Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-12-16 Cont ID  
Sent By jleahy Date 2021-12-16 Time 13:56 Rev Time 0.00
Received By jleahy Date 2021-12-16 Time 13:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-11-01 Cont ID  
Sent By jleahy Date 2021-11-01 Time 10:00 Rev Time 0.00
Received By jleahy Date 2021-11-01 Time 08:50 Sent To  
Notes
2021-11-01 10:01:46COMMENTS FOR PERMIT # 21090324
 1) DRAWING DOES NOT INCLUDE ELECTRICAL LOAD
 CALCULATIONS NEC 215.5
 2) DRAWING DOES NOT DELINEATE GROUNDING
 ELECTRODE/CONDUCTOR SYSTEM.
 SHOW ALL PRESENT GROUNDING ELECTRODES TO BE BONDED AS
 REQUIRED. NEC 250.50
 3) DRAWING DOES NOT SHOW IF THIS IS AN UNDERGROUND OR
 OVERHEAD SERVICE NEC 215.5
 4) DRAWING DOES NOT SHOW GROUND CONDUCTOR TO INTERIOR
 PANEL. NEC 215.5
 5) DRAWING DOES NOT DETAIL IF SMOKE DETECTORS ARE
 EXISTING. SMOKE DETECTORS SHALL BE INSTALLED WHERE
 PROVIDED IN THE FLORIDA BUILDING CODE RESIDENTIAL 2020
 R314.2.2 AND FLORIDA BUILDING CODE EXISTING BUILDING
 703.2
 6) DETAIL ELECTRICAL WIRING POWERING NEW AIR CONDITION
 UNITS
 7) INSTALL ELECTRICAL WIRING FOR NEW AIR CONDITIONERS
 AS REQUIRED. NEC 430, NEC 210.63AND OTHER APPLICABLE
 CODES
 8) PERMIT APPLICATION OMITS WIRING OF NEW AIR
 CONDITIONERS. IS THIS IN THE SCOPE OF WORK?
 9) DO THE WIRES FEEDING THE INTERIOR SUBPANEL NEED TO
 BE SIZED HIGHER? THESE FEEDERS DO NOT CARRY THE ENTIRE
 LOAD AS THERE ARE BRANCH CIRCUIT OCPDS CONTAINED IN THE
 METER MAIN.
 THE OUTDOOR METER MAIN DOES NOT CONTAIN FEEDER WIRES
 ONLY BUS BARS. HOW WOULD YOU APPLY NEC 310.15 (B) (7)
 IF IT IS AN UNDERGROUND SERVICE? WOULD WE USE THE
 AMPACITY OF THE BUS?
 ARE FPL, UNDERGROUND, SERVICE LATERAL, FEEDER
 CONDUCTORS, INTO A METER ENCLOSURE, CONSIDERED ?SERVICE
 ENTRANCE CONDUCTORS? THEN SHOULD NEC 310.15 (B) (7)
 APPLY AND ALLOW SIZING, OF DOWNSTREAM FEEDER CONDUCTORS
 ACCORDINGLY. FPL SERVICE LATERAL WIRES COULD HAVE A
 LOWER AMPACITY AS WOULD BE REQUIRED FOR OVERHEAD
 ENTRANCE CONDUCTORS.
  
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPT.
 561-805-6746
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-16 Cont ID  
Sent By jleahy Date 2021-12-16 Time 13:56 Rev Time 0.00
Received By jleahy Date 2021-12-02 Time 11:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-01 Cont ID  
Sent By jleahy Date 2021-11-01 Time 10:01 Rev Time 0.00
Received By jleahy Date 2021-10-06 Time 10:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-16 Cont ID  
Sent By jleahy Date 2021-12-16 Time 13:56 Rev Time 0.00
Received By jleahy Date 2021-12-16 Time 13:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-10-29 Cont ID  
Sent By mpeterso Date 2021-10-29 Time 13:47 Rev Time 0.00
Received By mpeterso Date 2021-10-29 Time 13:47 Sent To  
Notes
2021-10-29 13:47:38OWNER BUILDER/CONTRACTOR DRAWINGS SIGNATURE NOT
 REQUIRED


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved