| 21090359 801 S OLIVE AVE 104 |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| 1.PER WPB FBC 104.1, A PLUMBING SUB-PERMIT APPLICATION |
| SHALL BE SUBMITTED FOR THIS PROJECT BY A LICENSED |
| PLUMBING CONTRACTOR. |
| |
| 2.PER WPB FBC 107.2.1, A PLUMBING PLAN IS REQUIRED. |
| ?A) IF THE PLANS ARE NOT SIGNED AND SEALED BY A |
| PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN |
| IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR THE |
| PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION |
| NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR |
| LICENSED IN THE PLUMBING TRADE (SAID PLAN/PLANS MAY BE |
| A COPY OF THE ORIGINAL SUBMITTED PLANS TITLED PLUMBING |
| FIRST FLOOR/PLUMBING SECOND FLOOR). PLEASE NOTE THAT |
| WHEN SCANNED DRAWINGS ARE SUBMITTED WITH CONTRACTOR'S |
| PRINTED NAME, SIGNATURE AND LICENSE NUMBER IN |
| ACCORDANCE WITH WPB FBC 107.3.4.3, A PAPER PLAN WITH |
| WET SIGNATURE SHALL BE PROVIDED TO THE BUILDING |
| DEPARTMENT FOR HARD RECORD FILE PRIOR TO ISSUANCE OF A |
| PERMIT. |
| ?B) PER WPB FBC 107.2.1, PROVIDE AN EXISTING FLOOR PLAN |
| AND A PROPOSED FLOOR PLAN. CLEARLY INDICATE THE |
| PLUMBING SCOPE AND ANY CHANGES FROM THE EXISTING TO THE |
| PROPOSED. |
| ?C) PER WPB FBC 107.2.1, PROVIDE SHOWER PAN AND CURB |
| DETAIL PROVIDING THE FOLLOWING REQUIREMENTS NOTED IN |
| FBC PL 421.5.2. LINER SHALL TURN UP ON ALL SIDES NOT |
| LESS THAN 2 INCHES (51 MM) ABOVE THE FINISHED THRESHOLD |
| LEVEL. LINERS SHALL BE RECESSED AND FASTENED TO AN |
| APPROVED BACKING SO AS NOT TO OCCUPY THE SPACE REQUIRED |
| FOR WALL COVERING, AND SHALL NOT BE NAILED OR |
| PERFORATED AT ANY POINT LESS THAN 1 INCH (25 MM) ABOVE |
| THE FINISHED THRESHOLD. LINERS SHALL BE PITCHED |
| ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE |
| FIXTURE DRAIN AND BE SECURELY FASTENED TO THE WASTE |
| OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT |
| JOINT BETWEEN THE LINER AND THE OUTLET. |
| ??C1)SPECIFY ON THE DETAIL THE LINER MATERIAL SHOWING |
| COMPLIANCE WITH ONE OF THE FOLLOWING; FBC PL 421.5.2.1, |
| 421.5.2.2, 421.5.2.3, 421.5.2.4, 421.5.2.5, 421.5.2.6. |
| ??C2)INDICATE ON THE DETAIL THE TYPE OF FLOOR (I.E., |
| STRUCTURAL CONCRETE, CONCRETE WITH POST TENSION, WOOD, |
| ETC.) THE SHOWER COMPARTMENT WILL BE LAID ON TO SHOW |
| COMPLIANCE WITH FBC PL 421.5.1. |
| ?D) PER WPB FBC 107.2.1, SHOW COMPLIANCE WITH FBC PL |
| 421.4.1 BATHTUB FLOORS, SHOWER FLOORS, WALL AREAS ABOVE |
| BUILT-IN TUBS THAT HAVE INSTALLED SHOWER HEADS AND |
| WALLS IN SHOWER COMPARTMENTS SHALL BE CONSTRUCTED OF |
| SMOOTH, CORROSION-RESISTANT AND NONABSORBENT WATERPROOF |
| MATERIALS. WALL MATERIALS SHALL EXTEND TO A HEIGHT OF |
| NOT LESS THAN 6 FEET (1829 MM) ABOVE THE ROOM FLOOR |
| LEVEL, AND NOT LESS THAN 70 INCHES (1778 MM) ABOVE THE |
| DRAIN OF THE TUB OR SHOWER. SUCH WALLS SHALL FORM A |
| WATER-TIGHT JOINT WITH EACH OTHER AND WITH EITHER THE |
| TUB OR SHOWER FLOOR. |
| ?E)PER WPB FBC 107.2.1, PROVIDE NOTE STATING ?PER FBC |
| PL412.3, INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION |
| VALVES SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR |
| COMBINATION BALANCED-PRESSURE/THERMOSTATIC VALVES THAT |
| CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME |
| A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1 AND |
| SHALL BE INSTALLED AT THE POINT OF USE." |
| |
| 3.SUPPORTING DOCUMENT TITLED SITE LOCATION APPEARS TO |
| BE THE FIRST FLOOR/DOWNSTAIRS FLOOR PLAN; SUPPORTING |
| DOCUMENT TITLED SITE PLAN APPEARS TO BE THE SECOND |
| FLOOR/UPSTAIRS FLOOR PLAN. PER WPB FBC 107.2.1, |
| CLARIFY. IT WOULD BE HELPFUL TO NAME THE DOCUMENTS AS |
| SUCH AND WHEN RESUBMITTING, UPLOAD THEM TO THE DRAWINGS |
| FOLDER. |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |