Plan Review Details - Permit 21090534
Plan Review Stops For Permit 21090534
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-10-20 Cont ID  
Sent By cthroop Date 2021-10-20 Time 14:23 Rev Time 0.00
Received By cthroop Date 2021-10-20 Time 14:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-10 Cont ID  
Sent By shill Date 2021-10-10 Time 08:55 Rev Time 0.00
Received By shill Date 2021-10-10 Time 08:55 Sent To  
Notes
2021-10-10 08:56:37****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. REVISE THE PLAN TO SHOW THAT DOOR #4 (ELECTRIC ROOM)
 IS NOT REQUIRED TO HAVE PANIC DEVICES, FBC B 1010.1.10,
 OR REVISE SUBMITTAL TO PROPOSE PANIC DEVICES ON THIS
 PAIR OF DOORS:
  
 ELECTRICAL ROOMS WITH EQUIPMENT RATED 1,200 AMPERES OR
 MORE AND OVER 6 FEET (1829 MM) WIDE, AND THAT CONTAIN
 OVERCURRENT DEVICES, SWITCHING DEVICES OR CONTROL
 DEVICES WITH EXIT OR EXIT ACCESS DOORS, SHALL BE
 EQUIPPED WITH PANIC HARDWARE OR FIRE EXIT HARDWARE. THE
 DOORS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL.
  
 2. FOR DOORS 2, 5, AND 6 - REVISE PLAN TO CLARIFY THAT
 THESE DOORS ARE NOT PART OF THE MEANS OF EGRESS FOR
 ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD OF 50 OR MORE,
 FBC B 1010.1.10, OR REVISE SUBMITTAL TO PROPOSE PANIC
 HARDWARE:
  
 SWINGING DOORS SERVING . . . ROOMS OR SPACES WITH AN
 OCCUPANT LOAD OF 50 OR MORE IN A GROUP A ... OCCUPANCY
 SHALL NOT BE PROVIDED WITH A LATCH OR LOCK OTHER THAN
 PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-10-12 Cont ID  
Sent By cwalker Date 2021-10-12 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-20 Cont ID  
Sent By cthroop Date 2021-10-20 Time 14:24 Rev Time 0.00
Received By cthroop Date 2021-10-18 Time 13:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-13 Cont ID  
Sent By lmarchan Date 2021-10-13 Time 09:04 Rev Time 0.00
Received By lmarchan Date 2021-09-17 Time 10:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-20 Cont ID  
Sent By cthroop Date 2021-10-20 Time 14:23 Rev Time 0.00
Received By cthroop Date 2021-10-20 Time 14:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-10-10 Cont ID  
Sent By shill Date 2021-10-10 Time 08:49 Rev Time 0.00
Received By shill Date 2021-10-10 Time 08:49 Sent To  
Notes
2021-10-10 08:52:28SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A SIGNED
 PLAN IS NOT CONSIDERED AN ORIGINAL.
  
 THE WIND LOAD ENGINEERING PREPARED BY SPENCER LEDGARD,
 PE IS NOT DIGITALLY SIGNED; IT APPEARS TO BE A SCAN OF
 A (HAND) SIGNED AND SEALED DOCUMENT.
  
 EITHER UPLOAD DIGITALLY OR ELECTRONICALLY SIGNED
 ENGINEERINGG WITH YOUR RESUBMITTAL (IF APPLICABLE) AND
 COMPLETE THE UPLOAD TASK IN PROJECTDOX, OR YOU CAN
 SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER ORIGINAL
 WITH A WET SIGNATURE TO THE BUILDING DIVISION.
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
  