Plan Review Details - Permit 21090716
Plan Review Stops For Permit 21090716
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-10-22 Cont ID  
Sent By rmcdouga Date 2021-10-22 Time 09:05 Rev Time 0.00
Received By rmcdouga Date 2021-10-22 Time 09:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-10-20 Cont ID  
Sent By cthroop Date 2021-10-20 Time 07:08 Rev Time 0.00
Received By cthroop Date 2021-10-20 Time 07:01 Sent To  
Notes
2021-10-20 07:27:29ROOFING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SYSTEM W-84 HAS BEEN SELECTED FROM PRODUCT APPROVAL
 FL2533-R25. THE DESIGN PRESSURE OF -105.0 DOES NOT MEET
 OR EXCEED THE DESIGN PRESSURE OF THE ROOF PER FBC R
 CHPT 3.
 PER TABLE R301.2 (2), THE DESIGN PRESSURE OF THE ROOF
 IS -89.4. A COEFFICIENT OF 1.21 MUST BE APPLIED BASED
 ON VULT OF 170MPH AND EXPOSURE C PER TABLE R301.2 (3).
 THIS CALCULATION DETERMINES THE DESIGN PRESSUTRE OF THE
 ROOF TO BE -108.2.
 EITHER PROVIDE ENHANCED FASTENER CALCULATIONS, PER
 LIMITATIONS NOTE 5.6.1, OF THE PRODUCT APPROVAL OR
 CHOOSE ANOTHER SYSTEM THAT MEETS OR EXCEEDS THE DESIGN
 PRESSURE OF THE ROOF (-108.3).
  
 2. WHEN SUBMITTING DOCUMENTS FOR REVIEW, UPLOAD THE
 COMPLETE NOA OR PRODUCT APPROVAL FOR REVIEW. WE CANNOT
 REPLACE A SINGLE PAGE OF AN NOA OR PRODUCT APPROVAL.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-30 Cont ID  
Sent By rmcdouga Date 2021-09-30 Time 17:38 Rev Time 0.00
Received By rmcdouga Date 2021-09-30 Time 17:38 Sent To  
Notes
2021-09-30 17:38:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE W-79 ROOFING SYSTEM THAT YOU SELECTED ON PAGE 15
 OF THE CERTAINTEED PRODUCT APPROVAL HAS A MAXIMUM
 DESIGN PRESSURE OF -60 PSF. THIS IS NOT ADEQUATE FOR
 THE PERIMETER AND CORNER AREAS FOR THIS PROJECT. THE
 WIND SPEED IS 170 MPH VULT AND THE EXPOSURE CATEGORY IS
 C. SUBMIT SIGNED AND SEALED ENHANCED FASTENING
 CALCULATIONS IF ALLOWED BY THE PRODUCT APPROVAL OR
 SELECT ANOTHER SYSTEM. FBC-R301

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-10-22 Cont ID  
Sent By rmcdouga Date 2021-10-22 Time 09:05 Rev Time 0.00
Received By rmcdouga Date 2021-10-21 Time 13:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-20 Cont ID  
Sent By cthroop Date 2021-10-20 Time 07:27 Rev Time 0.00
Received By cthroop Date 2021-10-07 Time 07:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-30 Cont ID  
Sent By rmcdouga Date 2021-09-30 Time 17:38 Rev Time 0.00
Received By rmcdouga Date 2021-09-28 Time 12:07 Sent To  
Notes
***NONE***