Plan Review Details - Permit 21090582
Plan Review Stops For Permit 21090582
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2022-05-07 Cont ID  
Sent By cpuell Date 2022-05-07 Time 10:51 Rev Time 0.00
Received By cpuell Date 2022-05-07 Time 10:51 Sent To  
Notes
2022-05-07 10:51:38PARCELS MERGED TO CREATE A SINCE PARCEL
 74434322360033110 WITH THE ADDRESS OF 101 N CLEMATIS ST
 312, UPDATED PERMIT.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-04-17 Cont ID  
Sent By cpuell Date 2022-04-17 Time 09:25 Rev Time 0.00
Received By cpuell Date 2022-04-17 Time 09:25 Sent To  
Notes
2022-04-17 09:25:15PREVIOUS COMMENTS NOT ADDRESSED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-09-13 Cont ID  
Sent By cpuell Date 2021-09-13 Time 17:12 Rev Time 0.00
Received By cpuell Date 2021-09-13 Time 17:12 Sent To  
Notes
2021-09-13 17:14:19SCOPE OF WORK INDICATES THAT TWO UNITS ARE AFFECTED 311
 & 312, YOU WILL NEED TO CONTACT VINCE NOEL
 [email protected] OR CALL 561-494-1040 TO START THE UNITY
 OF TITLE PROCEDURE. CURRENTLY THERE ARE TWO SEPARATE
 PCNS FOR THE TWO UNITS, A SINGLE PCN MUST BE ISSUED BY
 THE COUNTY. ONCE YOU HAVE RECEIVED THE SINGLE PCN AFTER
 DOING THE UNITY OF TITLE AND THEN CONTACTING THE
 PROPERTY APPRAISERS AND ISSUED A SINGLE PROPERTY
 CONTROL NUMBER (PCN) PLEASE CONTACT [email protected] OR
 CALL 561-805-6659 TO BE ISSUED AN ADDRESS.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-05-03 Cont ID  
Sent By rmcphers Date 2022-05-03 Time 16:12 Rev Time 0.00
Received By rmcphers Date 2022-05-03 Time 16:12 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-10-16 Cont ID  
Sent By shill Date 2021-10-16 Time 09:44 Rev Time 0.00
Received By shill Date 2021-10-16 Time 09:44 Sent To  
Notes
2021-10-16 09:44:51AN ASBESTOS SURVEY WAS PROVIDED; THIS DOCUMENT HAS BEEN
 LOCKED AND IS NOT NEEDED FOR THIS BUILDING PERMIT.
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-05-10 Cont ID  
Sent By rmcphers Date 2022-05-10 Time 08:15 Rev Time 0.00
Received By rmcphers Date 2022-05-10 Time 08:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-05-03 Cont ID  
Sent By rmcphers Date 2022-05-03 Time 16:12 Rev Time 0.00
Received By rmcphers Date 2022-05-03 Time 16:12 Sent To  
Notes
2022-05-03 16:12:34INTERIOR DEMO
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) A UNITY OF TITLE IS REQUIRED TO REMOVE THE TENNANT
 SEPARATION WALL. FBC 420.2 SEPARATION WALLS.
 WALLS SEPARATING DWELLING UNITS IN THE SAME BUILDING,
 WALLS SEPARATING SLEEPING UNITS IN THE SAME BUILDING
 AND WALLS SEPARATING DWELLING OR SLEEPING UNITS FROM
 OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME
 BUILDING SHALL BE CONSTRUCTED AS FIRE PARTITIONS IN
 ACCORDANCE WITH SECTION 708.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-16 Cont ID  
Sent By shill Date 2021-10-16 Time 09:42 Rev Time 0.00
Received By shill Date 2021-10-16 Time 09:42 Sent To  
Notes
2021-10-16 09:44:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107 SCOPE NOT CLEAR. IT APPEARS THAT APPLICANT
 PROPOSES TO REMOVE A RATED DOOR IN THE RATED CORRIDOR.
 REMOVE FROM THE SCOPE AS THIS AFFECTS THE LIFE SAFETY
 OF OTHER UNITS.
  
 2. FBC 107 SCOPE NOT CLEAR. IT APPEARS THAT A FIRE
 RATED WALL IS BEING REMOVED. REVISE PLAN TO CLARIFY
 THAT TWO UNITS ARE BEING COMBINED, OR REMOVE THIS FROM
 SCOPE OF WORK AND SUBMIT A SECOND PERMIT SO YOU HAVE
 ONE INTERIOR DEMO PERMIT FOR EACH UNIT.
  
 3. IF YOU WISH TO COMBINE THE UNITS, PLEASE CONTACT THE
 ENGINEERING DEPARTMENT REGARDING A UNITY OF TITLE.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-05-05 Cont ID  
Sent By jleahy Date 2022-05-05 Time 09:48 Rev Time 0.00
Received By jleahy Date 2022-05-05 Time 09:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-04-22 Cont ID  
Sent By jleahy Date 2022-04-22 Time 13:25 Rev Time 0.00
Received By jleahy Date 2022-04-22 Time 13:24 Sent To  
Notes
2022-04-22 13:26:13WEST PALM BEACH PLAN REVIEW NEEDS AN ELECTRICAL PERMIT
 APPLICATION FOR APPROVAL. PLEASE EMAIL THE ELECTRICAL
 PERMIT APPLICATION TO [email protected], [email protected], AND
 [email protected] SO WE RECEIVE IT ALSO.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-10-20 Cont ID  
Sent By jleahy Date 2021-10-20 Time 13:48 Rev Time 0.00
Received By jleahy Date 2021-10-20 Time 13:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-04-18 Cont ID  
Sent By pleduc Date 2022-04-18 Time   Rev Time 0.00
Received By pleduc Date 2022-04-18 Time 10:17 Sent To  
Notes
2022-04-18 10:19:11FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ALL FIRE SPRINKLER & FIRE ALARM WORK. INCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-10-19 Cont ID  
Sent By pleduc Date 2021-10-19 Time   Rev Time 0.00
Received By pleduc Date 2021-10-19 Time 12:04 Sent To  
Notes
2021-10-19 12:04:48FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ALL FIRE SPRINKLER & FIRE ALARM WORK. INCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-05-10 Cont ID  
Sent By rmcphers Date 2022-05-10 Time 08:15 Rev Time 0.00
Received By rmcphers Date 2022-05-09 Time 14:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-03 Cont ID  
Sent By rmcphers Date 2022-05-03 Time 16:13 Rev Time 0.00
Received By rmcphers Date 2022-04-15 Time 09:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-20 Cont ID  
Sent By jleahy Date 2021-10-20 Time 13:54 Rev Time 0.00
Received By jleahy Date 2021-10-04 Time 12:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-03 Cont ID  
Sent By rmcphers Date 2022-05-03 Time 16:13 Rev Time 0.00
Received By rmcphers Date 2022-05-03 Time 16:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-10-16 Cont ID  
Sent By shill Date 2021-10-16 Time 09:46 Rev Time 0.00
Received By shill Date 2021-10-16 Time 09:46 Sent To  
Notes
***NONE***