2021-10-12 13:50:49 | SHUTTERS BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21081423 |
| |
| NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| SHALL COMPLY WITH THE MATERIALS AND METHODS |
| REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| |
| 1- REVISE SHUTTERS INSTALLATION SCHEDULE: |
| SHUTTERS INSTALLATION SCHEDULE SPECIFY WOOD AS THE |
| SUBSTRATE. TYPE OF ANCHOR AND MINIMUM EDGE DISTANCE (@ |
| WINODW SILL) SPECIFIED ON THE INSTALLATION SCHEDULE |
| DON'T CORRESPOND TO WOOD SUBSTRATE. SEE WALL HEADER |
| INSTALLATION "M" AND WALL SILL INSTALLATION "R" ON |
| SHEET 16 OF 20 OF SHUTTERS DRAWINGS SUBMITTED AND |
| REVISE AS REQUIRED. |
| NOTE: ANCHORS NEED 1-1/2 MIN. PENETRATION INTO THE WOOD |
| STRUCTURAL MEMBER. |
| |
| NOTE: PRODUCT APPROVAL SUBMITTED IS HIGHLIGHTING ANCHOR |
| SCHEDULES FOR CONCRETE INSTALLATION. PLEASE HIGHLIGHT |
| /MARK ONLY THE ANCHOR SCHEDULES CORRESPONDING TO THE |
| ACTUAL SUBSTRATE TO AVOID CONFLICTS/DELAYS. |
| |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |