2021-11-01 10:01:46 | COMMENTS FOR PERMIT # 21090324 |
| 1) DRAWING DOES NOT INCLUDE ELECTRICAL LOAD |
| CALCULATIONS NEC 215.5 |
| 2) DRAWING DOES NOT DELINEATE GROUNDING |
| ELECTRODE/CONDUCTOR SYSTEM. |
| SHOW ALL PRESENT GROUNDING ELECTRODES TO BE BONDED AS |
| REQUIRED. NEC 250.50 |
| 3) DRAWING DOES NOT SHOW IF THIS IS AN UNDERGROUND OR |
| OVERHEAD SERVICE NEC 215.5 |
| 4) DRAWING DOES NOT SHOW GROUND CONDUCTOR TO INTERIOR |
| PANEL. NEC 215.5 |
| 5) DRAWING DOES NOT DETAIL IF SMOKE DETECTORS ARE |
| EXISTING. SMOKE DETECTORS SHALL BE INSTALLED WHERE |
| PROVIDED IN THE FLORIDA BUILDING CODE RESIDENTIAL 2020 |
| R314.2.2 AND FLORIDA BUILDING CODE EXISTING BUILDING |
| 703.2 |
| 6) DETAIL ELECTRICAL WIRING POWERING NEW AIR CONDITION |
| UNITS |
| 7) INSTALL ELECTRICAL WIRING FOR NEW AIR CONDITIONERS |
| AS REQUIRED. NEC 430, NEC 210.63AND OTHER APPLICABLE |
| CODES |
| 8) PERMIT APPLICATION OMITS WIRING OF NEW AIR |
| CONDITIONERS. IS THIS IN THE SCOPE OF WORK? |
| 9) DO THE WIRES FEEDING THE INTERIOR SUBPANEL NEED TO |
| BE SIZED HIGHER? THESE FEEDERS DO NOT CARRY THE ENTIRE |
| LOAD AS THERE ARE BRANCH CIRCUIT OCPDS CONTAINED IN THE |
| METER MAIN. |
| THE OUTDOOR METER MAIN DOES NOT CONTAIN FEEDER WIRES |
| ONLY BUS BARS. HOW WOULD YOU APPLY NEC 310.15 (B) (7) |
| IF IT IS AN UNDERGROUND SERVICE? WOULD WE USE THE |
| AMPACITY OF THE BUS? |
| ARE FPL, UNDERGROUND, SERVICE LATERAL, FEEDER |
| CONDUCTORS, INTO A METER ENCLOSURE, CONSIDERED ?SERVICE |
| ENTRANCE CONDUCTORS? THEN SHOULD NEC 310.15 (B) (7) |
| APPLY AND ALLOW SIZING, OF DOWNSTREAM FEEDER CONDUCTORS |
| ACCORDINGLY. FPL SERVICE LATERAL WIRES COULD HAVE A |
| LOWER AMPACITY AS WOULD BE REQUIRED FOR OVERHEAD |
| ENTRANCE CONDUCTORS. |
| |
| |
| MICHAEL PETERSON |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES DEPT. |
| 561-805-6746 |
| |