Plan Review Details - Permit 21081320
Plan Review Stops For Permit 21081320
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-09-09 Cont ID  
Sent By cpuell Date 2021-09-09 Time 10:58 Rev Time 0.00
Received By cpuell Date 2021-09-09 Time 10:58 Sent To  
Notes
2021-09-09 10:59:58PASSED WITH PROVISO: A SECOND APPLICATION WILL BE
 REQUIRED FOR THE SECOND HABITABLE BUILDING. CUSTOMER
 INFORMED. EAST BUILDING WILL HAVE THE ADDRESS OF 239
 MURRAY RD AND WEST BUILDING WILL HAVE THE ADDRESS OF
 241 MURRAY RD, THIS WILL REPLACE 239 1/2 MURRAY RD.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-08-31 Cont ID  
Sent By cpuell Date 2021-08-31 Time 12:42 Rev Time 0.00
Received By cpuell Date 2021-08-31 Time 12:42 Sent To  
Notes
2021-08-31 12:47:07PARCEL WILL NEED TO BE READDRESSES, CURRENTLY THERE ARE
 TWO ADDRESSES ON THIS PARCEL 239 MURRAY ST AND 239 ?
 MURRAY ST, WHILE I DO SEE A DEMO PERMIT WAS ISSUED, THE
 HALF ADDRESS VIOLATION WILL REMAIN UNTIL THE FINAL
 INSPECTION IS DONE. IN REGARD TO THE PLANS, THE MAIN
 HOUSE BUILDING AND THE CABANA BUILDING WILL NEED THEIR
 OWN SEPARATE ADDRESS. ALL ACCESSORY
 RESIDENTIAL/COMMERCIAL UNITS AND OR OTHER HABITABLE
 STRUCTURES WILL BE ISSUED A UNIQUE SECONDARY ADDRESS
 NUMBER PER CITY'S ADDRESSING POLICY. PLEASE HAVE OWNER
 CONTACT [email protected] OF CALL 561-805-6659 TO DISCUSS
 ADDRESSING OPTIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-01-29 Cont ID  
Sent By cthroop Date 2022-01-29 Time 10:48 Rev Time 0.00
Received By cthroop Date 2022-01-29 Time 09:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-01-08 Cont ID  
Sent By cthroop Date 2022-01-08 Time 08:26 Rev Time 0.00
Received By cthroop Date 2022-01-08 Time 06:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-12-09 Cont ID  
Sent By cthroop Date 2021-12-09 Time 14:54 Rev Time 0.00
Received By cthroop Date 2021-12-09 Time 14:46 Sent To  
Notes
2021-12-09 14:56:33PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED.
  
  
 5. PROVIDE AN ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-10-25 Cont ID  
Sent By cthroop Date 2021-10-25 Time 14:42 Rev Time 0.00
Received By cthroop Date 2021-10-25 Time 07:59 Sent To  
Notes
2021-10-25 14:43:00PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED.
  
  
 5. PROVIDE AN ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 6. STATE R-VALUE OF FOIL FACED SEMI-PERMEABLE MASONRY
 WALL INSULATION. SEE PLAN PAGE A4.0.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-20 Cont ID  
Sent By cthroop Date 2021-09-20 Time 14:06 Rev Time 0.00
Received By cthroop Date 2021-09-17 Time 16:00 Sent To  
Notes
2021-09-20 14:58:00PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE:
  
 A SEPERATE PERMIT IS REQUIRED FOR THE CABANA.
 A SEPERATE PERMIT IS REQUIRED FOR SITE WALLS.
  
 1. REF. PROJECT DATA ON COVER PAGE FOR THE FOLLOWING
 STATEMENT:
 BUILDING OCCUPANCY IS R3.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. REF. PROJECT DATA ON COVER PAGE FOR THE FOLLOWING
 STATEMENT:
 INCLUDE SQ/FT UNDER AIR, SQ/FT OF GARAGE AND SQ/FT OF
 COVERED AREAS.
  
 3. PROVIDE A COPY OF THE BOUNDRY LINE SURVEY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4. REMANUFACTURED WOOD TRUSSES WILL REQUIRE THE
 APPROVAL OF THE BUILDING OFFICIAL.
 104.9.1 USED MATERIALS AND EQUIPMENT. THE USE OF USED,
 RECYCLED, OR RECLAIMED MATERIALS WHICH MEET THE
 REQUIREMENTS OF THIS CODE FOR NEW MATERIALS IS
 PERMITTED. USED EQUIPMENT AND DEVICES SHALL NOT BE
 REUSED UNLESS APPROVED BY THE BUILDING OFFICIAL.
  
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 5. PROVIDE AN ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 6. STATE R-VALUE OF CEILING AND WALL INSULATION ON
 PLANS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 7. PROVIDE A WINDOW AND DOOR SCHEDULE. INCLUDE ROUGH
 OPENINGS AND ESIGN PRESSURES OF ALL OPENINGS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 8. PROVIDE THE ICC-ES REPORT FOR THE SPRAY APPLIED
 INSULATION.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 9. PROVIDE FASTENER SCHEDULE FOR ENHANCED PRESSURES OF
 ROOF ZONE 3.
 TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING
 SCHEDULE FOR WOOD STRUCTURAL PANELS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-01-29 Cont ID  
Sent By cthroop Date 2022-01-29 Time 10:48 Rev Time 0.00
Received By cthroop Date 2022-01-29 Time 09:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-10-22 Cont ID  
Sent By jleahy Date 2021-10-22 Time 10:36 Rev Time 0.00
Received By jleahy Date 2021-10-22 Time 10:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-09-07 Cont ID  
Sent By jleahy Date 2021-09-07 Time 12:53 Rev Time 0.00
Received By jleahy Date 2021-08-31 Time 16:33 Sent To  
Notes
2021-09-07 13:03:45ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER DIAGRAM
  
 ALL PANELS HAVE 400A BUSS?
  
 PANEL LDP3 NEEDS A GROUNDING ELECTRODE SYSTEM
 INSTALLED. 250.32
  
 MDP SHOWS 2 CAR CHARGERS THAT ARE NOT SHOWN ON PLAN.
  
 LDP4 NOT SHOWN ON PLANS AND DOES NOT HAVE A PANEL
 SCHEDULE
  
 NOT SMOKE ALARMS SHOWN ON PLANS FBC R314,315
  
 LDP1, LDP2, LDP3, P ALL SHOWN AS TWO POLE 20A BREAKERS.
 215.5
  
 CABANA GFCI PROTECTION REQUIRED WITHIN 6' OF THE SINK
 ON FIRST FLOOR. 210.8
  
 CABANA SMOKE ALARMS NEEDED ON FIRST AND SECOND FLOORS.
 FBC R314
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-09-07 Cont ID  
Sent By lcrespo Date 2021-09-07 Time 11:45 Rev Time 0.00
Received By lcrespo Date 2021-09-07 Time 11:45 Sent To  
Notes
2021-09-07 11:47:40GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  
 NOTE: YOU MAY CHOOSE TO HAVE A GAS REVIEW DONE THIS
 TIME AND ADDRESS THE COMMENTS ABOVE. THIS WILL HAVE THE
 GAS APPROVE FOR A SUB PERMIT, OR IF YOU DECIDED NOT TO
 ADDRESS THE GAS AT THIS TIME, PLEASE PUT A NOTE ON THE
 GAS (A SEPARATE PERMIT BY A LICENSED CONTRACTOR FOR THE
 GAS SYSTEM). AN N WILL BE PUT ON THIS REVIEW, WHICH
 STANDS FOR NOT REQUIRED, BUT A SUB PERMIT WON'T BE
 ISSUED ONCE A REVIEW IS DONE FOR THAT SUB PERMIT, SO
 PLEASE BE ADVISED ON THIS PROCEDURE.
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2022-01-30 Cont ID  
Sent By lmarchan Date 2022-01-30 Time 07:34 Rev Time 0.00
Received By lmarchan Date 2022-01-27 Time 16:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-01-20 Cont ID  
Sent By cpuell Date 2022-01-20 Time 11:55 Rev Time 0.00
Received By cpuell Date 2022-01-19 Time 12:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-01-08 Cont ID  
Sent By cpuell Date 2022-01-08 Time 09:19 Rev Time 0.00
Received By cpuell Date 2021-12-17 Time 11:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-12-16 Cont ID  
Sent By ajones Date 2021-12-16 Time 10:37 Rev Time 0.00
Received By ajones Date 2021-12-01 Time 15:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-06 Cont ID  
Sent By lmarchan Date 2021-11-06 Time 17:37 Rev Time 0.00
Received By lmarchan Date 2021-10-07 Time 06:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-24 Cont ID  
Sent By shill Date 2021-09-24 Time 15:38 Rev Time 0.00
Received By shill Date 2021-08-26 Time 10:14 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2022-02-02 Cont ID  
Sent By lmarchan Date 2022-02-02 Time 16:51 Rev Time 0.00
Received By lmarchan Date 2022-01-31 Time 09:59 Sent To  
Notes
2022-02-02 16:51:06RECEIPT MU-2022-04801 - $6350.41 PAID
2022-01-31 09:59:501/31/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2022-01-30 Cont ID  
Sent By lmarchan Date 2022-01-30 Time 07:34 Rev Time 0.00
Received By lmarchan Date 2022-01-08 Time 08:27 Sent To  
Notes
2022-01-30 07:34:281/30/22 EMAILED APPLICANT TO HAVE THE NEW CONTRACTOR
 COMPLETE THE IMPACT QUESTIONNAIRE

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-09-20 Cont ID  
Sent By cthroop Date 2021-09-20 Time 06:40 Rev Time 0.00
Received By cthroop Date 2021-09-20 Time 06:40 Sent To  
Notes
2021-09-20 06:45:54IMPACT FEE QUESTIONNAIRE
  
 PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT
 LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO
 THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF.
 THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ
 B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE
 RECEIPT TO PROJECT DOX OR EMAIL IT TO
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2022-01-29 Cont ID  
Sent By cthroop Date 2022-01-29 Time 10:48 Rev Time 0.00
Received By cthroop Date 2022-01-29 Time 10:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2022-01-20 Cont ID  
Sent By medwards Date 2022-01-20 Time 06:33 Rev Time 0.00
Received By medwards Date 2022-01-20 Time 06:33 Sent To  
Notes
2022-01-20 06:34:56THE MECHANICAL EQUIPMENT SIZING CALCULATIONS MUST BE
 FOR ALL UNITS BEING INSTALLED FOR THIS PROJECT.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2021-12-20 Cont ID  
Sent By medwards Date 2021-12-20 Time 07:04 Rev Time 0.00
Received By medwards Date 2021-12-20 Time 06:38 Sent To  
Notes
2021-12-20 07:04:414TH REVIEW FBC-2020 MECHANICAL
 PERMIT-21081320
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) WHERE ARE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS? I ASSUMED THEY WOULD BE INCLUDED IN THE
 CORRECTED ENERGY CALCULATIONS. I DO NOT SEE THEM IN THE
 MAIN HOUSE OR CABANA ENERGY CALCULATIONS. PLEASE
 PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS.
 FBC EC R403.7.1
  
 2) PLEASE SEE COMMENT 3 OF PREVIOUS COMMENTS BELOW:
  
 3) THE CONDENSATE CANNOT TERMINATE IN THE SANITARY
 SYSTEM. PLEASE SHOW THE CONDENSATE TERMINATION LOCATION
 OUTSIDE OF THE STRUCTURE. FBC RES M1411.3
  
 3) PLEASE PROVIDE THE CFM?S OF THE KITCHEN HOOD. THE
 HOOD MUST MEET THE MAKE UP AIR OF FBC RES M1503.4 IF
 REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-12-02 Cont ID  
Sent By medwards Date 2021-12-02 Time 07:39 Rev Time 0.00
Received By medwards Date 2021-12-02 Time 07:38 Sent To  
Notes
2021-12-02 07:41:24PLEASE RESPOND TO 2ND CYCLE REVIEW COMMENTS BELOW.
  
 2ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21081320
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 2 OF 18 LISTS THE TYPE OF PROJECT AS
 MULTIFAMILY FOR BOTH THE MAIN HOUSE AND THE CABANA. THE
 PERMIT APPLICATION IS FOR A NEW RESIDENTIAL STRUCTURE
 AND A CABANA-ACCESSORY STRUCTURE.
  
 2) THE 2 RESCHECK REPORTS ARE IDENTICAL AND FOR A
 CONDITIONED FLOOR AREA OF 4850 SQ FT. NEITHER OF THESE
 PROJECT HAVE A FLOOR AREA OF THIS SIZE. PLEASE SUBMIT A
 RESCHECK FOR EACH STRUCTURE SEPARATELY.
  
 3) THE CONDENSATE CANNOT TERMINATE IN THE SANITARY
 SYSTEM. PLEASE SHOW THE CONDENSATE TERMINATION LOCATION
 OUTSIDE OF THE STRUCTURE. FBC RES M1411.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-10-12 Cont ID  
Sent By medwards Date 2021-10-12 Time 07:52 Rev Time 0.00
Received By medwards Date 2021-10-12 Time 07:51 Sent To  
Notes
2021-10-12 07:52:142ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21081320
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 2 OF 18 LISTS THE TYPE OF PROJECT AS
 MULTIFAMILY FOR BOTH THE MAIN HOUSE AND THE CABANA. THE
 PERMIT APPLICATION IS FOR A NEW RESIDENTIAL STRUCTURE
 AND A CABANA-ACCESSORY STRUCTURE.
  
 2) THE 2 RESCHECK REPORTS ARE IDENTICAL AND FOR A
 CONDITIONED FLOOR AREA OF 4850 SQ FT. NEITHER OF THESE
 PROJECT HAVE A FLOOR AREA OF THIS SIZE. PLEASE SUBMIT A
 RESCHECK FOR EACH STRUCTURE SEPARATELY.
  
 3) THE CONDENSATE CANNOT TERMINATE IN THE SANITARY
 SYSTEM. PLEASE SHOW THE CONDENSATE TERMINATION LOCATION
 OUTSIDE OF THE STRUCTURE. FBC RES M1411.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-28 Cont ID  
Sent By medwards Date 2021-08-28 Time 07:35 Rev Time 0.00
Received By medwards Date 2021-08-28 Time 07:35 Sent To  
Notes
2021-08-28 07:35:401ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21081320
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR BOTH THE
 CABANA AND THE MAIN HOUSE. FBC EC 101.5.1.1.2
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR BOTH THE CABANA AND THE MAIN HOUSE.
 FBC EC R403.7
  
 3) THE CABANA WILL REQUIRE A SEPARATE PERMIT.
  
 4) PLEASE PROVIDE A DETAIL OF THE CONDENSING UNITS TIE
 DOWN. FBC RES M1307.2
  
 5) PLEASE SHOW THE CONDENSATION PIPING AND THE
 TERMINATION LOCATION. FBC RES M1411.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-01-29 Cont ID  
Sent By cthroop Date 2022-01-29 Time 10:48 Rev Time 0.00
Received By cthroop Date 2022-01-29 Time 09:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-01-20 Cont ID  
Sent By lcrespo Date 2022-01-20 Time 07:44 Rev Time 0.00
Received By lcrespo Date 2022-01-20 Time 07:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-10-18 Cont ID  
Sent By lcrespo Date 2021-10-18 Time 15:32 Rev Time 0.00
Received By lcrespo Date 2021-10-18 Time 15:32 Sent To  
Notes
2021-10-18 15:32:4010/18/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-09-07 Cont ID  
Sent By lcrespo Date 2021-09-07 Time 10:57 Rev Time 0.00
Received By lcrespo Date 2021-09-07 Time 09:49 Sent To  
Notes
2021-09-07 10:57:4209/07/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC RISER
 DIAGRAM FOR WATER AND SANITARY PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING.
  
 2. WOULD YOU PLEASE SHOW A CONTINUOUS LOOP FOR THE
 RECIRCULATING SYSTEM PER THE 2020 FBC SEC. ER 403.5.1.1
 CIRCULATION SYSTEMS.
  
 3. ON SHEET P 101 A;
  
 A. IT SHOWS A FLOOR DRAIN IN THE HOUSE AND THE GUEST
 HOUSE. THERE IS NO SOURCE OF WATER SHOWN TO THE TRAP
 PRIMER ON THE WATER DIAGRAM. WOULD YOU PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. ON THAT SAME PAGE, IT SHOWS A GD-1 IN GRARAGE AND
 P001 FOR THE PLUMBING SCHEDULE. THERE IS NO SUCH NOTE
 FOR IT. IF IT STANDS FOR GRAVITY DRAIN, WOULD YOU
 PLEASE PROVIDE DETAIL OR MANUFACTURES SPECIFICATION AND
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. THIS IS A MULTI-FAMILY DWELLING, AND WATER USERS
 WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION
 ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW
 ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF
 HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE
 BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER
 THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND
 THEIR CONNECTION CONTROL PROGRAM. A NOTE ON PLANS FOR A
 SEPARATE PERMIT FOR BACKFLOW WILL BE FINE.
  
 5. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2021-09-20 Cont ID  
Sent By cthroop Date 2021-09-20 Time 10:44 Rev Time 0.00
Received By cthroop Date 2021-09-17 Time 16:00 Sent To  
Notes
2021-09-20 10:44:57PROVISO ON PLAN PAGE A1.3 & A 4.0: A SEPERATE ROOFING
 PERMIT IS REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 9 Status P Date 2022-01-31 Cont ID  
Sent By ccole Date 2022-01-31 Time 11:05 Rev Time 0.00
Received By ccole Date 2022-01-31 Time 11:05 Sent To  
Notes
2022-01-31 11:07:22 
 REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS AND
 CALCULATIONS APPROVED AND ROUTED TO STORAGE/CLC
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 8 Status P Date 2022-01-29 Cont ID  
Sent By cthroop Date 2022-01-29 Time 10:48 Rev Time 0.00
Received By cthroop Date 2022-01-28 Time 15:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status F Date 2022-01-20 Cont ID  
Sent By mpeterso Date 2022-01-20 Time 15:02 Rev Time 0.00
Received By mpeterso Date 2022-01-20 Time 15:02 Sent To  
Notes
2022-01-20 15:09:45SINGNATURE REVIEW FAILED
 IT APPEARS SHEET ?PERMIT COVER SHEET? WAS ALTERED AFTER
 DIGITAL SIGNATURE WAS AFFIXED
 IT APPEARS SHEET ?TRIM DETAIL SHEET? IS NOT SIGNED OR
 SEALED
 SHEETS M000, E000 AND P000 APPEAR TO HAVE BEEN ALTERED
 AFTER DIGITAL SIGNATURE WAS AFFIXED. IN ADDITION,
 ANDREW SILVERSTEIN, DETAILED AS THE ENGINEER OF RECORD,
 HAS A DIGITAL SIGNATURE THAT APPEARS TO BE SELF
 CERTIFIED
 SHEETS " M001, M102, , E001, E102, P101A , P101B,
 P102A, P102B, P100" WITH ANDREW SILVERSTEIN, DETAILED
 AS THE ENGINEER OF RECORD, HAS A DIGITAL SIGNATURE THAT
 APPEARS TO BE SELF CERTIFIED
  
  PLEASE, WHEN UPLOADING REPLACEMENT DRAWINGS OR
 DOCUMENTS, USE THE EXACT SAME NAMING CONVENTION. THIS
 WILL ENSURE THERE ARE NO DUPLICATE DRAWINGS OR
 DOCUMENTS IN THE PROJECT DOX FILE, AS THEY WILL BE
 VERSIONED INSTEAD OF DUPLICATED.
  
 61G15023.004(2) (2) A PROFESSIONAL ENGINEER UTILIZING A
 DIGITAL SIGNATURE TO ELECTRONICALLY SIGN AND SEAL
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS SHALL HAVE THEIR IDENTITY AUTHENTICATED BY A
 CERTIFICATION AUTHORITY AND SHALL ASSURE THAT THE
 DIGITAL SIGNATURE IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND,
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 DIGITAL SIGNATURE AND CORRESPONDINGLY THE DOCUMENT IS
 INVALIDATED IF ANY DATA IN THE DOCUMENT IS CHANGED.
  
 PLEASE FOLLOW THE INSTRUCTIONS BELOW TO CORRECT THIS
 ISSUE.
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION.
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected] WITH ANY QUESTIONS
  
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status F Date 2022-01-20 Cont ID  
Sent By cthroop Date 2022-01-20 Time 11:23 Rev Time 0.00
Received By cthroop Date 2022-01-20 Time 10:24 Sent To  
Notes
2022-01-20 11:25:06SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 2ND REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: PLAN PAGES MECH., ELECTRICAL AND PLUMBING
  
 NOTICE: DIGITAL SIGNATURE ON MEP PLANS HAVE EITHER
 INVALID DIGITAL SIGNATURES OR THE DIGITAL SIGNATURE HAS
 BEEN SELF CERTIFIED BY ANDREW SILVERSTEIN, P.E.
 ENGINEERS MAY N OT SELF CERTIFY THEIR DIGITAL
 SIGNATURES PER RULE FS 668.003.
 USE A THIRD PARTY TO CERTIFY DIGITAL SIGNATURE.
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
 NEW COMMENT:
 APPLICANT SHALL REMOVE DUPLICATE PLANS FROM SUBMITTAL.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2022-01-08 Cont ID  
Sent By cthroop Date 2022-01-08 Time 08:25 Rev Time 0.00
Received By cthroop Date 2022-01-08 Time 06:51 Sent To  
Notes
2022-01-08 08:25:57SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 5TH REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: MECH., ELECTRICAL & PLUMBING PLANS: DIGITAL
 SIGNATURE HAS BEEN SELF CERTIFIED BY EOR, ANDREW
 SILVERSTEIN, P.E.
 FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGNATURES AND SEALS PER FS 668.003.
 THE DESIGNER OF THE STRUCTURAL SHEETS CANNOT
 SELF-CERTIFY THEIR DIGITAL SIGNATURE. THE SIGNATURE
 MUST BE THIRD PARTY VERIFIED.
 61G15-23.004 F.A.C.
  
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-12-09 Cont ID  
Sent By cthroop Date 2021-12-09 Time 14:56 Rev Time 0.00
Received By cthroop Date 2021-12-09 Time 14:46 Sent To  
Notes
2021-12-09 14:57:59PENDING RE-SUBMITTAL OF NEW PLANS. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-11-30 Cont ID  
Sent By dbattles Date 2021-11-30 Time 11:24 Rev Time 0.00
Received By dbattles Date 2021-11-30 Time 11:24 Sent To  
Notes
2021-11-30 11:26:06RECEIVED MEP ORIGINAL COPY AND PUT IN SIGNATURE HOLD
 BOX IN SCANNING ROOM.
 NEEDS TO HAVE A MECHANICAL PASS OR ELSE ANY RESUBMITTED
 SHEETS WILL NEED NEW SIGNATURE REVIEW.
 PLUMBING AND ELECTRICAL ARE - OK

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-10-25 Cont ID  
Sent By cthroop Date 2021-10-25 Time 14:37 Rev Time 0.00
Received By cthroop Date 2021-10-25 Time 07:59 Sent To  
Notes
2021-10-25 14:41:56SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 2ND REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: PLAN PAGES C-1, C-2, ALL STRUCTURAL PLANS.
  
 NOTICE: DIGITAL SIGNATURE ON STRUCTURAL PLANS HAVE BEEN
 SELF CERTIFIED BY ANDREW SILVERSTEIN, P.E. ENGINEERS
 MAY N OT SELF CERTIFY THEIR DIGITAL SIGNATURES PER RULE
 FS 668.003.
 USE A THIRD PARTY TO CERTIFY DIGITAL SIGNATURE.
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-09-20 Cont ID  
Sent By cthroop Date 2021-09-20 Time 13:04 Rev Time 0.00
Received By cthroop Date 2021-09-17 Time 16:00 Sent To  
Notes
2021-09-20 13:05:39SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 1ST REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2021-12-16 Cont ID  
Sent By ajones Date 2021-12-16 Time 10:37 Rev Time 0.00
Received By ajones Date 2021-12-16 Time 10:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2021-11-05 Cont ID  
Sent By ajones Date 2021-11-05 Time 10:39 Rev Time 0.00
Received By ajones Date 2021-11-05 Time 10:39 Sent To  
Notes
2021-11-05 10:43:0311/5/21- FAILED. THE TOTAL HEIGHT OF THE STRUCTURE,
 INCLUDING THE CHIMNEY, CAN NOT EXCEED 33 FEET 3 INCHES
 TALL.
  
 ANGELLA VANN, AICP
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2021-09-24 Cont ID  
Sent By rthermid Date 2021-09-24 Time 14:17 Rev Time 0.00
Received By ajones Date 2021-09-24 Time 14:17 Sent To  
Notes
2021-09-24 14:21:509/24/21- FAILED- THE ZONING AND LAND DEVELOMENT
 REGULATIONS REQUIRE THE FOLLOWING FOR SIDE SETBACKS:
 1.FIVE (5) FOOT MINIMUM; 15 FEET TOTAL.
 SEPERATE PERMITS REQUIRED FOR LANDSCAPING, DRIVEWAY,
 POOL AND ANY WALL OR FENCE
  
 ANGELLA VANN, AICP
 561-822-1441
 [email protected]
  