH 1002.4.1.4.
  
 14. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 15. P3.1: ITEM 38, OVEN-STEAMER COMBINATION; PER WPB
 FBC 107.2.1, IDENTIFY ON PLAN. SPECIFY AND PROVIDE
 BACKFLOW PREVENTER PER FBC PL 608.1
  
 16. P3.1: ITEM 32; WAREWASHER. SPECIFY AND PROVIDE
 BACKFLOW PREVENTER PER FBC PL 608.1
  
 17. PER WPB FBC 107.2.1, RECIRC PUMP SCHEDULE & DETAIL;
 INCLUDE HP, ELECTRICAL CHARACTERISTICS, GPM, VALVES,
 ETC.
  
 18. PER WPB FBC 107.2.1, PROVIDE WATER SIZING
 CALCULATIONS. PROVIDE TABLE WITH FIXTURES AND EQUIPMENT
 SHOWING WSFU BREAKDOWN FOR COLD AND HOT WATER/GPM
 TOTALS
  
 19. PER WPB FBC 107.2.1, SANITARY PIPING SIZING
 CALCULATIONS. PROVIDE TABLE WITH FIXTURES/DRAINS AND
 SHOWING DFU BREAKDOWN AND TOTALS
  
 20. PER WPB FBC 107.2.1, GREASY WASTE PIPING SIZING
 CALCULATIONS. PROVIDE TABLE WITH FIXTURES/DRAINS AND
 SHOWING DFU BREAKDOWN AND TOTALS.
  
 21. PER WPB FBC 107.2.1, PROVIDE NOTE ON P5.1 ADJACENT
 TO SANITARY RISER DIAGRAM STATING FLOOR DRAINS, FLOOR
 SINKS AND TRENCH DRAINS ARE VENTED IN ACCORDANCE WITH
 FBC PL SECTION 915 COMBINATION WASTE AND VENT SYSTEM
  
 22. P2.1 APPEARS TO INDICATE A VERTICAL PIPE LOCATED
 BETWEEN THE TWO MOST UPSTREAM SINKS IN THE GREASY WASTE
 SYSTEM. P5.1 SANITARY RISER DIAGRAM DOES NOT SHOW THIS.
 PER WPB FBC 107.2.1, CLARIFY AND RECONCILE.
  
 23. PER WPB FBC 107.2.1, INDICATE AND SIZE THE MAIN
 VERTICAL VENT THAT PROVIDED IN ACCORDANCE WITH FBC PL
 915.2.3 AND 915.2.4. SAID VENT SHALL BE CONNECTED TO
 FULL SIZE BRANCH.
  
 24. P5.1, KEY NOTE 3 CALLS FOR NEW WATER METER AND
 BACKFLOW PREVENTER. P3.1, KEY NOTE 2 CALLS FOR
 CONNECTION TO EXISTING DOMESTIC WATER. PER WPB FBC
 107.2.1, CLARIFY AND RECONCILE.
  
 25. RE: COMMENT 24. PER WPB FBC 107.2.1, PROVIDE A
 DETAIL FOR THE APPLICABLE CONNECTION; INCLUDE ALL
 APPLICABLE METERS, BACKFLOW PREVENTERS AND VALVES.
  
 26. P3.1, KEY NOTE 2 CALLS FOR CONNECTION TO EXISTING
 DOMESTIC WATER. THERE IS A GAS CONNECTION POINT ON THE
 PLAN WHICH IS ALSO NOTED AS KEY NOTE 2. PER WPB FBC
 107.2.1, CLARIFY.
  
 27. P5.1, KEY NOTE 1 INDICATES EFFLUENT FROM GREASE
 INTERCEPTOR IS TO CONNECT TO EXISTING SEWER LATERAL;
 KEY NOTE 2 APPEARS TO SAY CONNECT NEW GREASY WASTE TO
 AN EXISTING INTERCEPTOR WITHOUT ACTUALLY STATING IT.
 PER WPB FBC 107.2.1, PLEASE CLARIFY. IS THIS A NEW
 INSTALLATION OR IS THE INTERCEPTOR EXISTING?
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21090948 505 S FLAGLER DR
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-01-04 Cont ID  
Sent By rmcphers Date 2022-01-04 Time 13:49 Rev Time 0.00
Received By rmcphers Date 2022-01-04 Time 13:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-12-20 Cont ID  
Sent By ccole Date 2021-12-20 Time 15:04 Rev Time 0.00
Received By ccole Date 2021-12-20 Time 15:04 Sent To  
Notes
2021-12-20 15:09:443RD SIGNATURE REVIEW
 12/20/21
  
 PLAN REVIEW RESULTS- DENIED.
  
 1) SHEETS P0.1, P2.1, P3.1, & P6.1 ARE NOT DIGITALLY
 SIGNED AND SEALED BY THE ENGINEER OF RECORD- FL.
 STATUTE 471.025, AND SECTION 61G15-23.005 FAC.
  
 2) THE PREVIOUS REVIEW COMMENT REQUESTING THE HOOD
 DRAWINGS TO BE DIGITALLY SIGNED AND SEALED STILL
 EXISTS. FIRE DRAWINGS APPROVED.
  
 ALL OF THE FIRE DRAWINGS AND HOOD DRAWINGS DO NOT SHOW
 AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-11-17 Cont ID  
Sent By rmcphers Date 2021-11-17 Time 14:55 Rev Time 0.00
Received By rmcphers Date 2021-11-17 Time 14:55 Sent To  
Notes
2021-11-17 14:56:05SIGNATURE REVIEW
  
 ALL OF THE FIRE DRAWINGS AND HOOD DRAWINGS DO NOT SHOW
 AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-10-22 Cont ID  
Sent By rmcphers Date 2021-10-22 Time 14:12 Rev Time 0.00
Received By rmcphers Date 2021-10-22 Time 14:12 Sent To  
Notes
2021-10-22 14:14:45SIGNATURE REVIEW
  
 ALL OF THE FIRE DRAWINGS AND HOOD DRAWINGS DO NOT SHOW
 AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2021-11-01 Cont ID  
Sent By aaponte Date 2021-11-01 Time 12:00 Rev Time 0.00
Received By ckimmerl Date 2021-11-01 Time 12:00 Sent To  
Notes
***NONE***