Plan Review Details - Permit 21090359
Plan Review Stops For Permit 21090359
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-02-10 Cont ID  
Sent By pvalenti Date 2022-02-10 Time 11:20 Rev Time 0.00
Received By pvalenti Date 2022-02-10 Time 11:20 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-02-09 Cont ID  
Sent By jwitmer Date 2022-02-09 Time 10:13 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-02-09 10:13:40TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-09-29 Cont ID  
Sent By jwitmer Date 2021-09-29 Time 14:54 Rev Time 0.00
Received By jwitmer Date 2021-09-29 Time 14:14 Sent To  
Notes
2021-09-29 14:54:21TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-02-09 Cont ID  
Sent By jwitmer Date 2022-02-09 Time 10:12 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-29 Cont ID  
Sent By jwitmer Date 2021-09-29 Time 14:54 Rev Time 0.00
Received By jwitmer Date 2021-09-29 Time 14:14 Sent To  
Notes
2021-09-29 14:53:50WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21090359
 ADD: 801 S OLIVE AVE. # 104
 CONT: FLORIDA TILE & GROUT RESTORATION
 TEL: 561-602-7970
 E-MAIL:
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 29/ 2021
 ACTION: DENIED
 1) CONTRACTOR DRAWN PLANS. CERTIFICATION BY CONTRACTOR.
 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME,
 SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
  
 2) UPPER BATHROOM COMPLETE DEMO THE PLANS DO NOT
 INDICATE COMPLIANCE WITH;
  
 2A) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS
 A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 2B) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 3) NOTE NO REQUIREMENT FOR TILE UNDERLAYMENT ON THE 1ST
 FLOOR OR MEZZANINE LEVEL. 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 105.2.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2022-01-27 Cont ID  
Sent By dbattles Date 2022-01-27 Time 08:41 Rev Time 0.00
Received By dbattles Date 2022-01-27 Time 08:41 Sent To  
Notes
2022-01-27 08:42:43ELECTRICAL REMOVED FROM SCOPE

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-10-07 Cont ID  
Sent By jleahy Date 2021-10-07 Time 09:36 Rev Time 0.00
Received By jleahy Date 2021-10-07 Time 09:36 Sent To  
Notes
2021-10-07 09:39:44ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 77H ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL WORK SHOWN OR NOTED. PLEASE INDICATE IF
 THERE IS ANY ELECTRICAL WORK TO BE DONE. IF SO PLEASE
 SHOW ON PLAN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-02-09 Cont ID  
Sent By pleduc Date 2022-02-09 Time   Rev Time 0.00
Received By pleduc Date 2022-02-09 Time 10:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-09-10 Cont ID  
Sent By pleduc Date 2021-09-10 Time   Rev Time 0.00
Received By pleduc Date 2021-09-10 Time 14:38 Sent To  
Notes
2021-09-10 14:40:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) AN UNDERLAYMENT IS INDICATED HOWEVER THE TYPE OR
 PRODUCT IS NOT.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE
 UNDERLAYMENT SPEC SHEET OR THE PRODUCT NAME AND
 MANUFACTURER.
  
  
 2) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-09 Cont ID  
Sent By aoliver Date 2022-02-09 Time 16:20 Rev Time 0.00
Received By aoliver Date 2022-02-09 Time 16:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-09 Cont ID  
Sent By lcrespo Date 2022-02-09 Time 10:28 Rev Time 0.00
Received By lcrespo Date 2022-02-09 Time 09:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-07 Cont ID  
Sent By jleahy Date 2021-10-07 Time 09:42 Rev Time 0.00
Received By jleahy Date 2021-09-09 Time 07:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-01-27 Cont ID  
Sent By dbattles Date 2022-01-27 Time 08:40 Rev Time 0.00
Received By dbattles Date 2022-01-27 Time 08:40 Sent To  
Notes
2022-01-27 08:41:13PLUMBING REMOVED FROM SCOPE

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-09-28 Cont ID  
Sent By pvalenti Date 2021-09-28 Time 12:36 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 14:37 Sent To  
Notes
2021-09-28 12:36:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21090359 801 S OLIVE AVE 104
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.PER WPB FBC 104.1, A PLUMBING SUB-PERMIT APPLICATION
 SHALL BE SUBMITTED FOR THIS PROJECT BY A LICENSED
 PLUMBING CONTRACTOR.
  
 2.PER WPB FBC 107.2.1, A PLUMBING PLAN IS REQUIRED.
 ?A) IF THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR THE
 PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION
 NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR
 LICENSED IN THE PLUMBING TRADE (SAID PLAN/PLANS MAY BE
 A COPY OF THE ORIGINAL SUBMITTED PLANS TITLED PLUMBING
 FIRST FLOOR/PLUMBING SECOND FLOOR). PLEASE NOTE THAT
 WHEN SCANNED DRAWINGS ARE SUBMITTED WITH CONTRACTOR'S
 PRINTED NAME, SIGNATURE AND LICENSE NUMBER IN
 ACCORDANCE WITH WPB FBC 107.3.4.3, A PAPER PLAN WITH
 WET SIGNATURE SHALL BE PROVIDED TO THE BUILDING
 DEPARTMENT FOR HARD RECORD FILE PRIOR TO ISSUANCE OF A
 PERMIT.
 ?B) PER WPB FBC 107.2.1, PROVIDE AN EXISTING FLOOR PLAN
 AND A PROPOSED FLOOR PLAN. CLEARLY INDICATE THE
 PLUMBING SCOPE AND ANY CHANGES FROM THE EXISTING TO THE
 PROPOSED.
 ?C) PER WPB FBC 107.2.1, PROVIDE SHOWER PAN AND CURB
 DETAIL PROVIDING THE FOLLOWING REQUIREMENTS NOTED IN
 FBC PL 421.5.2. LINER SHALL TURN UP ON ALL SIDES NOT
 LESS THAN 2 INCHES (51 MM) ABOVE THE FINISHED THRESHOLD
 LEVEL. LINERS SHALL BE RECESSED AND FASTENED TO AN
 APPROVED BACKING SO AS NOT TO OCCUPY THE SPACE REQUIRED
 FOR WALL COVERING, AND SHALL NOT BE NAILED OR
 PERFORATED AT ANY POINT LESS THAN 1 INCH (25 MM) ABOVE
 THE FINISHED THRESHOLD. LINERS SHALL BE PITCHED
 ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE
 FIXTURE DRAIN AND BE SECURELY FASTENED TO THE WASTE
 OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT
 JOINT BETWEEN THE LINER AND THE OUTLET.
 ??C1)SPECIFY ON THE DETAIL THE LINER MATERIAL SHOWING
 COMPLIANCE WITH ONE OF THE FOLLOWING; FBC PL 421.5.2.1,
 421.5.2.2, 421.5.2.3, 421.5.2.4, 421.5.2.5, 421.5.2.6.
 ??C2)INDICATE ON THE DETAIL THE TYPE OF FLOOR (I.E.,
 STRUCTURAL CONCRETE, CONCRETE WITH POST TENSION, WOOD,
 ETC.) THE SHOWER COMPARTMENT WILL BE LAID ON TO SHOW
 COMPLIANCE WITH FBC PL 421.5.1.
 ?D) PER WPB FBC 107.2.1, SHOW COMPLIANCE WITH FBC PL
 421.4.1 BATHTUB FLOORS, SHOWER FLOORS, WALL AREAS ABOVE
 BUILT-IN TUBS THAT HAVE INSTALLED SHOWER HEADS AND
 WALLS IN SHOWER COMPARTMENTS SHALL BE CONSTRUCTED OF
 SMOOTH, CORROSION-RESISTANT AND NONABSORBENT WATERPROOF
 MATERIALS. WALL MATERIALS SHALL EXTEND TO A HEIGHT OF
 NOT LESS THAN 6 FEET (1829 MM) ABOVE THE ROOM FLOOR
 LEVEL, AND NOT LESS THAN 70 INCHES (1778 MM) ABOVE THE
 DRAIN OF THE TUB OR SHOWER. SUCH WALLS SHALL FORM A
 WATER-TIGHT JOINT WITH EACH OTHER AND WITH EITHER THE
 TUB OR SHOWER FLOOR.
 ?E)PER WPB FBC 107.2.1, PROVIDE NOTE STATING ?PER FBC
 PL412.3, INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION
 VALVES SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR
 COMBINATION BALANCED-PRESSURE/THERMOSTATIC VALVES THAT
 CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME
 A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1 AND
 SHALL BE INSTALLED AT THE POINT OF USE."
  
 3.SUPPORTING DOCUMENT TITLED SITE LOCATION APPEARS TO
 BE THE FIRST FLOOR/DOWNSTAIRS FLOOR PLAN; SUPPORTING
 DOCUMENT TITLED SITE PLAN APPEARS TO BE THE SECOND
 FLOOR/UPSTAIRS FLOOR PLAN. PER WPB FBC 107.2.1,
 CLARIFY. IT WOULD BE HELPFUL TO NAME THE DOCUMENTS AS
 SUCH AND WHEN RESUBMITTING, UPLOAD THEM TO THE DRAWINGS
 FOLDER.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21090359 801 S OLIVE AVE 104
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-02-09 Cont ID  
Sent By lcrespo Date 2022-02-09 Time 09:53 Rev Time 0.00
Received By lcrespo Date 2022-02-09 Time 09:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-10-07 Cont ID  
Sent By jleahy Date 2021-10-07 Time 09:41 Rev Time 0.00
Received By jleahy Date 2021-10-07 Time 09:41 Sent To  
Notes
2021-10-07 09:42:51ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 77H ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS NOT SIGNED.
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL RESPONSIBLE FOR THE DESIGN. FBC 107.2.1,
 FS 471, 481
  
  