Plan Review Details - Permit 21090848
Plan Review Stops For Permit 21090848
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-10-06 Cont ID  
Sent By jwitmer Date 2021-10-06 Time 15:41 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-10-06 15:41:37TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-06 Cont ID  
Sent By jwitmer Date 2021-10-06 Time 15:41 Rev Time 0.00
Received By jwitmer Date 2021-10-06 Time 15:29 Sent To  
Notes
2021-10-06 15:40:52WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21090848
 ADD: 1551 N FLAGLER DR. # 615
 CONT: APV BUILDERS & ENGINEERING LLC
 TEL: 561-708-0776
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 06TH/2021
 ACTION: DENIED
  
 1) PLANS DRAWN BY CONTRACTORS NEED TO SHOW COMPLIANCE
 WITH: CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE
 CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF
 PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) ELEVATION SHEET OF BATHROOMS STATES THAT BATHTUB TO
 BE REMOVED (2) BATHROOMS. DOES THIS MEAN THE TUB IS
 GOING TO BE REMOVED AND TURNED INTO A SHOWER?
 ADDITIONAL INFORMATION IS REQUIRED, 107.2.1. 2020 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 107.2.1.
 W.P.B. ADMINISTRATIVE CODE/2020 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-09-23 Cont ID  
Sent By pleduc Date 2021-09-23 Time   Rev Time 0.00
Received By pleduc Date 2021-09-23 Time 13:14 Sent To  
Notes
2021-09-23 13:16:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO FLOOR PLAN SHOWING THE LOCATIONS OF THE
 BATHROOMS.
  
 FOR THE RECORD, PLEASE PROVIDE A FLOOR PLAN INDICATING
 THE LOCATIONS OF THE BATHROOMS.
  
  
 1A) THERE ARE NO INDICATIONS THAT ANY OF THE BATHROOM
 WALLS ARE FIRE RATED TENANT SEPARATION WALLS.
  
 ENSURE FIRE RATED TENANT SEPARATION WALLS ARE REPAIRED
 TO THE EXISTING FIRE RATED SEPARATION.
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT.
  
  
  
 2) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-07 Cont ID  
Sent By lcrespo Date 2021-10-07 Time 15:47 Rev Time 0.00
Received By lcrespo Date 2021-09-22 Time 11:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-10-12 Cont ID  
Sent By lcrespo Date 2021-10-07 Time 15:45 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 14:24 Sent To  
Notes
2021-10-12 09:11:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21090848 1551 N FLAGLER DR 615
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.PLANS ARE UNCLEAR AS TO A SCOPE OF WORK. PER WPB FBC
 107.2.1, PROVIDE
 ?A) COMPLETE SCOPE OF WORK
 ?B) DEMO FLOOR PLAN OF THE UNIT
 ?C) PROPOSED FLOOR PLAN OF THE UNIT
 ?D) A PLUMBING FLOOR PLAN; IF THE PLANS ARE NOT SIGNED
 AND SEALED BY A PROFESSIONAL ENGINEER OR ARCHITECT, THE
 PLUMBING PLAN IN ACCORDANCE WITH WPB FBC 107.3.4.3
 SHALL BEAR THE PRINTED NAME, THE SIGNATURE AND THE
 CERTIFICATION NUMBER OF THE DESIGNER WHO SHALL BE A
 CONTRACTOR LICENSED IN THAT TRADE.
  
 2. IF TUBS ARE REPLACED WITH SHOWERS THEN PER WPB FBC
 107.2.1, PROVIDE ON THE REQUIRED DESIGNATED PLUMBING
 PLAN, PROVIDE THE FLOOR PLAN, WORK DESCRIPTION AND A
 SHOWER WALL/DRAIN AND THRESHOLD DETAIL
 ...A) PROVIDE A SHOWER WALL/DRAIN AND THRESHOLD DETAIL
 SHOWING THE FOLLOWING INFORMATION SHOWING COMPLIANCE
 WITH FBC PL 421
 .........1) FBC PL 421.3 WASTE OUTLETS SERVING SHOWERS
 SHALL BE NOT LESS THAN 1-1/2 INCHES (38 MM) IN DIAMETER
 AND, FOR OTHER THAN WASTE OUTLETS IN BATHTUBS, SHALL
 HAVE REMOVABLE STRAINERS NOT LESS THAN 3 INCHES (76 MM)
 IN DIAMETER WITH STRAINER OPENINGS NOT LESS THAN 1/4
 INCH (6.4 MM) IN LEAST DIMENSION. WHERE EACH SHOWER
 SPACE IS NOT PROVIDED WITH AN INDIVIDUAL WASTE OUTLET,
 THE WASTE OUTLET SHALL BE LOCATED, AND THE FLOOR
 PITCHED SO THAT WASTE FROM ONE SHOWER DOES NOT FLOW
 OVER THE FLOOR AREA SERVING ANOTHER SHOWER. WASTE
 OUTLETS SHALL BE FASTENED TO THE WASTE PIPE IN AN
 APPROVED MANNER.
 .........2) FBC PL 421.4.1 BATHTUB FLOORS, SHOWER
 FLOORS, WALL AREAS ABOVE BUILT-IN TUBS THAT HAVE
 INSTALLED SHOWER HEADS AND WALLS IN SHOWER COMPARTMENTS
 SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND
 NONABSORBENT WATERPROOF MATERIALS. WALL MATERIALS SHALL
 EXTEND TO A HEIGHT OF NOT LESS THAN 6 FEET (1829 MM)
 ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES
 (1778 MM) ABOVE THE DRAIN OF THE TUB OR SHOWER. SUCH
 WALLS SHALL FORM A WATER-TIGHT JOINT WITH EACH OTHER
 AND WITH EITHER THE TUB OR SHOWER FLOOR.
 .........3) FBC PL 421.5 FLOOR SURFACES SHALL BE
 CONSTRUCTED OF IMPERVIOUS, NONCORROSIVE, NONABSORBENT
 AND WATERPROOF MATERIALS.
 .........4) FBC PL 421.5.1 FLOORS OR RECEPTORS UNDER
 SHOWER COMPARTMENTS SHALL BE LAID ON, AND SUPPORTED BY,
 A SMOOTH AND STRUCTURALLY SOUND BASE.
 .........5) FBC PL 421.5.2 FLOORS UNDER SHOWER
 COMPARTMENTS, EXCEPT WHERE PREFABRICATED RECEPTORS HAVE
 BEEN PROVIDED, SHALL BE LINED AND MADE WATER-TIGHT
 UTILIZING MATERIAL COMPLYING WITH SECTIONS 421.5.2.1
 THROUGH 421.5.2.6 (SEE BELOW). SUCH LINERS SHALL TURN
 UP ON ALL SIDES NOT LESS THAN 2 INCHES (51 MM) ABOVE
 THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE RECESSED
 AND FASTENED TO AN APPROVED BACKING SO AS NOT TO OCCUPY
 THE SPACE REQUIRED FOR WALL COVERING AND SHALL NOT BE
 NAILED OR PERFORATED AT ANY POINT LESS THAN 1 INCH (25
 MM) ABOVE THE FINISHED THRESHOLD. LINERS SHALL BE
 PITCHED ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE
 FIXTURE DRAINS AND BE SECURELY FASTENED TO THE WASTE
 OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT
 JOINT BETWEEN THE LINER AND THE OUTLET. THE COMPLETED
 LINER SHALL BE TESTED IN ACCORDANCE WITH SECTION 312.9.
 .........5A) FBC PL 421.5.2.1 PLASTICIZED POLYVINYL
 CHLORIDE (PVC) SHEETS SHALL MEET THE REQUIREMENTS OF
 ASTM D4551. SHEETS SHALL BE JOINED BY SOLVENT WELDING
 IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
 .........5B) FBC PL 421.5.2.2 NON-PLASTICIZED
 CHLORINATED POLYETHYLENE SHEET SHALL MEET THE
 REQUIREMENTS OF ASTM D4068. THE LINER SHALL BE JOINED
 IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
 .........5C) FBC PL 421.5.2.3 SHEET LEAD SHALL WEIGH
 NOT LESS THAN 4 POUNDS PER SQUARE FOOT (19.5 KG/M2) AND
 SHALL BE COATED WITH AN ASPHALT PAINT OR OTHER APPROVED
 COATING. THE LEAD SHEET SHALL BE INSULATED FROM
 CONDUCTING SUBSTANCES OTHER THAN THE CONNECTING DRAIN
 BY 15-POUND (6.80 KG) ASPHALT FELT OR AN EQUIVALENT.
 SHEET LEAD SHALL BE JOINED BY BURNING.
 .........5D) FBC PL 421.5.2.4 SHEET COPPER SHALL
 CONFORM TO ASTM B152 AND SHALL WEIGH NOT LESS THAN 12
 OUNCES PER SQUARE FOOT (3.7 KG/M2). THE COPPER SHEET
 SHALL BE INSULATED FROM CONDUCTING SUBSTANCES OTHER
 THAN THE CONNECTING DRAIN BY 15-POUND (6.80 KG) ASPHALT
 FELT OR AN EQUIVALENT. SHEET COPPER SHALL BE JOINED BY
 BRAZING OR SOLDERING.
 .........5E) FBC PL 421.5.2.5 SHEET-APPLIED, LOAD
 BEARING, BONDED, WATERPROOF MEMBRANES SHALL MEET
 REQUIREMENTS OF ANSI A118.10 AND SHALL BE APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
 .........5F) FBC PL 421.5.2.6L LIQUID-TYPE,
 TROWEL-APPLIED, LOAD BEARING, BONDED WATERPROOF
 MATERIALS SHALL MEET THE REQUIREMENTS OF ANSI A118.10
 AND SHALL BE APPLIED IN ACCORDANCE WITH THE
 MANUFACTURER'S INSTRUCTIONS.
  
 3.PER FBC PL 412.3, ALL NEW IN-WALL TUB/SHOWER
 COMBINATION VALVES SHALL BE BALANCED-PRESSURE,
 THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE. SHOWER AND TUB-SHOWER
 COMBINATION VALVES REQUIRED BY THIS SECTION SHALL BE
 EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF
 THE VALVE TO 120?F (49?C), WHICH SHALL BE FIELD
 ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 UTILIZED FOR COMPLIANCE WITH THIS SECTION.
  
 4. PER FBC PL 412.5, THE HOT WATER SUPPLIED TO BATHTUBS
 AND WHIRLPOOL BATHTUBS SHALL BE LIMITED TO A MAXIMUM
 TEMPERATURE OF 120?F (49?C) BY A WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3, EXCEPT WHERE SUCH PROTECTION IS OTHERWISE
 PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN
 ACCORDANCE WITH SECTION 412.3.
  
 END OF COMMENTS.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS
 FROM THE PRIOR REVIEW.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21090848 1551 N FLAGLER DR 615
  
  
  
2021-10-07 15:46:58REVIEW DONE BY JERRY SMITH

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-10-07 Cont ID  
Sent By lcrespo Date 2021-10-07 Time 15:46 Rev Time 0.00
Received By lcrespo Date 2021-10-07 Time 15:46 Sent To  
Notes
***NONE***