Plan Review Stops For Permit 21090139 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2021-09-16 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2021-09-16 |
Time |
16:08 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2021-09-16 |
Time |
16:08 |
Sent To |
|
|
Notes |
2021-09-16 16:09:06 | NEW BUILDING WITHIN ADDRESS RANGE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2021-11-06 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-11-06 |
Time |
08:37 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-11-06 |
Time |
08:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-09-30 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-09-30 |
Time |
15:29 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-09-29 |
Time |
13:07 |
Sent To |
|
|
Notes |
2021-09-30 15:33:57 | BUILDING PLAN REVIEW | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | PLANS EXAMINER II PX3169/SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | DEVELOPMENT SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | (561) 805-6726 | | [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | 2017 NEC | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. PROVIDE A COPY OF THE CURRENT BOUNDRY LINE SURVEY. | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2021-09-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-09-28 |
Time |
11:37 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-09-28 |
Time |
11:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2021-10-25 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-10-25 |
Time |
07:55 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-10-25 |
Time |
07:55 |
Sent To |
|
|
Notes |
2021-10-25 07:55:26 | 10/25/21 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2021-09-23 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-09-23 |
Time |
12:56 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-09-23 |
Time |
12:56 |
Sent To |
|
|
Notes |
2021-09-23 13:31:16 | 09/23/21 1 ST GAS REVIEW**DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. WOULD YOU PLEASE SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE | | PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2. | | | | 2. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL | | BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC. | | G2413. | | | | 3. MOST TANKLESS UNITS CALL FOR A 10.5" WATER COLUMN, | | AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN | | REQUIRING A REGULATOR FOR THIS UNIT AS PER THE | | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S | | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS | | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE | | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. | | SEC. G2421.1. | | | | 4. WOULD YOU PLEASE PROVIDE MANUFACTURES SPECIFICATIONS | | FOR ALL GAS EQUIPMENT PER THE WPB AMENDMENTS TO THE FBC | | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 5. WOULD YOU PLEASE SHOW ON PLANS THE LOCATION OF THE | | TANK-LESS WATER HEATER AND THE LOCATION AND DISTANCE OF | | ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER | | HEATER? THE LOCATION OF THE WATER HEATER SHALL COMPLY | | WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE | | HOUSE PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO | | THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION | | DOCUMENTS. | | | | 6. GAS UNITS MAY REQUIRE CONDENSATE, AND THEY NEED TO | | BE 1' AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC | | R318.5. A NOTE ON ISO WILL BE OK. | | | | 7. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE | | INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE | | 403.5.3. A NOTE ON ISO WILL BE OK. | | | | 8. THE GRILL SEEMS TO BE IN A COVERED PATIO; IF SO, | | PLEASE PROVIDE THE MANUFACTURER'S RECOMMENDATION FOR A | | VENTILATION HOOD PER THE 2020 FBC RES. SEC. G2408.1. | | THE GRILL MAY REQUIRE A VENT IF IN THE CABINET. | | | | 9. WOULD YOU PLEASE LABEL AND SHOW ALL UNIONS IN FRONT | | OF REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES. | | SEC G2421.2. | | | | 10. WOULD YOU PLEASE LABEL THE SHUTOFF VALVE ON GAS | | ISOMERIC PER THE 2020 FBC FG SEC. 409.5 OR 2020 FBC | | RES. SEC. G2420.5. | | | | 11. THE SHUT-OFF INSIDE SHALL BE ACCESSIBLE WITHOUT | | MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202) | | GD, ACCESS. A NOTE ON ISO WILL BE OK. | | | | 12. DRIP LEG ON EQUIPMENT IS SHOWN INSTALLED | | INCCORECTLY. WOULD YOU PLEASE REFER TO THE 2020 FBC R | | FIGURE G2419.4 (408.4) METHOD OF INSTALLING A TEE | | FITTING SEDIMENT TRAP | | | | 13. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2020 | | FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES DRYERS). | | | | 14. IF USING LOVERS FOR COMBUSTION AIR, PLEASE SHOW THE | | LOCATION OF THE LOUVERS THAT ARE BEING INSTALLED. THE | | LOUVERS CANNOT BE LOCATED ON AN EXTERIOR WALL THAT IS | | FIRE RATED AS THE FIRE RATING OF THE WALL MUST BE | | MAINTAINED PER THE WPB AMENDMENTS TO FBC SEC.107.2.1. | | | | 15. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE | | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT | | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE FBC | | RES. SEC. G2413.2 AND G2404.3. | | | | 16. WOULD YOU PLEASE PROVIDE THE TABLE USED IN THE | | DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS | | OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR | | ANOTHER STANDARD USED IN THE DESIGN OF THIS SYSTEM PER | | THE 2020 FBC RES. SEC. G2413.3. | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2021-11-19 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-11-19 |
Time |
10:10 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-11-09 |
Time |
15:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-11-06 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-11-06 |
Time |
08:37 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-10-20 |
Time |
10:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-09-30 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-09-30 |
Time |
15:44 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-09-15 |
Time |
12:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2021-11-30 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-11-30 |
Time |
09:47 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-11-19 |
Time |
10:19 |
Sent To |
|
|
Notes |
2021-11-29 11:12:00 | RECEIPT - MU-2021-055436 - $2404.37 PAID | 2021-11-19 10:19:30 | 11/19/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2021-09-30 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-09-30 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-09-30 |
Time |
13:54 |
Sent To |
|
|
Notes |
2021-09-30 13:55:45 | IMPACT FEE QUESTIONNAIRE | | | | PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT | | LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO | | THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF. | | THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ | | B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE | | RECEIPT TO PROJECT DOX OR EMAIL IT TO | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2021-09-23 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-09-23 |
Time |
08:48 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-09-23 |
Time |
08:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2021-10-25 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-10-25 |
Time |
07:54 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-10-25 |
Time |
07:54 |
Sent To |
|
|
Notes |
2021-10-25 07:56:06 | 10/25/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2021-09-23 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-09-23 |
Time |
12:54 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-09-23 |
Time |
10:13 |
Sent To |
|
|
Notes |
2021-09-23 12:55:27 | 09/23/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. ON SHEET P1.1, THE SANITARY LINES ARE SHOWN COMING | | IN AT DIFFERENT POINTS, WHICH CONSTRUED A NEW SYSTEM AT | | EACH ENTRY. AS IT ENTERS THE BUILDING, IT IS CONSIDERED | | A BUILDING DRAIN THAT REQUIRES A VENT THROUGH THE ROOF | | AND CLEAN-OUT FOR EACH SYSTEM. YOU MAY MINIMIZE THIS BY | | DOING TWO, ONE ON EACH SIDE. WOULD YOU PLEASE REFER TO | | THE FOLLOWING 2020 FBC R P3005.2.3 BUILDING DRAIN AND | | BUILDING SEWER JUNCTION AND R3102.1 REQUIRED VENT | | EXTENSION, THE VENT SYSTEM SERVING EACH BUILDING DRAIN | | SHALL HAVE NOT LESS THAN ONE VENT PIPE; THAT EXTENDS TO | | THE OUTDOORS? | | | | 2. ON SHEET P1.2; | | A. THERE IS A WATER FEATURE IN THE COURTYARD. WOULD YOU | | PLEASE PROVIDE A DETAIL AND BACKFLOW DEVICE BEING USED | | UNDER THE PLUMBING FIXTURE CONNECTION SCHEDULE ON PAGE | | P1.0 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 | | (12) RESIDENTIAL PLUMBING. | | | | B. THERE IS A BACKFLOW DEVICE AT THE METER THAT | | PROTECTS THE CITY OF WEST PALM BEACH WITH THEIR | | UTILITIES DEPARTMENT; CROSS CONNECTION PROGRAM MAY NEED | | TO BE A REDUCED PRINCIPAL VACUUM BREAKER. THE SECOND | | BACKFLOW IS A PRESSURE VACUUM BREAKER AT THE METER, BUT | | K COPPER IS NOT ALLOWED ON THE SIDE FROM THE METER TO | | THE DEVICE, ONLY L COPPER. WOULD YOU PLEASE CONTACT | | THEM TO DETERMINE WHAT THE NEEDED AT 561-822-2240? | | | | C. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW | | DEVICES PER THE WPB AMENDMENTS TO FBC SEC. 105.1. | | | | D. HOT WATER LINES UNDER SLAB NOT IN CONDITION SPACE | | NEED TO BE INSULATED WITH A MINIMUM R-3 PER THE 2020 | | FBC SEC. RE 403.5.3. PLEASE PLACE A NOTE. | | | | E. IF THE TANKLESS HAS A CONDENSATE, IT NEEDS TO BE 1' | | AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC. R318.5. | | | | 3. ON SHEET P1.4; | | A. ON THE ISOMETRIC FOR THE HOT WATER RECIRCULATING | | SYSTEM, THERE IS NO CONTINUOUS LOOP ON THE SYSTEM AS IT | | TEE?S OFF IN SEVERAL LOCATIONS. WOULD YOU PLEASE | | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | B. HOT WATER LINES OUTSIDE NOT IN CONDITION SPACE NEED | | TO BE INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC | | SEC. RE 403.5.3. | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2021-09-30 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-09-30 |
Time |
15:29 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-09-29 |
Time |
13:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2021-11-10 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-11-10 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-11-10 |
Time |
09:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2021-10-25 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2021-10-25 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2021-10-25 |
Time |
14:49 |
Sent To |
|
|
Notes |
2021-10-25 14:51:32 | IT APPEARS PLANS TITLED "C1 AND C2" ARE STILL NOT | | DIGITALLY SIGNED AND SEALED. FOLLOW THE INSTRUSTIONS | | BELOW TO CORRECT THIS ISSUE. | | | | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND | | SIGNED. | | EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF | | APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX, | | OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER | | ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION. | | SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO | | BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED | | DOCUMENTS ARE PREFERRED. | | | | PLEASE EMAIL [email protected] AND CC TO | | [email protected] | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2021-09-30 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-09-30 |
Time |
15:43 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-09-30 |
Time |
15:35 |
Sent To |
|
|
Notes |
2021-09-30 15:44:07 | SIGNATURE REVIEW | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | PLANS EXAMINER II PX3169/SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | DEVELOPMENT SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | (561) 805-6726 | | [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | NEC2017 | | | | 1ST REVIEW | | RESULTS: DENIED | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | RE: PLAN PAGES C1 AND C2 | | | | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR | | DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL | | SIGNATURE. | | | | 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR | | DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL | | WET SEAL AND SIGNATURE TO: | | | | BUILDING DIVISION, FIRST FLOOR | | CITY OF WEST PALM BEACH | | 401 CLEMATIS ST | | WEST PALM BEACH, FL 33401 | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2021-11-18 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2021-11-18 |
Time |
17:38 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2021-11-18 |
Time |
17:25 |
Sent To |
|
|
Notes |
2021-11-18 17:34:22 | PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES OR | | PALMS, YOU MUST HAVE AN ISSUED TREE ALTERATION PERMIT. | | | | SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR: | | | | A. DRIVEWAY/APPROACH | | B. IRRIGATION | | C. POOL, POOL EQUIPMENT, AND POOL DECK. | | D. FIRE PIT | | E. FENCES AND GATES | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2021-10-25 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2021-10-25 |
Time |
14:43 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2021-10-25 |
Time |
14:08 |
Sent To |
|
|
Notes |
2021-10-25 14:44:18 | FAILED | | | | 1) REPEAT COMMENT: ZONING WILL NOT APPROVE THIS PERMIT | | UNTIL YOU HAVE SUBMITTED A LANDSCAPE PERMIT. PLEASE | | NOTE: THAT PRIOR TO THE REMOVAL OR RELOCATION OF ANY | | TREES OR PALMS, YOU MUST HAVE AN ISSUED TREE ALTERATION | | PERMIT. | | | | SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR: | | | | A. DRIVEWAY/APPROACH | | B. IRRIGATION | | C. POOL, POOL EQUIPMENT, AND POOL DECK. | | D. FIRE PIT | | E. FENCES AND GATES | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2021-09-24 |
|
|
Cont ID |
|
Sent By |
eshneide |
Date |
2021-09-24 |
Time |
16:14 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2021-09-24 |
Time |
15:39 |
Sent To |
|
|
Notes |
2021-09-24 16:15:27 | FAILED | | | | 1) PROVIDE A SURVEY THAT IS LESS THAN ONE YEAR OLD. | | | | 2) ZONING WILL NOT APPROVE THIS PERMIT UNTIL YOU HAVE | | SUBMITTED A LANDSCAPE PERMIT. PLEASE NOTE: THAT PRIOR | | TO THE REMOVAL OR RELOCATION OF ANY TREES OR PALMS, YOU | | MUST HAVE AN ISSUED TREE ALTERATION PERMIT. | | | | 3) PROVIDE THE SETBACK DIMENSIONS FROM THE EDGE OF THE | | CONDENSING UNIT PADS TO THE PROPERTY LINE. THIS | | DIMENSION MAY NOT BE LESS THAN THREE FEET SIX INCHES. | | | | 4) PLEASE PROVIDE THE BUILDING HEIGHT AS DEFINED BY THE | | CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT | | REGULATIONS - BUILDING, HEIGHT OF, MEANS THE VERTICAL | | DISTANCE FROM THE MEAN GRADE OF A LOT AT THE FRONTAGE | | OF THE BUILDING TO THE HIGHEST POINT OF THE TOP OF THE | | STRUCTURE OF A FLAT ROOF, OR TO THE DECK LINE OF A | | MANSARD ROOF, OR TO THE MID-HEIGHT LEVEL BETWEEN EAVES | | AND RIDGE FOR GABLE, HIP, AND GAMBREL ROOFS. THE PLANS | | PROVIDE THE HEIGHT BASED ON THE FINISHED FLOOR AND NOT | | THE FINISHED GRADE OF THE LOT. | | | | SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR: | | | | A. DRIVEWAY/APPROACH | | B. IRRIGATION | | C. POOL, POOL EQUIPMENT, AND POOL DECK. | | D. FIRE PIT | | E. FENCES AND GATES | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] |
|
|