2021-11-23 11:15:02 | RESIDENTIAL (R3) SHUTTERS, SECOND BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21090525 |
| |
| NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| SHALL COMPLY WITH THE MATERIALS AND METHODS |
| REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| |
| ORIGINAL COMMENT: |
| 1- PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE AS |
| REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE |
| DEBRIS IMPACT PROTECTION FOR THE FLORIDA BUILDING CODE. |
| SEE CITY SAMPLE. ALL THE COLUMNS NEED TO BE COMPLETED. |
| ALTERNATIVELY, YOU MAY PROVIDE COMPLETE INSTALLATION |
| SCHEDULE IN ANY OTHER FORMAT AS LONG AS ALL THE |
| REQUIRED INFORMATION IS PROVIDED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| RESPONSE: |
| BASED ON SHUTTERS PRODUCT APPROVAL FL12549-R7 THE |
| INSTALLATION SCHEDULE NEEDS TO BE REVISED. SEC. 107.2.1 |
| CITY AMENDMENTS: |
| A) 2" ITW TAPCON DOESN'T PROVIDE 1-3/4" EMBEDMENT INTO |
| CONCRETE AS REQUIRED BY ANCHOR SCHEDULE ON SHEET 11 OF |
| 12. |
| B) DESIGN PRESSURES DON'T MATCH THOSE SHOWN ON THE |
| DESIGN PRESSURES CHART SUBMITTED. |
| NOTE: BASED ON THE DESIGN PRESSURES CHART SUBMITTED |
| NEED TO USE THE 60PSF DESIGN PRESSURES TO DETERMINE THE |
| ANCHOR SPACING. |
| C) BOTTOM OF OPENING IS CONCRETE BLOCK. NEED TO USE THE |
| CONCRETE BLOCK ANCHOR SCHEDULE. REVISE ANCHOR SPACING |
| AS REQUIRED. |
| NOTE: BASED ON ON THE ANCHOR SCHEDULE ON SHEET 12 OF 12 |
| IT LOOKS LIKE THE 1/4" ITW TAPCON CAN NOT BE USED. |
| REVISE AS REQUIRED. NEED TO USE ANOTHER FASTENER TYPE. |
| |
| NOTE: |
| MINIMUM EDGE DISTANCE EXCLUDES STUCCO FINISH. |
| |