Plan Review Stops For Permit 21090311 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2022-07-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2022-07-28 |
Time |
12:43 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2022-07-28 |
Time |
12:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2022-01-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2022-01-31 |
Time |
10:39 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2022-01-31 |
Time |
10:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2021-10-14 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-10-14 |
Time |
17:26 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-10-14 |
Time |
17:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2022-01-06 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-01-06 |
Time |
15:51 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2021-10-13 |
|
|
Cont ID |
|
Sent By |
ppetty |
Date |
2021-10-13 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
ppetty |
Date |
2021-10-13 |
Time |
13:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2022-07-18 |
|
|
Cont ID |
|
Sent By |
rrossano |
Date |
2022-07-18 |
Time |
|
Rev Time |
0.00 |
Received By |
rrossano |
Date |
2022-07-18 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2022-07-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2022-07-28 |
Time |
12:44 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2022-07-06 |
Time |
15:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2022-02-17 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-02-17 |
Time |
10:00 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-01-04 |
Time |
09:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-10-18 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-10-18 |
Time |
15:57 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-09-17 |
Time |
12:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2023-05-01 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-07-08 |
Time |
08:30 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-07-08 |
Time |
08:00 |
Sent To |
|
|
Notes |
2023-05-01 13:12:49 | 3RD PLUMBING REVIEW | | 7/8/2022 | | | | 1) THE NEW SUBMITTED PLANS SHEETS- F1.0, F7.0, F7.1, | | F7.2 & F7.3 ARE NOT DIGITALLY SIGNED AND SEALED BY THE | | ENGINEER OF RECORD. PLEASE NOTE THAT ELECTRONICALLY | | TRANSMITTED PLANS SHALL BEAR THE DIGITAL SIGNATURES OF | | THE ENGINEER OF RECORD- FL. STATUTE 471.025, AND | | SECTION 61G15-23.005 FAC. THESE DRAWINGS WERE ALSO | | SUBMITTED ALL TOGETHER IN A FILE HOWEVER ONLY THE F1.0 | | PLAN WAS DIGITALLY SIGNED AND SEALED. | | | | FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR | | ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND | | DOCUMENTS. | | A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL | | ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY | | CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION. | | THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE | | A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES | | NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.) | | YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE | | ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT | | USE A THIRD PARTY. | | YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT | | IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE | | AND DOCUMENT. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2022-01-10 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-01-10 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-01-10 |
Time |
10:10 |
Sent To |
|
|
Notes |
2022-01-10 11:38:18 | 2ND REVIEW FBC-2020 PLUMBING | | PERMIT- 21090311 | | 1/10/22 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. FAILED COMMENT #4 FROM THE | | 1ST REVIEW IS PRINTED BELOW WITH ADDITIONAL NOTES IN | | CAP LETTERS. | | | | 4) FAILED. BASED ON COMMENT #2 ABOVE PLEASE PROVIDE A | | CIVIL PLAN OR SITE UTILITY PLAN SHOWING HOW WASTE WATER | | FROM THE POOL AND SPA WILL BE DRAINED TO AN APPROVED | | PLACE OF DISPOSAL- SECTION 107.2.1 WPB. SHEETS F7.0, | | F7.1, F7.3 REFERENCE CIVIL DRAWINGS FOR OVERFLOW AND | | PUMP WASTE. PLEASE PROVIDE THE CIVIL PLANS SHOWING THE | | WASTE DRAIN POINTS OF CONNECTION TO THE MAIN STORM | | DRAIN, AND THE AUTO FILL WATER LINE CONNECTION TO THE | | MAIN POTABLE ONSITE SERVICE LINE. PLEASE PLACE A NOTE | | TO INDICATE A BACKFLOW PREVENTER WILL BE PROVIDED AT | | THE AUTOFILL LOCATION. PLEASE NOTE SEPARATE PLUMBING | | PERMITS ARE REQUIRED FOR INSTALLATION OF THE AUTO FILL | | AND THE REQUIRED BACKFLOW PREVENTER- SECS 105.1 7 | | 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2021-10-05 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-10-05 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-10-05 |
Time |
07:46 |
Sent To |
|
|
Notes |
2021-10-05 11:23:05 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT- 21090311 | | 10/5/21 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET F1: DESIGN CRITERIA- PLEASE PROVIDE A LIST OF | | CURRENT CODES AND STANDARDS USED IN THE DESIGN OF THE | | FOUNTAIN- SECTION 107.2.1 WPB. | | | | 2) F1: PLEASE PROVIDE A NOTE ON THE PLAN INDICATING | | THAT THE FOUNTAIN IS NOT FOR BATHING, SWIMMING, WADING | | OR FOR INTERACTIVE WATER ACTIVITIES- SECTION 454.1 FBC | | B. | | | | 3) F7.3: PLEASE CORRECT THE DETAIL SHOWING POOL WASTE | | BY GENERAL CONTRACTOR. THE ENGINEER OF RECORD SHALL | | DESIGN THE WASTE WATER REMOVAL SYSTEM IN ACCORDANCE | | WITH- SECTION 454.1.6.5.15 FBC B, AND SECS. 90-126 & | | 203 WPB CODE OF ORDINANCES. UNDER SEC. 90-126 (5) | | SWIMMING POOL DISCHARGES ARE PROHIBITED TO DRAIN INTO | | THE CITY SANITARY SYSTEM. UNDER SEC. 90-203 NO PERSON | | SHALL DIRECTLY OR INDIRECTLY DISCHARGE, SPILL, OR DUMP | | INTO ANY OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE | | STORM SEWER SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER | | THAN THAT COMPOSED OF STORMWATER. THERE IS AN EXCEPTION | | UNDER SEC. 90-205 FOR DECHLORINATED SWIMMING POOL | | DISCHARGES, HOWEVER THE ENGINEER MUST PROVIDE DETAILS | | AND SPECIFICATIONS FOR DECHLORINATION OF THE POOL WASTE | | WATER. | | | | 4) BASED ON COMMENT #2 ABOVE PLEASE PROVIDE A CIVIL | | PLAN OR SITE UTILITY PLAN SHOWING HOW WASTE WATER FROM | | THE POOL AND SPA WILL BE DRAINED TO AN APPROVED PLACE | | OF DISPOSAL- SECTION 107.2.1 WPB. | | | | 5) F7.3: PROVIDE TOTAL DYNAMIC HEAD CALCULATIONS TO | | VERIFY PUMP SIZING AND PUMP SELECTION SHOWN IN THE PUMP | | CURVE- SECTION 454.1.6.5.4 FBC B. THE CALCULATIONS | | SHALL INCLUDE THE CALCULATED HEAD FOR PIPING AND | | EQUIPMENT. | | | | 6) F7.3: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR | | RECIRCULATION AND TREATMENT EQUIPMENT INCLUDING THE | | PUMPS, FILTERS, CHLORINATOR AND MAIN DRAINS AND COVERS- | | SECTION 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
F |
Date |
2022-07-08 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-07-08 |
Time |
08:26 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-07-08 |
Time |
08:26 |
Sent To |
|
|
Notes |
2022-07-08 08:30:06 | 3RD SIGNATURE REVIEW | | 7/8/2022 | | | | 1) THE NEW SUBMITTED PLANS SHEETS- F1.0, F7.0, F7.1, | | F7.2 & F7.3 ARE NOT DIGITALLY SIGNED AND SEALED BY THE | | ENGINEER OF RECORD. PLEASE NOTE THAT ELECTRONICALLY | | TRANSMITTED PLANS SHALL BEAR THE DIGITAL SIGNATURES OF | | THE ENGINEER OF RECORD- FL. STATUTE 471.025, AND | | SECTION 61G15-23.005 FAC. THESE DRAWINGS WERE ALSO | | SUBMITTED ALL TOGETHER IN A FILE HOWEVER ONLY THE F1.0 | | PLAN WAS DIGITALLY SIGNED AND SEALED. | | | | | | FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR | | ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND | | DOCUMENTS. | | A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL | | ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY | | CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION. | | THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE | | A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES | | NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.) | | YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE | | ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT | | USE A THIRD PARTY. | | YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT | | IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE | | AND DOCUMENT. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2022-01-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2022-01-31 |
Time |
10:41 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2022-01-31 |
Time |
10:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2021-10-14 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-10-14 |
Time |
17:27 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-10-14 |
Time |
17:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2022-07-20 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2022-07-20 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2022-07-20 |
Time |
11:05 |
Sent To |
|
|
Notes |
2022-07-20 11:05:18 | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | PROVISOS: | | | | 1. ALL FOUNTAIN EQUIPMENT SHALL BE COMPLETELY SCREENED | | FROM VIEW. | | | | 2. THE BANYAN CAY DEVELOPMENT SHALL BE SUBJECT TO ALL | | DEVELOPMENT ORDER CONDITIONS, AS OUTLINED IN RESOLUTION | | NO.177-21, AND AS MAY BE AMENDED. ALL CONDITIONS OF | | APPROVAL IMPOSED BY RESOLUTION NO. 177-21, AS AMENDED, | | SHALL BE ADDRESSED WITHIN THE APPROPRIATE SPECIFIED | | TIMEFRAMES. | | _______________________________________________________ | | _____________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | _______________________________________________________ | | _____________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | P: 561.822.1448 | E: [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2022-02-17 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2022-02-17 |
Time |
09:25 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2022-02-17 |
Time |
09:25 |
Sent To |
|
|
Notes |
2022-02-17 09:26:05 | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | PROVISOS: | | | | 1. ALL FOUNTAIN EQUIPMENT SHALL BE COMPLETELY SCREENED | | FROM VIEW. | | | | 2. THE BANYAN CAY DEVELOPMENT SHALL BE SUBJECT TO ALL | | DEVELOPMENT ORDER CONDITIONS, AS OUTLINED IN RESOLUTION | | NO.177-21, AND AS MAY BE AMENDED. ALL CONDITIONS OF | | APPROVAL IMPOSED BY RESOLUTION NO. 177-21, AS AMENDED, | | SHALL BE ADDRESSED WITHIN THE APPROPRIATE SPECIFIED | | TIMEFRAMES. | | _______________________________________________________ | | _____________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | _______________________________________________________ | | _____________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | P: 561.822.1448 | E: [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2021-10-18 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2021-10-18 |
Time |
14:22 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2021-10-18 |
Time |
14:22 |
Sent To |
|
|
Notes |
2021-10-18 14:23:04 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 10.18.2021 | | PERMIT NO.: 21090311 | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. THE PROPOSED PLAN FOR THE FOUNTAIN (SPECIFICALLY THE | | AREA FOR THE EQUIPMENT) DOES NOT MATCH THE SITE PLAN | | THAT IS APPROVED FOR THE COMMERCIAL PLANNED DEVELOPMENT | | (CPD). STAFF IS AWAITING A RESUBMITTAL OF A MINOR | | AMENDMENT TO REFLECT THE REVISED POOLSIDE BAR/EQUIPMENT | | COMPOUND. SUCH REVISED PLANS SHALL BE SUBMITTED PRIOR | | TO ISSUANCE OF A PERMIT FOR THE FOUNTAIN/EQUIPMENT. | | | | 2. DETAILS WILL NEED TO BE PROVIDED REGARDING THE | | SCREENING OF THE EQUIPMENT COMPOUND. SCREENING OF THE | | EQUIPMENT SHALL COMPLY WITH SEC. 94-315 OF THE CITY?S | | ZONING AND LAND DEVELOPMENT REGULATIONS. | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | TTY: 800.955.8771 | | E: [email protected] | | | | W: WPB.ORG | | |
|
|