Plan Review Stops For Permit 21081320 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2021-09-09 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2021-09-09 |
Time |
10:58 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2021-09-09 |
Time |
10:58 |
Sent To |
|
|
Notes |
2021-09-09 10:59:58 | PASSED WITH PROVISO: A SECOND APPLICATION WILL BE | | REQUIRED FOR THE SECOND HABITABLE BUILDING. CUSTOMER | | INFORMED. EAST BUILDING WILL HAVE THE ADDRESS OF 239 | | MURRAY RD AND WEST BUILDING WILL HAVE THE ADDRESS OF | | 241 MURRAY RD, THIS WILL REPLACE 239 1/2 MURRAY RD. |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2021-08-31 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2021-08-31 |
Time |
12:42 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2021-08-31 |
Time |
12:42 |
Sent To |
|
|
Notes |
2021-08-31 12:47:07 | PARCEL WILL NEED TO BE READDRESSES, CURRENTLY THERE ARE | | TWO ADDRESSES ON THIS PARCEL 239 MURRAY ST AND 239 ? | | MURRAY ST, WHILE I DO SEE A DEMO PERMIT WAS ISSUED, THE | | HALF ADDRESS VIOLATION WILL REMAIN UNTIL THE FINAL | | INSPECTION IS DONE. IN REGARD TO THE PLANS, THE MAIN | | HOUSE BUILDING AND THE CABANA BUILDING WILL NEED THEIR | | OWN SEPARATE ADDRESS. ALL ACCESSORY | | RESIDENTIAL/COMMERCIAL UNITS AND OR OTHER HABITABLE | | STRUCTURES WILL BE ISSUED A UNIQUE SECONDARY ADDRESS | | NUMBER PER CITY'S ADDRESSING POLICY. PLEASE HAVE OWNER | | CONTACT [email protected] OF CALL 561-805-6659 TO DISCUSS | | ADDRESSING OPTIONS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2022-01-29 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2022-01-29 |
Time |
10:48 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2022-01-29 |
Time |
09:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2022-01-08 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2022-01-08 |
Time |
08:26 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2022-01-08 |
Time |
06:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2021-12-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-12-09 |
Time |
14:54 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-12-09 |
Time |
14:46 |
Sent To |
|
|
Notes |
2021-12-09 14:56:33 | PLAN REVIEW BUILDING | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | PLANS EXAMINER II PX3169/SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | DEVELOPMENT SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | (561) 805-6726 | | [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | 2017 NEC | | | | 2ND REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. | | | | | | 5. PROVIDE AN ENERGY SUBMITTAL. | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | COMPLIANCE BY SECTION 405. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2021-10-25 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-10-25 |
Time |
14:42 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-10-25 |
Time |
07:59 |
Sent To |
|
|
Notes |
2021-10-25 14:43:00 | PLAN REVIEW BUILDING | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | PLANS EXAMINER II PX3169/SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | DEVELOPMENT SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | (561) 805-6726 | | [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | 2017 NEC | | | | 2ND REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. | | | | | | 5. PROVIDE AN ENERGY SUBMITTAL. | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | COMPLIANCE BY SECTION 405. | | | | 6. STATE R-VALUE OF FOIL FACED SEMI-PERMEABLE MASONRY | | WALL INSULATION. SEE PLAN PAGE A4.0. | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-09-20 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-09-20 |
Time |
14:06 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-09-17 |
Time |
16:00 |
Sent To |
|
|
Notes |
2021-09-20 14:58:00 | PLAN REVIEW BUILDING | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | PLANS EXAMINER II PX3169/SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | DEVELOPMENT SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | (561) 805-6726 | | [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | 2017 NEC | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | NOTICE: | | | | A SEPERATE PERMIT IS REQUIRED FOR THE CABANA. | | A SEPERATE PERMIT IS REQUIRED FOR SITE WALLS. | | | | 1. REF. PROJECT DATA ON COVER PAGE FOR THE FOLLOWING | | STATEMENT: | | BUILDING OCCUPANCY IS R3. | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | 2. REF. PROJECT DATA ON COVER PAGE FOR THE FOLLOWING | | STATEMENT: | | INCLUDE SQ/FT UNDER AIR, SQ/FT OF GARAGE AND SQ/FT OF | | COVERED AREAS. | | | | 3. PROVIDE A COPY OF THE BOUNDRY LINE SURVEY. | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | 4. REMANUFACTURED WOOD TRUSSES WILL REQUIRE THE | | APPROVAL OF THE BUILDING OFFICIAL. | | 104.9.1 USED MATERIALS AND EQUIPMENT. THE USE OF USED, | | RECYCLED, OR RECLAIMED MATERIALS WHICH MEET THE | | REQUIREMENTS OF THIS CODE FOR NEW MATERIALS IS | | PERMITTED. USED EQUIPMENT AND DEVICES SHALL NOT BE | | REUSED UNLESS APPROVED BY THE BUILDING OFFICIAL. | | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | 5. PROVIDE AN ENERGY SUBMITTAL. | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | COMPLIANCE BY SECTION 405. | | | | 6. STATE R-VALUE OF CEILING AND WALL INSULATION ON | | PLANS. | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | 7. PROVIDE A WINDOW AND DOOR SCHEDULE. INCLUDE ROUGH | | OPENINGS AND ESIGN PRESSURES OF ALL OPENINGS. | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | 8. PROVIDE THE ICC-ES REPORT FOR THE SPRAY APPLIED | | INSULATION. | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | 9. PROVIDE FASTENER SCHEDULE FOR ENHANCED PRESSURES OF | | ROOF ZONE 3. | | TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING | | SCHEDULE FOR WOOD STRUCTURAL PANELS. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2022-01-29 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2022-01-29 |
Time |
10:48 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2022-01-29 |
Time |
09:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2021-10-22 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-10-22 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-10-22 |
Time |
10:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2021-09-07 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-09-07 |
Time |
12:53 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-08-31 |
Time |
16:33 |
Sent To |
|
|
Notes |
2021-09-07 13:03:45 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | RISER DIAGRAM | | | | ALL PANELS HAVE 400A BUSS? | | | | PANEL LDP3 NEEDS A GROUNDING ELECTRODE SYSTEM | | INSTALLED. 250.32 | | | | MDP SHOWS 2 CAR CHARGERS THAT ARE NOT SHOWN ON PLAN. | | | | LDP4 NOT SHOWN ON PLANS AND DOES NOT HAVE A PANEL | | SCHEDULE | | | | NOT SMOKE ALARMS SHOWN ON PLANS FBC R314,315 | | | | LDP1, LDP2, LDP3, P ALL SHOWN AS TWO POLE 20A BREAKERS. | | 215.5 | | | | CABANA GFCI PROTECTION REQUIRED WITHIN 6' OF THE SINK | | ON FIRST FLOOR. 210.8 | | | | CABANA SMOKE ALARMS NEEDED ON FIRST AND SECOND FLOORS. | | FBC R314 | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2021-09-07 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-09-07 |
Time |
11:45 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-09-07 |
Time |
11:45 |
Sent To |
|
|
Notes |
2021-09-07 11:47:40 | GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN | | THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN | | PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS | | WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE | | RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT | | REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER | | THE WPB AMENDMENTS TO FBC SEC. 107.2.1. | | | | A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR | | FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC | | SEC. 105.1. | | | | NOTE: YOU MAY CHOOSE TO HAVE A GAS REVIEW DONE THIS | | TIME AND ADDRESS THE COMMENTS ABOVE. THIS WILL HAVE THE | | GAS APPROVE FOR A SUB PERMIT, OR IF YOU DECIDED NOT TO | | ADDRESS THE GAS AT THIS TIME, PLEASE PUT A NOTE ON THE | | GAS (A SEPARATE PERMIT BY A LICENSED CONTRACTOR FOR THE | | GAS SYSTEM). AN N WILL BE PUT ON THIS REVIEW, WHICH | | STANDS FOR NOT REQUIRED, BUT A SUB PERMIT WON'T BE | | ISSUED ONCE A REVIEW IS DONE FOR THAT SUB PERMIT, SO | | PLEASE BE ADVISED ON THIS PROCEDURE. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2022-01-30 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-01-30 |
Time |
07:34 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-01-27 |
Time |
16:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2022-01-20 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2022-01-20 |
Time |
11:55 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2022-01-19 |
Time |
12:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2022-01-08 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2022-01-08 |
Time |
09:19 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2021-12-17 |
Time |
11:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2021-12-16 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2021-12-16 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2021-12-01 |
Time |
15:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-11-06 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-11-06 |
Time |
17:37 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-10-07 |
Time |
06:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-09-24 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2021-09-24 |
Time |
15:38 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2021-08-26 |
Time |
10:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
3 |
Status |
P |
Date |
2022-02-02 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-02-02 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-01-31 |
Time |
09:59 |
Sent To |
|
|
Notes |
2022-02-02 16:51:06 | RECEIPT MU-2022-04801 - $6350.41 PAID | 2022-01-31 09:59:50 | 1/31/22 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
F |
Date |
2022-01-30 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-01-30 |
Time |
07:34 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2022-01-08 |
Time |
08:27 |
Sent To |
|
|
Notes |
2022-01-30 07:34:28 | 1/30/22 EMAILED APPLICANT TO HAVE THE NEW CONTRACTOR | | COMPLETE THE IMPACT QUESTIONNAIRE |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2021-09-20 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-09-20 |
Time |
06:40 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-09-20 |
Time |
06:40 |
Sent To |
|
|
Notes |
2021-09-20 06:45:54 | IMPACT FEE QUESTIONNAIRE | | | | PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT | | LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO | | THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF. | | THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ | | B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE | | RECEIPT TO PROJECT DOX OR EMAIL IT TO | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
P |
Date |
2022-01-29 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2022-01-29 |
Time |
10:48 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2022-01-29 |
Time |
10:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
F |
Date |
2022-01-20 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-01-20 |
Time |
06:33 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2022-01-20 |
Time |
06:33 |
Sent To |
|
|
Notes |
2022-01-20 06:34:56 | THE MECHANICAL EQUIPMENT SIZING CALCULATIONS MUST BE | | FOR ALL UNITS BEING INSTALLED FOR THIS PROJECT. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
F |
Date |
2021-12-20 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-12-20 |
Time |
07:04 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-12-20 |
Time |
06:38 |
Sent To |
|
|
Notes |
2021-12-20 07:04:41 | 4TH REVIEW FBC-2020 MECHANICAL | | PERMIT-21081320 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) WHERE ARE THE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS? I ASSUMED THEY WOULD BE INCLUDED IN THE | | CORRECTED ENERGY CALCULATIONS. I DO NOT SEE THEM IN THE | | MAIN HOUSE OR CABANA ENERGY CALCULATIONS. PLEASE | | PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS. | | FBC EC R403.7.1 | | | | 2) PLEASE SEE COMMENT 3 OF PREVIOUS COMMENTS BELOW: | | | | 3) THE CONDENSATE CANNOT TERMINATE IN THE SANITARY | | SYSTEM. PLEASE SHOW THE CONDENSATE TERMINATION LOCATION | | OUTSIDE OF THE STRUCTURE. FBC RES M1411.3 | | | | 3) PLEASE PROVIDE THE CFM?S OF THE KITCHEN HOOD. THE | | HOOD MUST MEET THE MAKE UP AIR OF FBC RES M1503.4 IF | | REQUIRED. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2021-12-02 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-12-02 |
Time |
07:39 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-12-02 |
Time |
07:38 |
Sent To |
|
|
Notes |
2021-12-02 07:41:24 | PLEASE RESPOND TO 2ND CYCLE REVIEW COMMENTS BELOW. | | | | 2ND REVIEW FBC-2020 MECHANICAL | | PERMIT-21081320 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET 2 OF 18 LISTS THE TYPE OF PROJECT AS | | MULTIFAMILY FOR BOTH THE MAIN HOUSE AND THE CABANA. THE | | PERMIT APPLICATION IS FOR A NEW RESIDENTIAL STRUCTURE | | AND A CABANA-ACCESSORY STRUCTURE. | | | | 2) THE 2 RESCHECK REPORTS ARE IDENTICAL AND FOR A | | CONDITIONED FLOOR AREA OF 4850 SQ FT. NEITHER OF THESE | | PROJECT HAVE A FLOOR AREA OF THIS SIZE. PLEASE SUBMIT A | | RESCHECK FOR EACH STRUCTURE SEPARATELY. | | | | 3) THE CONDENSATE CANNOT TERMINATE IN THE SANITARY | | SYSTEM. PLEASE SHOW THE CONDENSATE TERMINATION LOCATION | | OUTSIDE OF THE STRUCTURE. FBC RES M1411.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2021-10-12 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-10-12 |
Time |
07:52 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-10-12 |
Time |
07:51 |
Sent To |
|
|
Notes |
2021-10-12 07:52:14 | 2ND REVIEW FBC-2020 MECHANICAL | | PERMIT-21081320 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET 2 OF 18 LISTS THE TYPE OF PROJECT AS | | MULTIFAMILY FOR BOTH THE MAIN HOUSE AND THE CABANA. THE | | PERMIT APPLICATION IS FOR A NEW RESIDENTIAL STRUCTURE | | AND A CABANA-ACCESSORY STRUCTURE. | | | | 2) THE 2 RESCHECK REPORTS ARE IDENTICAL AND FOR A | | CONDITIONED FLOOR AREA OF 4850 SQ FT. NEITHER OF THESE | | PROJECT HAVE A FLOOR AREA OF THIS SIZE. PLEASE SUBMIT A | | RESCHECK FOR EACH STRUCTURE SEPARATELY. | | | | 3) THE CONDENSATE CANNOT TERMINATE IN THE SANITARY | | SYSTEM. PLEASE SHOW THE CONDENSATE TERMINATION LOCATION | | OUTSIDE OF THE STRUCTURE. FBC RES M1411.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2021-08-28 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-08-28 |
Time |
07:35 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-08-28 |
Time |
07:35 |
Sent To |
|
|
Notes |
2021-08-28 07:35:40 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21081320 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR BOTH THE | | CABANA AND THE MAIN HOUSE. FBC EC 101.5.1.1.2 | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS FOR BOTH THE CABANA AND THE MAIN HOUSE. | | FBC EC R403.7 | | | | 3) THE CABANA WILL REQUIRE A SEPARATE PERMIT. | | | | 4) PLEASE PROVIDE A DETAIL OF THE CONDENSING UNITS TIE | | DOWN. FBC RES M1307.2 | | | | 5) PLEASE SHOW THE CONDENSATION PIPING AND THE | | TERMINATION LOCATION. FBC RES M1411.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2022-01-29 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2022-01-29 |
Time |
10:48 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2022-01-29 |
Time |
09:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2022-01-20 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2022-01-20 |
Time |
07:44 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2022-01-20 |
Time |
07:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2021-10-18 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-10-18 |
Time |
15:32 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-10-18 |
Time |
15:32 |
Sent To |
|
|
Notes |
2021-10-18 15:32:40 | 10/18/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2021-09-07 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-09-07 |
Time |
10:57 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-09-07 |
Time |
09:49 |
Sent To |
|
|
Notes |
2021-09-07 10:57:42 | 09/07/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC RISER | | DIAGRAM FOR WATER AND SANITARY PER THE WPB AMENDMENTS | | TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING. | | | | 2. WOULD YOU PLEASE SHOW A CONTINUOUS LOOP FOR THE | | RECIRCULATING SYSTEM PER THE 2020 FBC SEC. ER 403.5.1.1 | | CIRCULATION SYSTEMS. | | | | 3. ON SHEET P 101 A; | | | | A. IT SHOWS A FLOOR DRAIN IN THE HOUSE AND THE GUEST | | HOUSE. THERE IS NO SOURCE OF WATER SHOWN TO THE TRAP | | PRIMER ON THE WATER DIAGRAM. WOULD YOU PLEASE CORRECT | | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | B. ON THAT SAME PAGE, IT SHOWS A GD-1 IN GRARAGE AND | | P001 FOR THE PLUMBING SCHEDULE. THERE IS NO SUCH NOTE | | FOR IT. IF IT STANDS FOR GRAVITY DRAIN, WOULD YOU | | PLEASE PROVIDE DETAIL OR MANUFACTURES SPECIFICATION AND | | CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 4. THIS IS A MULTI-FAMILY DWELLING, AND WATER USERS | | WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION | | ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW | | ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF | | HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE | | BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER | | THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND | | THEIR CONNECTION CONTROL PROGRAM. A NOTE ON PLANS FOR A | | SEPARATE PERMIT FOR BACKFLOW WILL BE FINE. | | | | 5. A SUB GAS PERMIT IS REQUIRED BY A LICENSED | | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS | | TO THE FBC SEC. 105.1. | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
N |
Date |
2021-09-20 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-09-20 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-09-17 |
Time |
16:00 |
Sent To |
|
|
Notes |
2021-09-20 10:44:57 | PROVISO ON PLAN PAGE A1.3 & A 4.0: A SEPERATE ROOFING | | PERMIT IS REQUIRED. CT |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
9 |
Status |
P |
Date |
2022-01-31 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2022-01-31 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2022-01-31 |
Time |
11:05 |
Sent To |
|
|
Notes |
2022-01-31 11:07:22 | | | REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS AND | | CALCULATIONS APPROVED AND ROUTED TO STORAGE/CLC | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
8 |
Status |
P |
Date |
2022-01-29 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2022-01-29 |
Time |
10:48 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2022-01-28 |
Time |
15:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
7 |
Status |
F |
Date |
2022-01-20 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2022-01-20 |
Time |
15:02 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2022-01-20 |
Time |
15:02 |
Sent To |
|
|
Notes |
2022-01-20 15:09:45 | SINGNATURE REVIEW FAILED | | IT APPEARS SHEET ?PERMIT COVER SHEET? WAS ALTERED AFTER | | DIGITAL SIGNATURE WAS AFFIXED | | IT APPEARS SHEET ?TRIM DETAIL SHEET? IS NOT SIGNED OR | | SEALED | | SHEETS M000, E000 AND P000 APPEAR TO HAVE BEEN ALTERED | | AFTER DIGITAL SIGNATURE WAS AFFIXED. IN ADDITION, | | ANDREW SILVERSTEIN, DETAILED AS THE ENGINEER OF RECORD, | | HAS A DIGITAL SIGNATURE THAT APPEARS TO BE SELF | | CERTIFIED | | SHEETS " M001, M102, , E001, E102, P101A , P101B, | | P102A, P102B, P100" WITH ANDREW SILVERSTEIN, DETAILED | | AS THE ENGINEER OF RECORD, HAS A DIGITAL SIGNATURE THAT | | APPEARS TO BE SELF CERTIFIED | | | | PLEASE, WHEN UPLOADING REPLACEMENT DRAWINGS OR | | DOCUMENTS, USE THE EXACT SAME NAMING CONVENTION. THIS | | WILL ENSURE THERE ARE NO DUPLICATE DRAWINGS OR | | DOCUMENTS IN THE PROJECT DOX FILE, AS THEY WILL BE | | VERSIONED INSTEAD OF DUPLICATED. | | | | 61G15023.004(2) (2) A PROFESSIONAL ENGINEER UTILIZING A | | DIGITAL SIGNATURE TO ELECTRONICALLY SIGN AND SEAL | | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | DOCUMENTS SHALL HAVE THEIR IDENTITY AUTHENTICATED BY A | | CERTIFICATION AUTHORITY AND SHALL ASSURE THAT THE | | DIGITAL SIGNATURE IS: | | (A) UNIQUE TO THE PERSON USING IT; | | (B) CAPABLE OF VERIFICATION; | | (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND, | | (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE | | DIGITAL SIGNATURE AND CORRESPONDINGLY THE DOCUMENT IS | | INVALIDATED IF ANY DATA IN THE DOCUMENT IS CHANGED. | | | | PLEASE FOLLOW THE INSTRUCTIONS BELOW TO CORRECT THIS | | ISSUE. | | | | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND | | SIGNED. | | | | EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF | | APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX, | | OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER | | ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION. | | SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO | | BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED | | DOCUMENTS ARE PREFERRED. | | | | PLEASE EMAIL [email protected] AND CC TO | | [email protected] WITH ANY QUESTIONS | | | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
6 |
Status |
F |
Date |
2022-01-20 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2022-01-20 |
Time |
11:23 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2022-01-20 |
Time |
10:24 |
Sent To |
|
|
Notes |
2022-01-20 11:25:06 | SIGNATURE REVIEW | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | PLANS EXAMINER II PX3169/SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | DEVELOPMENT SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | (561) 805-6726 | | [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | NEC2017 | | | | 2ND REVIEW | | RESULTS: DENIED | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | RE: PLAN PAGES MECH., ELECTRICAL AND PLUMBING | | | | NOTICE: DIGITAL SIGNATURE ON MEP PLANS HAVE EITHER | | INVALID DIGITAL SIGNATURES OR THE DIGITAL SIGNATURE HAS | | BEEN SELF CERTIFIED BY ANDREW SILVERSTEIN, P.E. | | ENGINEERS MAY N OT SELF CERTIFY THEIR DIGITAL | | SIGNATURES PER RULE FS 668.003. | | USE A THIRD PARTY TO CERTIFY DIGITAL SIGNATURE. | | | | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR | | DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL | | SIGNATURE. | | | | 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR | | DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL | | WET SEAL AND SIGNATURE TO: | | | | BUILDING DIVISION, FIRST FLOOR | | CITY OF WEST PALM BEACH | | 401 CLEMATIS ST | | WEST PALM BEACH, FL 33401 | | | | NEW COMMENT: | | APPLICANT SHALL REMOVE DUPLICATE PLANS FROM SUBMITTAL. | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
5 |
Status |
F |
Date |
2022-01-08 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2022-01-08 |
Time |
08:25 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2022-01-08 |
Time |
06:51 |
Sent To |
|
|
Notes |
2022-01-08 08:25:57 | SIGNATURE REVIEW | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | PLANS EXAMINER II PX3169/SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | DEVELOPMENT SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | (561) 805-6726 | | [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | NEC2017 | | | | 5TH REVIEW | | RESULTS: DENIED | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | RE: MECH., ELECTRICAL & PLUMBING PLANS: DIGITAL | | SIGNATURE HAS BEEN SELF CERTIFIED BY EOR, ANDREW | | SILVERSTEIN, P.E. | | FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY | | DIGITAL SIGNATURES AND SEALS PER FS 668.003. | | THE DESIGNER OF THE STRUCTURAL SHEETS CANNOT | | SELF-CERTIFY THEIR DIGITAL SIGNATURE. THE SIGNATURE | | MUST BE THIRD PARTY VERIFIED. | | 61G15-23.004 F.A.C. | | | | | | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR | | DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL | | SIGNATURE. | | | | 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR | | DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL | | WET SEAL AND SIGNATURE TO: | | | | BUILDING DIVISION, FIRST FLOOR | | CITY OF WEST PALM BEACH | | 401 CLEMATIS ST | | WEST PALM BEACH, FL 33401 | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
F |
Date |
2021-12-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-12-09 |
Time |
14:56 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-12-09 |
Time |
14:46 |
Sent To |
|
|
Notes |
2021-12-09 14:57:59 | PENDING RE-SUBMITTAL OF NEW PLANS. CT |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
F |
Date |
2021-11-30 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2021-11-30 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2021-11-30 |
Time |
11:24 |
Sent To |
|
|
Notes |
2021-11-30 11:26:06 | RECEIVED MEP ORIGINAL COPY AND PUT IN SIGNATURE HOLD | | BOX IN SCANNING ROOM. | | NEEDS TO HAVE A MECHANICAL PASS OR ELSE ANY RESUBMITTED | | SHEETS WILL NEED NEW SIGNATURE REVIEW. | | PLUMBING AND ELECTRICAL ARE - OK |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2021-10-25 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-10-25 |
Time |
14:37 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-10-25 |
Time |
07:59 |
Sent To |
|
|
Notes |
2021-10-25 14:41:56 | SIGNATURE REVIEW | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | PLANS EXAMINER II PX3169/SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | DEVELOPMENT SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | (561) 805-6726 | | [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | NEC2017 | | | | 2ND REVIEW | | RESULTS: DENIED | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | RE: PLAN PAGES C-1, C-2, ALL STRUCTURAL PLANS. | | | | NOTICE: DIGITAL SIGNATURE ON STRUCTURAL PLANS HAVE BEEN | | SELF CERTIFIED BY ANDREW SILVERSTEIN, P.E. ENGINEERS | | MAY N OT SELF CERTIFY THEIR DIGITAL SIGNATURES PER RULE | | FS 668.003. | | USE A THIRD PARTY TO CERTIFY DIGITAL SIGNATURE. | | | | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR | | DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL | | SIGNATURE. | | | | 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR | | DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL | | WET SEAL AND SIGNATURE TO: | | | | BUILDING DIVISION, FIRST FLOOR | | CITY OF WEST PALM BEACH | | 401 CLEMATIS ST | | WEST PALM BEACH, FL 33401 | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2021-09-20 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-09-20 |
Time |
13:04 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-09-17 |
Time |
16:00 |
Sent To |
|
|
Notes |
2021-09-20 13:05:39 | SIGNATURE REVIEW | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | PLANS EXAMINER II PX3169/SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | DEVELOPMENT SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | (561) 805-6726 | | [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | NEC2017 | | | | 1ST REVIEW | | RESULTS: DENIED | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR | | DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL | | SIGNATURE. | | | | 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR | | DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL | | WET SEAL AND SIGNATURE TO: | | | | BUILDING DIVISION, FIRST FLOOR | | CITY OF WEST PALM BEACH | | 401 CLEMATIS ST | | WEST PALM BEACH, FL 33401 | | | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2021-12-16 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2021-12-16 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2021-12-16 |
Time |
10:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2021-11-05 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2021-11-05 |
Time |
10:39 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2021-11-05 |
Time |
10:39 |
Sent To |
|
|
Notes |
2021-11-05 10:43:03 | 11/5/21- FAILED. THE TOTAL HEIGHT OF THE STRUCTURE, | | INCLUDING THE CHIMNEY, CAN NOT EXCEED 33 FEET 3 INCHES | | TALL. | | | | ANGELLA VANN, AICP | | 561-822-1441 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2021-09-24 |
|
|
Cont ID |
|
Sent By |
rthermid |
Date |
2021-09-24 |
Time |
14:17 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2021-09-24 |
Time |
14:17 |
Sent To |
|
|
Notes |
2021-09-24 14:21:50 | 9/24/21- FAILED- THE ZONING AND LAND DEVELOMENT | | REGULATIONS REQUIRE THE FOLLOWING FOR SIDE SETBACKS: | | 1.FIVE (5) FOOT MINIMUM; 15 FEET TOTAL. | | SEPERATE PERMITS REQUIRED FOR LANDSCAPING, DRIVEWAY, | | POOL AND ANY WALL OR FENCE | | | | ANGELLA VANN, AICP | | 561-822-1441 | | [email protected] | | |
|
|