Plan Review Details - Permit 21090225
Plan Review Stops For Permit 21090225
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2022-04-19 Cont ID  
Sent By cpuell Date 2022-04-19 Time 15:03 Rev Time 0.00
Received By cpuell Date 2022-04-19 Time 15:03 Sent To  
Notes
2022-04-19 15:04:18FOLLWOING ADDRESSES HAVE BEEN APPROVED:
  
 GROUND FLOOR
 5179 BROADWAY (PRIMARY ADDRESS FOR THE PROJECT AND
 BUILDING)
 5169 BROADWAY (NORTH COMMERCIAL SPACE)
 5159 BROADWAY (SOUTH COMMERCIAL SPACE)
  
 SECOND FLOOR
 5179 BROADWAY # 200
 5179 BROADWAY # 201
 5179 BROADWAY # 202
 5179 BROADWAY # 203
 5179 BROADWAY # 204
 5179 BROADWAY # 205
  
 THIRD FLOOR
 5179 BROADWAY # 300
 5179 BROADWAY # 301
 5179 BROADWAY # 302
 5179 BROADWAY # 303
 5179 BROADWAY # 304
 5179 BROADWAY # 305
  
 UPDATED PERMIT.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-11-15 Cont ID  
Sent By cpuell Date 2021-11-15 Time 16:22 Rev Time 0.00
Received By cpuell Date 2021-11-15 Time 16:22 Sent To  
Notes
2021-11-15 16:23:00PROPOSED THE FOLLOWING ADDRESSES, WAITING TO HEAR BACK
 FROM OWNERS:
 GROUND FLOOR
 5179 BROADWAY (PRIMARY ADDRESS FOR THE PROJECT AND
 BUILDING)
 5169 BROADWAY (NORTH COMMERCIAL SPACE)
 5159 BROADWAY (SOUTH COMMERCIAL SPACE)
  
 SECOND FLOOR
 5179 BROADWAY # 200
 5179 BROADWAY # 201
 5179 BROADWAY # 202
 5179 BROADWAY # 203
 5179 BROADWAY # 204
 5179 BROADWAY # 205
  
 THIRD FLOOR
 5179 BROADWAY # 300
 5179 BROADWAY # 301
 5179 BROADWAY # 302
 5179 BROADWAY # 303
 5179 BROADWAY # 304
 5179 BROADWAY # 305
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-09-22 Cont ID  
Sent By cpuell Date 2021-09-22 Time 14:49 Rev Time 0.00
Received By cpuell Date 2021-09-22 Time 14:49 Sent To  
Notes
2021-09-22 14:52:34PARCEL NEEDS TO BE READDRESS SO THAT THE ENTRANCES ON
 THE GROUND FLOOR FALL IN LINE WITH THE CITY'S ROAD
 CENTER LINES. ADDRESSES NEEDS THAT NEED TO BE
 ESTABLISHED WOULD BE FOR THE BUILDING ITSELF, THE
 GROUND FLOOR COMMERCIAL SPACE AND THE UNITS ON THE
 SECOND AND THRID FLOOR. PLEASE CONTACT [email protected]
 OR CALL 561-805-6659 TO WORK ON THE READDRESSING
 ISSUES.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status   Date 2021-09-08 Cont ID  
Sent By scwelter Date 2021-09-08 Time 10:54 Rev Time 0.00
Received By scwelter Date 2021-09-08 Time 10:54 Sent To  
Notes
2021-09-08 10:54:37PUBLIC ART REQUIREMENT:
 IF TOTAL CONSTRUCTION COSTS OF THIS DEVELOPMENT ARE
 OVER $500,000 IT WILL BE SUBJECT TO THE PUBLIC ART
 REQUIREMENT AS PER CITY ORDINANCE.
 SECTION 78-129: ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT.
 OPTION 1: INSTALL ARTWORK ON THE DEVELOPMENT SITE
 VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE
 TOTAL CONSTRUCTION COSTS; OR
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF
 ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT
 TO THE PUBLIC ART ACCOUNT.
 A COMPLETED PUBLIC ART ASSESSMENT APPLICATION IS
 REQUIRED AT TIME OF BUILDING PERMIT SUBMITTAL.
  
 PLEASE CONTACT SYBILLE WELTER AT [email protected] OR
 561.822.1521 TO OBTAIN AN APPLICATION AND REVIEW THE
 REQUIREMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-27 Cont ID  
Sent By rmcphers Date 2021-10-27 Time 15:43 Rev Time 0.00
Received By rmcphers Date 2021-10-26 Time 09:20 Sent To  
Notes
2021-10-26 16:42:50NEW 3 STORY BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A LIFE SAFETY PLAN FOR THE 2ND FLOOR,
 3RD FLOOR AND ROOF TERRACE - SHOW THE OCCUPANCY LOADS,
 EXIT ACCESS TRAVEL DISTANCE TO THE EXIT DISCHARGE ETC.
 FBC WPB 107.3.5.1.1 (6)
  
 2) DRAWING LS-01 SHOWS BUILDING CONSTRUCTION TYPE (I) -
 PLEASE SHOW (IA OR IB) FBC CHAPTER 6
  
 3) DRAWING LS-01 DOES NOT SHOW THE OCCUPANCY FOR EACH
 ROOM - PLEASE SHOW THE OCCUPANT LOAD FOR EACH ROOM OR
 SPACE - FBC 1004.1.2
  
 4) 2 EXITS ARE REQUIRED FROM EACH STORY AND ROOF
 TERRACE FBC 1006.3
  
 5) THE TRASH CHUTE CANNOT OPEN TO A CORRIDOR - FBC
 713.13.1 - FBC 713.13.3 CHUTE ACCESS ROOMS.
 ACCESS OPENINGS FOR WASTE OR LINEN CHUTES SHALL BE
 LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY NOT LESS
 THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE
 WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED
 IN ACCORDANCE WITH SECTION 711, OR BOTH. OPENINGS INTO
 THE ACCESS ROOMS SHALL BE PROTECTED BY OPENING
 PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS
 THAN 3/4 HOUR. DOORS SHALL BE SELF- OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 716.5.9.3.
  
 6) PLEASE SHOW THE STAIR RISER HEIGHTS FBC 1011.5.2
  
 7) DRAWING A4-1.01 PLEASE SHOW THE BOTTOM HAND RAIL
 EXTENSION TO CONTINUE TO SLOPE (NOT LEVEL) - FBC 1014.6
  
 8) PLEASE PROVIDE THE EXTERIOR FRAMING DETAILS FBC WPB
 107.2.1
  
 9) PLEASE PROVIDE THE EXTERIOR CLADDING (TEAK WOOD
 FINISH) DETAILS FBC WPB 107.2.1
  
 10) PLEASE SHOW THE HORIZONTAL ASSEMBLY HOURLY FIRE
 RATING TO COMPLY WITH FBC 711.2.4
  
 11) PLEASE SHOW THE ROOFING SYSTEM REQUIRED WIND DESIGN
 PRESSURES FBC 1603.1.4
  
 12) PLEASE SHOW THE GUARDRAIL HEIGHT FROM THE ROOF
 TERRACE FINISHED FLOOR TO THE TOP OF THE PARAPET (GUARD
 RAIL). FBC 1015.3
  
 13) PLEASE PROVIDE A SURVEY.
  
 14) PLEASE SHOW THE COMMERCIAL RESTROOMS WALL FINISH -
 FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 15) PLEASE PROVIDE COPIES OF ALL OF THE PRODUCT
 APPROVALS (NOA) MENTIONED ON THE DRAWINGS.
  
 16) PROVIDED NOA 20-0813.03 FOR THE SLIDING WINDOWS
 REQUIRES SHUTTERS - PLEASE PROVIDE THE SHUTTER PRODUCT
 APPROVALS. PRODUCT APPROVALS THAT ARE NOT LISTED ON THE
 DRAWINGS NEED TO BE REVIEWED AND MARKED APPROVED BY THE
 DESIGNER OF RECORD FBC WPB 107.3.4
  
 17) DRAWING A1-1.01 SHOWS DOOR OR SOMETHING AS SF-2 -
 WHAT IS SF-2 ?
  
 18) PLEASE SHOW THE COMMERCIAL RESTROOMS TO COMPLY WITH
 FBC ACCESSIBILITY - SHOW FIXTURE FLOOR SPACES, GRAB BAR
 LOCATION AND SIZE DIMENSIONS, TOILET PAPER HOLDER
 LOCATION DIMENSIONS, MIRROR LOCATION DIMENSIONS PER FBC
 ACCESSIBILITY CHAPTER 6.
  
 19) PLEASE SHOW RESIDENTIAL UNIT COMPLIANCE WITH FHA -
 SHOW THE REQUIRED FLOOR SPACE IN THE UNITS - -
 REQUIREMENT 7 -USABLE KITCHENS AND BATHROOMS.
 SECTION 100.205(C)(3)(IV) REQUIRES THAT COVERED
 MULTIFAMILY DWELLINGS WITH A BUILDING ENTRANCE ON AN
 ACCESSIBLE ROUTE SHALL BE DESIGNED AND CONSTRUCTED IN
 SUCH A MANNER THAT ALL PREMISES WITHIN COVERED
 MULTIFAMILY DWELLING UNITS CONTAIN USABLE KITCHENS AND
 BATHROOMS SUCH THAT AN INDIVIDUAL IN A WHEELCHAIR CAN
 MANEUVER ABOUT THE SPACE.
 GUIDELINE(1)USABLE KITCHENS. USABLE KITCHENS WOULD MEET
 SECTION 100.205(C)(3)(IV) IF:
 (A)A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 THAT ALLOWS A PARALLEL APPROACH BY A PERSON IN A
 WHEELCHAIR IS PROVIDED AT THE RANGE OR COOKTOP AND SINK
 AND EITHER A PARALLEL OR FORWARD APPROACH IS PROVIDED
 AT OVEN, DISH WASHER, REFRIGERATOR/FREEZER OR TRASH
 COMPACTOR. (SEE FIGURE FHAG-6)
 (B)CLEARANCE BETWEEN COUNTERS AND ALL OPPOSING BASE
 CABINETS, COUNTERTOPS, APPLIANCES OR WALLS IS AT LEAST
 40 INCHES.
 (C)IN U-SHAPED KITCHENS WITH SINK OR RANGE OR COOKTOP
 AT THE BASE OF THE ?U?, A 60-INCH TURNING RADIUS IS
 PROVIDED TO ALLOW PARALLEL APPROACH, OR BASE CABINETS
 ARE REMOVABLE AT THAT LOCATION TO ALLOW KNEE SPACE FOR
 A FORWARD APPROACH.
  
 (2)USABLE BATHROOMS. TO MEET THE REQUIREMENTS OF
 SECTION 100.205(C)(3)(IV) EITHER.
 ALL BATHROOMS IN THE DWELLING UNIT COMPLY WITH OPTION
 2, OR THE PROVISIONS OF PARAGRAPH (A): OR
 AT LEAST ONE BATHROOM IN THE DWELLING UNIT COMPLIES
 WITH THE PROVISIONS OF PARAGRAPH (B), AND ALL OTHER
 BATHROOMS AND POWDER ROOMS WITHIN THE DWELLING UNIT
 MUST BE ON AN ACCESSIBLE ROUTE WITH USABLE ENTRY DOORS
 IN ACCORDANCE WITH THE GUIDELINES FOR REQUIREMENTS 3
 AND 4.
  
 20) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 21) PLEASE PROVIDE DETAILS SHOWING THAT THE UNIT
 SEPARATION WALLS COMPLY WITH THE AIRBORNE SOUND
 REQUIREMENTS FBC 1207.2 AIRBORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH
 OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT
 LESS THAN 45 IF FIELD TESTED, FOR AIRBORNE NOISE WHEN
 TESTED IN ACCORDANCE WITH ASTM E90. ALTERNATIVELY, THE
 SOUND TRANSMISSION CLASS OF WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SHALL BE ESTABLISHED BY
 ENGINEERING ANALYSIS BASED ON A COMPARISON OF WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES HAVING SOUND
 TRANSMISSION CLASS RATINGS AS DETERMINED BY THE TEST
 PROCEDURES SET FORTH IN ASTM E90. PENETRATIONS OR
 OPENINGS IN CONSTRUCTION ASSEMBLIES FOR PIPING;
 ELECTRICAL DEVICES; RECESSED CABINETS; BATHTUBS;
 SOFFITS; OR HEATING, VENTILATING OR EXHAUST DUCTS SHALL
 BE SEALED, LINED, INSULATED OR OTHERWISE TREATED TO
 MAINTAIN THE REQUIRED RATINGS. THIS REQUIREMENT SHALL
 NOT APPLY TO ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL
 BE TIGHT FITTING TO THE FRAME AND SILL.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-11-06 Cont ID  
Sent By fgiaquin Date 2021-11-06 Time 17:55 Rev Time 0.00
Received By fgiaquin Date 2021-11-04 Time 22:45 Sent To  
Notes
2021-11-06 17:55:54ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO PLANS SUBMITTED FOR 1ST FLOOR? FBC 107.2.1
  
 2. NO PLANS SUBMITTED FOR FIRST FLOOR AND SERVICE SHOWN
 ON PLANS APPEARS TO FEED ONLY 2ND ND 3RD FLOORS. NEC
 230.2 STATES ONE SERVICE PER BUILDING. PROVIDE MORE
 INFORMATION. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-10-15 Cont ID  
Sent By rrossano Date 2021-10-15 Time   Rev Time  
Received By rrossano Date 2021-10-15 Time   Sent To  
Notes
2021-10-15 08:12:33PLEASE ADDRESS ZONING COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-09-21 Cont ID  
Sent By pleduc Date 2021-09-21 Time   Rev Time 0.00
Received By pleduc Date 2021-09-21 Time 14:25 Sent To  
Notes
2021-09-21 14:28:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) LIFE SAFETY SHEETS - THERE IS AN INDICATION OF A
 SINGLE EXIT OFF OF THE 2ND & 3RD FLOORS.
  
 PER NFPA 101 CH 30, NEW APARTMENT BUILDINGS
  
 30.2.4.6 A SINGLE EXIT SHALL BE PERMITTED IN BUILDINGS
 WHERE THE TOTAL
 NUMBER OF STORIES DOES NOT EXCEED FOUR, PROVIDED THAT
 ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THERE ARE FOUR OR FEWER DWELLING UNITS PER STORY.
 (2) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH 30.3.5.
 (3) THE EXIT STAIRWAY DOES NOT SERVE MORE THAN ONE-HALF
 STORY BELOW
 THE LEVEL OF EXIT DISCHARGE.
 (4) THE TRAVEL DISTANCE FROM THE ENTRANCE DOOR OF ANY
 DWELLING UNIT TO
 AN EXIT DOES NOT EXCEED 35 FT (10.7 M).
 (5) THE EXIT STAIRWAY IS COMPLETELY ENCLOSED OR
 SEPARATED FROM THE REST
 OF THE BUILDING BY BARRIERS HAVING A MINIMUM 1-HOUR
 FIRE RESISTANCE
 RATING.
 (6) ALL OPENINGS BETWEEN THE EXIT STAIRWAY ENCLOSURE
 AND THE BUILDING
 ARE PROTECTED WITH SELF-CLOSING DOOR ASSEMBLIES HAVING
 A MINIMUM
 1-HOUR FIRE PROTECTION RATING.
 (7) ALL CORRIDORS SERVING AS ACCESS TO EXITS HAVE A
 MINIMUM 1-HOUR
 FIRE RESISTANCE RATING.
 (8) HORIZONTAL AND VERTICAL SEPARATION HAVING A MINIMUM
 1?2-HOUR FIRE
 RESISTANCE RATING IS PROVIDED BETWEEN DWELLING UNITS.
  
 THE PROPOSED IS IN DIRECT VIOLATIONS OF (1), (4), (5) &
 (6)
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES AND DETAILED NARRATIVE.
  
  
  
 2) COVER SHEET - THERE IS AN INDICATION OF A FIRE
 SPRINKLER SYSTEM.
  
 THERE ARE NO INDICATIONS OF FIRE SPRINKLER DOCUMENTS IN
 COMPLIANCE WITH F.A.C. 61G
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 61G15-30.003 MINIMUM REQUIREMENTS FOR ENGINEERING
 DOCUMENTS.
 (1) ENGINEERING DOCUMENTS ARE PREPARED IN THE COURSE OF
 PERFORMING ENGINEERING SERVICES. WHEN PREPARED FOR
 INCLUSION WITH AN APPLICATION FOR A GENERAL BUILDING
 PERMIT, THE DOCUMENTS SHALL MEET ALL ENGINEER?S
 RESPONSIBILITY RULES, SET FORTH IN CHAPTERS 61G15-31,
 61G15-32, 61G15-33, AND 61G15-34, F.A.C., AND BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ADOPTED IN SECTION 553.73, F.S., AND APPLICABLE
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE AHJ. THE DOCUMENTS SHALL INCLUDE:
 (A) INFORMATION THAT PROVIDES MATERIAL SPECIFICATIONS
 REQUIRED FOR THE SAFE OPERATION OF THE SYSTEM THAT IS A
 RESULT OF ENGINEERING CALCULATIONS, KNOWLEDGE AND
 EXPERIENCE.
 (B) LIST FEDERAL, STATE, MUNICIPAL, AND COUNTY
 STANDARDS, CODES, ORDINANCES, LAWS, AND RULES, WITH
 THEIR EFFECTIVE DATES, THAT THE ENGINEERING DOCUMENTS
 ARE INTENDED TO CONFORM TO.
 (C) INFORMATION, AS DETERMINED BY THE ENGINEER OF
 RECORD, NEEDED FOR THE SAFE AND EFFICIENT OPERATION OF
 THE SYSTEM.
 (D) LIST ENGINEERING DESIGN CRITERIA; REFERENCE PROJECT
 SPECIFIC STUDIES, REPORTS, AND DELEGATED ENGINEERING
 DOCUMENTS.
 (E) IDENTIFY CLEARLY ELEMENTS OF THE DESIGN THAT VARY
 FROM THE GOVERNING STANDARDS AND DEPICT/IDENTIFY THE
 ALTERNATE METHOD USED TO ENSURE COMPLIANCE WITH THE
 STATED PURPOSE OF THESE RESPONSIBILITY RULES.
 (2) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND
 BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING
 DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR
 CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE
 OF SUCH DOCUMENTS.
 (3) WHEN ELEMENTS OF THE PROJECT ARE SHOWN ON AN
 ENGINEERING DOCUMENT ONLY FOR INFORMATION OR
 CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO
 ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER
 SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS
 RESPONSIBILITY.
 (4) ENGINEERING DRAWINGS SHALL BE LEGIBLE AND CLEARLY
 DEFINE AND DELINEATE THE WORK IN THE PROJECT. THEY MUST
 ALSO COMPLY WITH CHAPTER 61G15-23, F.A.C., SEALS.
 (5) ENGINEERS SHALL CLEARLY NOTE ON ANY PRELIMINARY
 ENGINEERING DOCUMENTS THAT SUCH DOCUMENTS ARE NOT IN
 FINAL FORM, BUT ARE BEING TRANSMITTED TO THE PUBLIC
 AGENCY TO RECEIVE AGENCY REVIEWS, COMMENTS AND
 INTERPRETATIONS. THE DOCUMENTS MAY SUBSEQUENTLY BE
 REVISED BY THE ENGINEER TO REFLECT RESOLUTION OF ISSUES
 WITH THE PUBLIC AGENCY PRIOR TO FINAL ACTION BY THE
 AGENCY. CHANGES, REVISIONS AND MODIFICATIONS TO A
 PROJECT MAY PROMPT ADDITIONAL DOCUMENT SUBMITTAL FOR
 AGENCY APPROVAL ACTION ON THE SAME PROJECT.
 SPECIFIC AUTHORITY 471.033(2), 471.008 FS. LAW
 IMPLEMENTED 471.033(1)(G), 471.025(3) FS. HISTORY?NEW
 1-26-93, FORMERLY 21H-30.003, AMENDED 11-13-08.
  
 ALL FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE
 PERMIT & SHOP DRAWINGS.
  
 PLEASE PROVIDE THE REQUIRED DOCUMENTATION WITH THIS
 MASTER PERMIT.
  
  
  
  
 2A) CIVIL SHEETS - THERE ARE NO INDICATIONS OF FIRE
 LINE, FDC AND FIRE DDCV DETAILS.
  
 PLEASE PROVIDE DETAILS FOR THE PROPOSED FIRE LINE, FDC
 AND DDCV LOCATIONS.
  
 ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED PER NFPA
 24. PLEASE PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 3) 1ST FLOOR LIFE SAFETY SHEET - THERE IS AN INDICATION
 OF A COMMERCIAL SPACE WITH AN AREA OF 1,222 AND SQ FT
 OF 2,057 OCCUPANCY LOAD.
  
 PLEASE CLARIFY IS IS 1,222 OR 2,057
  
  
 3A) 1ST FLOOR LIFE SAFETY SHEET - THERE IS AN
 INDICATION OF 2 DOUBLE IN-SWING EXIT DOES TO THE
 COMMERCIAL SPACE.
  
 SHOULD THESE SPACES BE CONVERTED TO A MERCANTILE OR
 ASSEMBLY OCCUPANCY THESE DOORS ARE REQUIRED TO
 OUT-SWING.
  
 PLEASE REVIEW AND PROVIDE FOR CLARIFICATION OR CORRECT
 TO OUT-SWING FOR FLEX SPACE PURPOSES.
  
  
  
 4) 1ST FLOOR LIFE SAFETY PLAN - THE SINGLE EXIT
 STAIRWAY EXITS INTO THE PARKING GARAGE.
  
 PER NFPA 101 CH 7, MEANS OF EGRESS.
  
 7.2.3.5 DISCHARGE.
 7.2.3.5.1 EVERY SMOKEPROOF ENCLOSURE SHALL DISCHARGE
 INTO A PUBLIC WAY,
 INTO A YARD OR COURT HAVING DIRECT ACCESS TO A PUBLIC
 WAY, OR INTO AN EXIT
 PASSAGEWAY. SUCH EXIT PASSAGEWAYS SHALL BE WITHOUT
 OPENINGS, OTHER
 THAN THE ENTRANCE TO THE SMOKEPROOF ENCLOSURE AND THE
 DOOR OPENING TO
 THE OUTSIDE YARD, COURT, OR PUBLIC WAY. THE EXIT
 PASSAGEWAY SHALL BE
 SEPARATED FROM THE REMAINDER OF THE BUILDING BY A
 2-HOUR FIRE RESISTANCE
 RATING.
 7.2.3.5.2 THE SMOKEPROOF ENCLOSURE SHALL BE PERMITTED
 TO DISCHARGE
 THROUGH INTERIOR BUILDING AREAS, PROVIDED THAT ALL OF
 THE FOLLOWING CRITERIA
 ARE MET:
 (1) THE BUILDING SHALL BE PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 9.7.
 (2) THE DISCHARGE FROM THE SMOKEPROOF ENCLOSURE SHALL
 LEAD TO A FREE
 AND UNOBSTRUCTED WAY TO AN EXTERIOR EXIT, AND SUCH WAY
 SHALL BE
 READILY VISIBLE AND IDENTIFIABLE FROM THE POINT OF
 DISCHARGE FROM
 THE SMOKEPROOF ENCLOSURE.
 (3) NOT MORE THAN 50 PERCENT OF THE REQUIRED NUMBER AND
 CAPACITY OF
 EXITS COMPRISED OF SMOKEPROOF ENCLOSURES SHALL
 DISCHARGE THROUGH
 INTERIOR BUILDING AREAS IN ACCORDANCE WITH 7.7.2.
  
 THE STAIRWAY CANNOT EXIT INTO THE PARKING GARAGE.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 5) THERE IS NO INDICATIONS OF A REQUIRED FIRE ALARM.
  
 PER NFPA 101 CH. 30
  
 30.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 30.3.4.1 GENERAL.
 30.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN
 HEIGHT OR WITH
 MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE MEETING
 THE REQUIREMENTS
 OF 30.3.4.1.2, SHALL BE PROVIDED WITH A FIRE ALARM
 SYSTEM IN ACCORDANCE
 WITH SECTION 9.6, EXCEPT AS MODIFIED BY 30.3.4.2
 THROUGH 30.3.4.5.
  
 61G15-32.008 DESIGN OF FIRE ALARMS, SIGNALING SYSTEMS
 AND CONTROL SYSTEMS.
  
 (1) FIRE ALARMS, SIGNALING, AND CONTROL SYSTEMS
 INCLUDE, BUT ARE NOT LIMITED TO, FIRE PROTECTION
 SUPERVISION AND ALARM CIRCUITS, ACTIVATION CONTROLS,
 AND REMOTE SIGNALING.
 (2) THE FIRE PROTECTION SYSTEM DESIGN SPECIFICATIONS
 SHALL BE BASED ON APPLICABLE NFPA STANDARDS, WHEN
 AVAILABLE, OR ALTERNATIVE ENGINEERING SOURCES AND GOOD
 ENGINEERING PRACTICE WHEN REQUIRED, AND SHALL COMPLY
 WITH THE PROVISIONS OF RULE 61G15-33.006, F.A.C.
 SPECIFIC AUTHORITY 471.008, 471.033(2) FS.
 LAW IMPLEMENTED 471.033 FS.
 HISTORY--NEW 5-19-93, FORMERLY 21H-32.008.
  
 ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT
 & SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
  
 6) EXIT SIGNAGE EMERGENCY LIGHTING - THERE DOES NOT
 APPEAR TO BE ANY CLEAR EXIT SIGNAGE THROUGHOUT THE
 PROPOSED OCCUPANCIES.
  
 30.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL BE
 ILLUMINATED IN ACCORDANCE WITH SECTION 7.8.
 30.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING IN
 ACCORDANCE WITH
 SECTION 7.9 SHALL BE PROVIDED IN ALL BUILDINGS FOUR OR
 MORE STORIES IN
 HEIGHT, OR WITH MORE THAN 12 DWELLING UNITS, UNLESS
 EVERY DWELLING UNIT
 HAS A DIRECT EXIT TO THE OUTSIDE OF THE BUILDING AT THE
 FINISHED GROUND LEVEL.
 30.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE
 SIGNS IN ACCORDANCE WITH SECTION 7.10 IN ALL BUILDINGS
 REQUIRING MORE
 THAN ONE EXIT.
  
  
 PLEASE REVIEW AND CORRECT OR INDICATE WHERE THE EXIT
 SIGNS ARE LOCATED.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-06 Cont ID  
Sent By fgiaquin Date 2021-11-06 Time 17:56 Rev Time 0.00
Received By fgiaquin Date 2021-09-20 Time 10:09 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-10-27 Cont ID  
Sent By rmcphers Date 2021-10-27 Time 15:43 Rev Time 0.00
Received By rmcphers Date 2021-10-27 Time 15:43 Sent To  
Notes
2021-10-27 15:47:18PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-14 Cont ID  
Sent By medwards Date 2021-10-14 Time 13:27 Rev Time 0.00
Received By medwards Date 2021-10-14 Time 13:27 Sent To  
Notes
2021-10-14 13:27:451ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21090225
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE COMCHECK IS FOR MIAMI, FLORIDA WITH NO ADDRESS
 IN WEST PALM BEACH. PLEASE PROVIDE THE CALCULATIONS FOR
 THE ADDRESS IN THE CITY OF WEST PALM BEACH FLORIDA. FBC
 107.2.1
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS WITH THE CORRECT ADDRESS IN WEST PALM
 BEACH. FBC 107.2.1
  
 3) SHEET M-1.0: PLEASE REFERENCE THE CORRECT CODE
 SECTIONS IN THE EQUIPMENT NOTES: FBC M 301.15- WIND
 RESISTANCE; 301.16- FLOOD HAZARD
  
 4) PLEASE SHOW HOW YOU WILL MEET THE VENTILATION OF THE
 RESIDENTIAL LIVING UNITS. FBC M 402, 403
  
 5) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THE
 PUBLIC SPACES IN THIS BUILDING. FBC M 403.3.1.1 & TABLE
 403.3.1.1
  
 6) PLEASE PROVIDE MECHANICAL DRAWINGS SHOWING THE
 MECHANICAL SYSTEMS AND DUCTWORK FOR THE PUBLIC AREAS OF
 THE FIRST FLOOR. FBC 107.2.1
  
 7) PLEASE PROVIDE THE CALCULATIONS FOR THE PARKING
 GARAGE VENTILATION CALCULATIONS. FBC M TABLE 403.3.1.1
 & 502.13 & 404
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-10-29 Cont ID  
Sent By lcrespo Date 2021-10-29 Time 12:55 Rev Time 0.00
Received By lcrespo Date 2021-10-27 Time 13:34 Sent To  
Notes
2021-10-29 12:56:1910/29/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE NOW,
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET G-0, THERE IS A LIST OF DRAWINGS MISSING;
 L-S1, A3-103, AND S, M, E, P ARE NOT LISTED. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 2. ON SHEET G-1;
  
 A. UNDER CODES STANDARDS, THERE IS NO SAFE HARBOR
 MENTIONED FOR FHA. ARE YOU USING THE DESIGN MANUAL OR
 THE GUIDELINES? WOULD YOU PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. WOULD YOU PLEASE PROVIDE THE EDITION USED IN THE
 2020 CODES MENTIONED PER THE WPB AMENDMENTS TO FBC
 102.3 APPLICATION OF REFERENCES.
  
 3. ON SHEET G-2;
  
 A. UNDER GOVERNING CODES, THERE IS NO SAFE HARBOR
 MENTIONED FOR FHA. ARE YOU USING THE DESIGN MANUAL OR
 THE GUIDELINES? WOULD YOU PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. WOULD YOU PLEASE PROVIDE THE EDITION USED IN THE
 GOVERNING CODES MENTIONED PER THE WPB AMENDMENTS TO FBC
 102.3 APPLICATION OF REFERENCES.
  
 4. ON SHEET LS-01;
  
 A. WOULD YOU PLEASE PROVIDE THE TABLE USED AND THE
 NUMBER OF OCCUPANTS IN THE PLUMBING FIXTURE COUNT FOR
 THE LOBBY, RETAIL AREA, AND COMMERCIAL SPACE PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 5. ON SHEET A1-1.02;
  
 A. WOULD YOU PLEASE LABEL THE UNIT TYPE THAT ARE FHA,
 EITHER A OR B WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. ON SHEET A1-1.03;
  
 A. WOULD YOU PLEASE PROVIDE THE TABLE USED FOR THE
 STORMWATER PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. WOULD YOU PLEASE CORRECT THE SCUPPER DETAIL NOTE; IT
 SAYS A6 BUT IS A7-107 DETAIL 10.
  
 C. WOULD YOU PLEASE PROVIDE THE SQUARE FOOTAGE BEING
 DRAINED TO DETERMINE THE GPM AND SHOW THE SIZE OF THE
 ROOF DRAIN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. ON SHEET A1-201;
  
 A. PLAN NOTES SAY REFER TO SHEET A0-0.00 AND NO SUCH
 PAGE. WOULD YOU PLEASE PROVIDE THE CORRECT PAGE NUMBER
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS? THIS IS A
 TYPICAL COMMENT FOR OTHER PAGES
  
 B. GENERAL NOTES REFERS TO THE CITY OF MIAMI BEACH.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 8. ON SHEET A1-301, 302, AND 303;
  
 A. PLAN NOTES SAY REFER TO SHEET A0-0.00 AND NO SUCH
 PAGE. WOULD YOU PLEASE PROVIDE THE CORRECT PAGE NUMBER
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. GENERAL NOTES REFERS TO THE CITY OF MIAMI BEACH.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. WOULD YOU PLEASE LABEL THE UNIT TYPE THAT ARE FHA,
 EITHER A OR B WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 FHA ON THE SINK, IN FRONT OF THE REFRIGERATOR, TUB,
 LAV, AND TOILET. WOULD YOU PLEASE SHOW PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 9. ON SHEET A4-102;
  
 A. THE ELEVATOR SHOWS A PIT, AND IN THE PIT, WILL THERE
 BE A PUMP TO PUMP OUT WATER? IF SO, WOULD YOU PLEASE
 PROVIDE DETAIL THAT HAS A PUMP DETAIL AND SHOW AN
 INDIRECT WASTE ON FLAT AND ISOMETRIC DRAWINGS? WOULD
 YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 10. ON SHEET A4.103;
  
 A. IN SOME APPLICATIONS OF A TRASH SHOOT, THERE IS A
 SANITIZING DISPENSER ON THE TOP FLOOR. IF ONE WILL BE
 PROVIDED WOULD YOU, PLEASE SHOW A DETAIL ALONG WITH
 SHUTOFF AND AN ATMOSPHERIC VACUUM BREAKER THAT COMPLIES
 WITH THE 2020 FBC P 608.14.6ATMOSPHERIC-TYPE VACUUM
 BREAKERS.
  
 B. IT MOTIONS A HOSE BIBB IN THE GENERAL NOTES. WOULD
 YOU PLEASE SHOW THE ISOMETRIC AND THE LOCATION AND GIVE
 THE DETAILED SECTION SHEET PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 11. ON SHEET A1-501;
  
 A. WOULD YOU PLEASE LABEL THE UNIT TYPE THAT ARE FHA,
 EITHER A OR B PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 FHA ON THE SINK, IN FRONT OF THE REFRIGERATOR, TUB,
 LAV, AND TOILET PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. THE FAIR HOUSING ACT PROVIDES TWO SETS OF
 SPECIFICATIONS TO DESIGN BATHROOMS THAT ARE USABLE BY
 PEOPLE WITH DISABILITIES. THOUGH THERE ARE OTHER
 DIFFERENCES, SPECIFICATION B BATHROOMS OFFER GREATER
 ACCESS TO THE TUB THAN SPECIFICATION A BATHROOMS.
  
 IF THE SPECIFICATION A DESIGN IS SELECTED, ALL
 BATHROOMS IN THE UNIT MUST COMPLY WITH THE
 SPECIFICATION A STANDARD (SECTION 7.14). THIS INCLUDES
 ACCESS TO ALL FIXTURES IN EACH SPECIFICATION A BATHROOM
 (E.G., TWO LAVATORIES IN ONE BATHROOM WOULD BOTH NEED
 TO MEET FHA REGULATIONS).
  
 IF THE SPECIFICATION B DESIGN IS SELECTED, ONLY ONE
 BATHROOM IN THE UNIT, AND ONLY ONE OF EACH TYPE OF
 FIXTURE WITHIN THE BATHROOM, MUST COMPLY WITH
 SPECIFICATION B STANDARDS (SECTION 7.15). ALL OTHER
 BATHROOMS IN THE UNIT MUST MEET THE USABLE BATHROOM
 REQUIREMENTS (SECTION 7.11), EXEMPTING MANEUVERING
 CLEARANCES, AND CLEAR FLOOR SPACE REQUIREMENTS AT
 FIXTURES. THE TOP FIXTURE RIM IS A MAXIMUM OF 34 INCHES
 AFF, WITH THE APRON AT LEAST 27 INCHES AFF. IN
 INSTANCES WHERE REMOVABLE CABINETRY IS PROVIDED, PIPES
 ARE COVERED FOR PROTECTION; INSULATION AROUND PIPES, OR
 ADDING A FIXED, ONE-PIECE PROTECTION PANEL.
  
 F. FOR ALL BATHROOM DIMENSIONS OF THE FIXTURES SHALL
 COMPLY WITH THE 2020 FBC SEC. P 405.3.1 WATER CLOSETS
 AND LAVATORIES. THE FHA HAS SOME DIMENSIONS THAT MAY BE
 DIFFERENT. SHOW THE DEPTH OF THE NEW VANITY. THE VANITY
 SHALL BE A MAXIMUM OF 24 INCHES DEEP PER THE FAIR
 HOUSING ACT. ADDITIONAL REINFORCEMENT MAY BE REQUIRED
 IN THE WALLS AROUND THE TUB TO ALLOW FOR THE FUTURE
 INSTALLATION OF GRAB BARS PER THE FAIR HOUSING ACT.
  
 G. SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE TUB OR
 SHOWER IN ACCORDANCE WITH THE FAIR HOUSING ACT.
  
 12. ON SHEET A5-1.02;
  
 A. UNDER NOTE, IT REFERS TO THE FBC 2014 R 307.2, WHICH
 IS THE WRONG CODE YEAR, AND OTHER COMMENTS ABOUT THE
 SHOWER THAT HAS NOTHING TO DO WITH THIS DRAWING. WOULD
 YOU PLEASE REMOVE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. UNDER INTERIOR FISHES, THERE ARE SHOWER GLASS
 COMMENTS THAT DON'T PERTAIN TO THIS DRAWING. WOULD YOU
 PLEASE REMOVE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. THESE RESTROOMS ARE TO COMPLY WITH THE 2020 FBC
 ACCESSIBILITY CODE. PLEASE PROVIDE THIS INFORMATION ON
 THIS PAGE PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. WOULD YOU PLEASE GIVE DIMENSIONS FOR FIXTURE
 CLEARANCES PER FLORIDA BUILDING CODE AND FLORIDA
 ACCESSIBILITY CODE FOR TOILET AND LAV.
  
 E. PLEASE SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS FOR THE LAVATORY PER THE 2020 FBC ACC SEC.
 606.2 CLEAR FLOOR SPACE. THE LAV NEEDS TO SHOW THE
 DIMENSIONS OF THE CLEAR FLOOR SPACE OF 30? X 48? PER
 THE 2020 FBC SEC. ACC 305.3.
  
 F. THE BOTTOM ON THE LAV SHALL BE A MINIMUM OF 27" KNEE
 CLEARANCE PER THE 2020 FBC SEC. 306.3.
  
 G. WOULD YOU PLEASE SHOW THE WATER CLOSET FLUSH CONTROL
 LOCATION PER THE 2020 FBC SEC. 604.6 FLUSH CONTROLS.
  
 H. WOULD YOU PLEASE SHOW THE FLUSH CONTROLS SHALL BE
 LOCATED ON THE OPEN SIDE OF THE WATER CLOSET PER THE
 2020 ACC SEC. 604.6 FLUSH CONTROLS.
  
 J. THE WATER CLOSET IN THE ACCESSIBLE RESTROOM SHALL BE
 TO THE CENTERLINE OF THE WATER CLOSET 16 INCHES MINIMUM
 TO 18 INCHES MAXIMUM FROM THE SIDE WALL PER THE 2020
 FBC ACC. SEC. 604.2 LOCATION.
  
 K. THE GRAB BARS ARE NOT SHOWN. WOULD YOU PLEASE SHOW
 THEM MEASURED TO THE TOP OF THE GRIPPING SURFACE PER
 THE 2020 FBC ACC SEC. 609.4.
  
 L. WOULD YOU PLEASE SHOW THE GRAB BARS, WHICH SHALL BE
 INSTALLED IN A HORIZONTAL POSITION PER THE 2020 FBC ACC
 SEC. 609.4.
  
 L. WOULD YOU PLEASE SHOW THE HORIZONTAL GRAB BARS WHICH
 NEED TO BE MEASURED TO THE CENTER OF THE BAR PER THE
 2020 FBC ACC SEC. 604.5.1 SIDE WALL AND 604.5.2 REAR
 WALL.
  
 M. WOULD YOU PLEASE SHOW THE HORIZONTAL GRAB BARS ON
 THE REAR TO BE MEASURED TO THE CENTER OF THE WATER
 CLOSET TO 12 INCHES TO THE WALL AND 24 INCHES TO THE
 OPEN SIDE PER THE 604.5.1 SIDE WALL AND 604.5.2 REAR
 WALL.
  
 N. WOULD YOU PLEASE PROVIDE CABINET DETAIL SHOWING THE
 SINK AND OR LAVS HEIGHT OF 34 INCHES MAXIMUM PER THE
 2020 FBC ACC SEC. 606.3.
  
 O. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE
 SIDEWALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR
 FROM THE REAR WALL PER THE 2020 FBC ACC. SEC. 604.3.1.
  
 P. THE DOORS ARE SWINGING IN THE CLEAR FLOOR SPACE OF
 THE LAVS. WOULD YOU PLEASE SHOW THE TURNING SPACE
 DIAMETER- SPACE OF 60 INCHES DIAMETER MINIMUM AND
 INSIDE OF THAT THE 30 INCHES BY 60 INCHES PER THE 2020
 FBC ACC SEC. 304.3. YOU CAN ALSO HAVE THE DOOR SWING
 OUT AND NOT SHOW THIS.
  
 Q. WOULD YOU PLEASE SHOW THE TOILET PAPER DISPENSERS
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF
 DISPENSER PER THE 2020 FBC ACC SEC. 604.7.
  
 R. WOULD YOU PLEASE PROVIDE A NOTE OR SHOW THE LAVATORY
 WATER SUPPLY AND DRAINPIPES UNDERSIDE THAT SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT PER THE 2020 FBC ACC SEC. 606.5.
  
 S. WOULD YOU PLEASE SHOW THE TOILET SEAT TO BE 17
 INCHES TO 19 INCHES MAXIMUM MEASURED TO THE TOP OF THE
 SEAT PER THE 2020 FBC ACC SEC. 604.4 SEATS.
  
 T. WOULD YOU PLEASE SHOW THE REFLECTIVE PART OF THE
 MIRROR NEEDS TO BE THE 40" TO THE REFLECTIVE SIDE PER
 THE 2020 FBC ACC SEC. 603.3.
  
 U. WOULD YOU PLEASE PROVIDE A NOTE THAT THE SEATS OF
 WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER 2020 FBC P
 425.3 WATER CLOSET SEATS
  
 13. ON SHEET A5-103;
  
 A. DETAIL ONE SHOWS A U SHAPE, AND A 60-INCH TURNING
 CIRCLE IS REQUIRED. WOULD YOU PLEASE AND PER THE FHA
 PAGE 7.9.
  
 14. ON SHEET A5-104;
  
 A. THE DETAIL FOR THE GRAB BARS IS NOT REQUIRED AS THEY
 DO NOT NEED TO BE INSTALLED FOR COMPLIES, AND ONLY THE
 BACKING NEEDS TO BE SHOWN. WOULD YOU PLEASE DELETE TO
 PREVENT FIELD CONFUSION PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. WOULD YOU PLEASE SHOW THE WATER CLOSET DIMENSIONS
 THAT COMPLY WITH THE DESIGNED BATHROOMS AS PER PAGE
 7.43 OF THE FHA DESIGN MANUAL.
  
 C. WOULD YOU PLEASE SHOW THE HEIGHT OF THE LAV IN THE
 SPECIFICATION TYPE "B" WILL BE THE USE OF 34 INCHES IN
 THE BATHROOMS AS PER FHA DESIGN MANUAL PAGE 7.52.
  
 15. ON SHEET A7-1.09;
  
 A. THE FIRE PENETRATIONS FOR CAJ 2392, WL 12, AND WL
 2128 FROM HILTI HAVE VERY LIGHT VERBIAGE. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 16. ON SHEET P-1.0;
  
 A. WOULD YOU PLEASE SHOW THE ADA FIXTURES SCHEDULE FOR
 THE ACCESSIBLE RESTROOM PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. UNDER PLUMBING FIXTURES FOR COMMENT ONE, IT REFERS
 TO MIAMI DADE COUNTY AMENDMENTS. WE HAVE OUR
 AMENDMENTS, AND A COPY CAN BE FURNISHED BY CONTACTING
 ME IF YOU LIKE. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 C. IN THOSE SAME COMMENTS, TWO AND THREE ARE NOT THE
 CORRECT CODE REFERENCES, AND WOULD YOU PLEASE GIVE THE
 WHOLE YEAR AND EDTION YOU REFER TO PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION? ON
 CONSTRUCTION DOCUMENTS.
  
 D. UNDER PLUMBING GENERAL NOTES, NUMBER 16 REFERS TO
 STACKS WITH A CLEANOUT AT THE BASE OF STACK OR VENT AND
 IN THE NEW CODE CYCLE THAT WAS ELIMINATED. THAT MAY BE
 AN RFI IN THE FIELD. THE INSPECTOR MAY ASK TO BE
 INSTALLED IN DRAWING, WHICH MOST PLUMBING CONTRACTORS
 DO NOT DO ANYMORE. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 E. ON THOSE SAME NOTES FOR NUMBER 19, IT SAYS
 UNDERGROUND PIPING TO BE HUNG FROM THE SLAB. YOU MAY
 KEEP THAT BUT NOT REQUIRED BY OUR CODE. IF SO, WOULD
 YOU PROVIDE DETAIL ON HOW DISTANCE AND MATERIALS ARE
 BEING USED PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 F. ON NUMBER 23, THE ANTI-SCALDING THE 110, I PRESUME,
 IS THE TEMPERATURE WHICH IN THE CODE IS 120 PER THE
 2020 FBC SEC. P 412.3INDIVIDUAL SHOWER VALVES. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 G. WOULD YOU PLEASE PROVIDE DETAIL FOR THE TANKLESS AND
 SPECIFICATIONS IN THE UNITS AND THE COMMERCIAL PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 17. ON SHEET P-2.0;
  
 A. THE WATER ISOMETRIC SHOWS THE WATER FOR BOTH IN ONE
 SERVICE LINE FOR HOT WATER AND THE COLD PER THE 2020
 FBC SEC. P 606.1 (6) LOCATION OF FULL-OPEN VALVES.
 WOULD YOU SEPARATE THEM AS THEY ARE INDIVIDUAL UNITS,
 AND BUILD-OUT MAY CAUSE ISSUES IN THE FUTURE? PLEASE
 SHOW ITS OWN WATER SERVICE AND HOT TANKLESS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. WOULD YOU PLEASE SHOW SHUT-OFF VALVES FOR ALL RISERS
 WITH ACCESS PANELS IN THE GARAGE AREA PER THE 2020 FBC
 SEC? P 606.1 (4) LOCATION OF FULL-OPEN VALVES.
  
 C. WOULD YOU PLEASE SHOW ON THE ISOMETRIC A TRAP PRIMER
 AND ITS SOURCE PER THE 2020 FBC SEC. 1002.4.1 TRAP SEAL
 PROTECTION.
  
 D. WOULD YOU PLEASE SHOW THE CLEANOUT ON THE BUILDING
 DRAIN PER THE 2020 FBC SEC. P 708.1.3BUILDING DRAIN AND
 BUILDING SEWER JUNCTION.
  
 E. WOULD YOU PLEASE SHOW A BACKFLOW DEVICE NEXT TO THE
 METER AND PUT A SEPARATE PERMIT REQUIRED FOR THE
 BACKFLOW DEVICE PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 18. ON SHEET P-2.2;
  
 A. CORRECTION NEEDS TO BE MADE TO THE PLUMBING LAYOUT.
 PLEASE REFER TO COMMENT 20 TO MATCH SANITARY RISER PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 B. WASHING MACHINE VALES SHALL BE ACCESSIBLE WITHOUT
 MOVING THE UNIT PER THE 2020 FBC SEC. P 606.3.
 ACCESSIBLE SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL
 OF AN ACCESS PANEL OR SIMILAR REMOVABLE OBSTRUCTION.
  
 19. ON SHEET P-3.0;
  
 A. IN THE GENERAL SANITARY RISER, WOULD YOU PLEASE SHOW
 A CLEANOUT ON EACH ENTRANCE TO THE BUILDING (COMMERCIAL
 SPACE AND UNITS). THE FOUR-INCH CLEAN-OUT-UP MAY NEED
 TO BE MOVED BEFORE THE WYE AND ADD ONE DOWNSTREAM OF
 THE WYE PER THE 2020 FBC SEC. 708.1.3BUILDING DRAIN AND
 BUILDING SEWER JUNCTION.
  
 B. IN THE GENERAL WATER RISER, THERE IS ONE METER, BUT
 IT GOES UP AND FEEDS TWO UNITS SHOULD THEY BE IN THE
 UNITS AND BE TWO INSTEAD OF ONE. WOULD YOU PLEASE
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. IN THAT SAME RIDER, THE COLD LINE TO THE COMMERCIAL
 SPACE IS MISSING A DIMENSION BEFORE IT TEES OFF FROM
 THE 1 1/4 LINE. WOULD YOU PLEASE ADD THE SIZE PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 D. THERE IS NO ISOMETRIC FOR THE CONDENSATE LINES WITH
 A P-TRAP AND UNDER 2020 FBC M307.2.4 AND P1002.1. EACH
 TRAP SHALL BE VENTED TO PERMIT THE ADMISSION OR
 EMISSION OF AIR SO THAT THE SEAL OF ANY FIXTURE TRAP
 SHALL NOT BE SUBJECTED TO A PRESSURE DIFFERENTIAL OF
 MORE THAN 1 INCH OF WATER COLUMN PER THE 2020 FBC
 SECTION 901.2 TRAP SEAL PROTECTION. THE CONDENSATE LINE
 SHOULD SHOW A VENT TERMINATION AND LOCATION, AND THEY
 CANNOT TERMINATE IN A WALL AS IT HAS NO NEGATIVE OR
 POSITIVE PRESSURE TO HAVE A DIFFERENTIAL OF ONE-INCH
 WATER COLUMN. WOULD YOU PLEASE PROVIDE DETAIL OF HOW
 THEY WILL BE VENTED PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. IF
 TERMINATION IN PLENUM, IT MUST BE CPVC THAT HAS THE
 REQUIRED SMOKE INDEX.
  
 E. CONDENSATE IS NOT PERMITTED TO DISCHARGE INTO THE
 CITY'S SANITARY SYSTEM PER CITY ORDINANCE CHAPTER 90,
 ARTICLE III, SEC.90-126 (B)(5). THEY SHALL DISPOSE OF
 IN A SAFE LOCATION OR A DRY WELL. IF A DRY WELL WILL BE
 USED, WOULD YOU PLEASE PROVIDE DETAILS OF THE DRY WELL
 FOR THE CONDENSATE LINE PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 E. WOULD YOU PLEASE SHOW STORM LINES ON THE LAYOUT AND
 ISOMETRIC WITH ITS SIZE AND LOCATION OF TERMINATION PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 F. HOSE BIBB NOT SHOWN FOR THE TRASH SHOOT, AND IF ANY
 OTHER HOSE BIBB IS REQUIRED FOR THE COMMON AREAS, WOULD
 YOU PLEASE SHOW A SHUT-OFF VALVE PER THE 2020 FBC SEC.
 P 606.2 (2) LOCATION OF SHUTOFF VALVES.
  
 20. ON SHEET P-3.01;
  
 A. ON ALL SANITARY RISERS, THE FIXTURE DRAIN FOR THE
 STANDPIPE SERVING AN AUTOMATIC CLOTHES WASHER SHALL
 CONNECT TO A 3-INCH OR LARGER DIAMETER FIXTURE BRANCH
 OR STACK PER THE 2020 FBC SEC. R 406.2 WASTE
 CONNECTION.
  
 B. IN THE SAME RISERS, BATHROOM GROUPS ( D, C AND E)
 HAVE THE TOILET AND THE SHOWER NOT VENTED. THE VENT
 NEEDS TO GO BETWEEN THE TOILET AND THE SHOWER OR USE A
 DOUBLE WYE PATTERN AS EACH TRAP SHALL BE VENTED PER THE
 2020 FBC SEC. 910.1 INDIVIDUAL VENTS PERMITTED.
  
 C. THE ISOMETRIC DOES NOT SHOW VALVES TO SHUT OFF EACH
 UNIT IN SOME UNIT TYPE WITH THE CONNECTION IS UNCLEAR.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2022-04-20 Time   Rev Time 0.00
Received By   Date 2022-04-20 Time   Sent To  
Notes
2022-04-20 14:23:09 
 PLEASE PROVIDE THE FOLLOWINGS:
 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND
 QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR)
 THAT WILL BE UTILIZED THAT WILL BE UTILIZED FOR THE
 SANITATION SERVICE.
 2- DUMPSTER ENCLOSURE DETAIL. DETAILS FOR SANITATION
 SERVICE (I.E. SOLID WASTE CONTAINER(S) TYPE, COLLECTION
 LOCATION, ETC.). FOR A FREESTANDING SITE DUMPSTER
 ENCLOSURE, THE ENCLOSURE SHALL COMPLY WITH THE LATEST
 REVISION OF CITY OF WEST PALM BEACH GENERAL
 CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, GC-7. (LINK TO
 THE LATEST REVISION OF THE GC-7 DOCUMENT: HTTPS://WWW.W
 PB.ORG/HOME/SHOWPUBLISHEDDOCUMENT/3690/6376290604221000
 00)
 3- AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE VEHICLE?S
 WHEEL PATH) FOR THE SANITATION SERVICE, FRONT LOADER
 TRUCK WITH THE FOLLOWING SPECS:
 - DUAL AXLES
 - TRUCK LENGTH: 35 FT
 - TRUCK WIDTH: 11 FT
 - TURNING RADIUS:
 - SAE TURNING RADIUS: 32.5 FT
 - CURB-TO-CURB DIAMETER: 74 FT
 - WALL-TO-WALL DIAMETER: 86.3 FT
 4- CONTINGENCY PLAN, FOR WHEN THE COMPACTOR IS OUT OF
 SERVICE (I.E. CITY DUMPSTER, ROLL-OFF CONTAINER)
 5- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND
 RECYCLING CONTAINERS
 6- OWNERS AND/OR OCCUPANTS OF PROPERTY THAT REQUIRE
 GREASE HAULING SERVICES SHALL ENSURE THAT THEIR GREASE
 TANKS OR CONTAINERS REMAIN CLEAN, AND ARE ENCLOSED AND
 NOT IN PUBLIC VIEW.
  
 7- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN
 THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF
 THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC
 WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND
 COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING
 MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE
 CAN(S).
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-10-27 Cont ID  
Sent By rmcphers Date 2021-10-27 Time 15:47 Rev Time 0.00
Received By rmcphers Date 2021-10-27 Time 15:47 Sent To  
Notes
2021-10-27 15:49:38SEE BUILDING REVIEW
 PLEASE PROVIDE A COPY OF THE PRODUCT APPROVALS (NOA'S)
 THAT ARE LISTED ON THE DRAWINGS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-10-27 Cont ID  
Sent By rmcphers Date 2021-10-27 Time 16:03 Rev Time 0.00
Received By rmcphers Date 2021-10-27 Time 16:02 Sent To  
Notes
2021-10-27 16:06:12SIGNATURE REVIEW
  
 ALL A, G, LS, SP DRAWINGS AND THE SOIL REPORT DO NOT
 SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-10-01 Cont ID  
Sent By llouie Date 2021-10-01 Time   Rev Time  
Received By llouie Date 2021-10-01 Time   Sent To  
Notes
2021-10-01 10:20:57** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROJECT CANNOT BE SUBMITTED FOR BUILDING PERMIT
 UNTIL APPROVED THROUGH THE SITE PLAN APPROVAL PROCESS.
 A PRE-APPLICATION MEETING WITH PLANNING STAFF AND
 SUBMISSION OF A 2021 DEVELOPMENT APPLICATION IS
 REQUIRED AS PART OF THE SITE PLAN APPROVAL PROCESS.
 THERE IS CURRENTLY NO RECORD OF A SITE PLAN APPLICATION
 WITH THE PLANNING DIVISION.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: BMUD-TYPE II; ABUTS RESIDENTIAL TO THE WEST.
  