Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-04-26 Cont ID  
Sent By rmcphers Date 2022-04-26 Time 08:50 Rev Time 0.00
Received By rmcphers Date 2022-04-26 Time 08:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-03-15 Cont ID  
Sent By rmcphers Date 2022-03-15 Time 13:51 Rev Time 0.00
Received By rmcphers Date 2022-03-15 Time 13:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-07-01 Cont ID  
Sent By mpeterso Date 2022-06-30 Time 11:26 Rev Time 0.00
Received By mpeterso Date 2022-06-30 Time 11:26 Sent To  
Notes
2022-06-30 11:28:26PASSED ELECTRIC REVIEW WITH THE PROVISO TO ENSURE
 COMPLIANCE WITH THE BELOW COMMENTS.MP
  
 ELECTRICAL REVIEW FAILED
  
 1) PLEASE PROVIDE LOAD CALCULATIONS FOR DOCK PANEL THAT
 CORRECTLY STATE THE LOADS BEING SERVED. I.E. SHORE
 POWER IS LISTED AS 30 AMP, DRAWING DETAILS 50-AMP. NO
 BOAT LIFTS ARE DETAILED. NEC 215.5 PANEL SCHEDULE HAS
 BEEN REVISED TO SHOW A 50-AMP SHORE POWER PEDESTAL,
 HOWEVER BOATLIFT CIRCUITS ARE STILL NOT LISTED IN THE
 SCHEDULE AND LOAD CALCULATIONS UPDATED.
 NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE
 AUTHORITY HAVING
 JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS SHALL BE
 PROVIDED
 PRIOR TO THE INSTALLATION OF THE FEEDERS. SUCH A
 DIAGRAM SHALL
 SHOW THE AREA IN SQUARE FEET OF THE BUILDING OR OTHER
 STRUCTURE
 SUPPLIED BY EACH FEEDER, THE TOTAL CALCULATED LOAD
 BEFORE APPLYING
 DEMAND FACTORS, THE DEMAND FACTORS USED, THE CALCULATED
 -------------------------------------------------------
 -------------------------------------------------
 2) PLEASE DETAIL GROUND FAULT PROTECTION AS REQUIRED BY
 NEC 555.3 AND 210.8(C) THERE IS STILL NO INDICATION ON
 ANY PLANS OR SCHEDULES DETAILING THE REQUIRED GFP AS
 REQUIRED
 NEC 210.8(C) BOAT HOISTS. GFCI PROTECTION SHALL BE
 PROVIDED FOR OUTLETS
 NOT EXCEEDING 240 VOLTS THAT SUPPLY BOAT HOISTS
 INSTALLED IN DWELLING
 UNIT LOCATIONS.
 NEC 555.3 GROUND-FAULT PROTECTION. THE OVERCURRENT
 PROTECTIVE
 DEVICES THAT SUPPLY THE MARINA, BOATYARDS, AND
 COMMERCIAL AND
 NONCOMMERCIAL DOCKING FACILITIES SHALL HAVE
 GROUND-FAULT PROTECTION
 NOT EXCEEDING 30 MA.
 -------------------------------------------------------
 --------------------------------------------------
 3) PLEASE DETAIL ELECTRIC CONNECTIONS ARE 12? ABOVE
 ELECTRICAL DATUM PLANE AS DETAILED BY NEC 555.2 AND
 555.9. ALTHOUGH PLAN LABELED BOAT LIFT SECTION DOES NOT
 DETAIL THESE MEASUREMENTS, ONE MIGHT ASSUME THE
 ELECTRICAL CONNECTIONS SHOULD BE IN COMPLIANCE
 555.2 DEFINITIONS.
 ELECTRICAL DATUM PLANE. THE ELECTRICAL DATUM PLANE IS
 DEFINED
 AS FOLLOWS:
 (1) IN LAND AREAS SUBJECT TO TIDAL FLUCTUATION, THE
 ELECTRICAL
 DATUM PLANE IS A HORIZONTAL PLANE 606 MM (2 FT) ABOVE
 THE HIGHEST TIDE LEVEL FOR THE AREA OCCURRING UNDER
 NORMAL
 CIRCUMSTANCES, THAT IS, HIGHEST HIGH TIDE.
 555.9 ELECTRICAL CONNECTIONS. ELECTRICAL CONNECTIONS
 SHALL BE
 LOCATED AT LEAST 305 MM (12 IN.) ABOVE THE DECK OF A
 FLOATING PIER.
 CONDUCTOR SPLICES, WITHIN APPROVED JUNCTION BOXES,
 UTILIZING
 SEALED WIRE CONNECTOR SYSTEMS LISTED AND IDENTIFIED FOR
 SUBMERSION
 SHALL BE PERMITTED WHERE LOCATED ABOVE THE WATERLINE
 BUT
 BELOW THE ELECTRICAL DATUM PLANE FOR FLOATING PIERS.
 ALL ELECTRICAL CONNECTIONS SHALL BE LOCATED AT LEAST
 305 MM
 (12 IN.) ABOVE THE DECK OF A FIXED PIER BUT NOT BELOW
 THE ELECTRICAL
 DATUM PLANE.
 -------------------------------------------------------
 -----------------------------------------------
 4) PLEASE DETAIL SHOCK HAZARD SIGNAGE AS REQUIRED BY
 NEC 555.24. SHOCK HAZARD SIGN HAS BEEN PROVIDED IN THE
 SUPPORTING DOCS FOLDER
 -------------------------------------------------------
 -------------------------------------------------------
 -----------------------
 5) PLEASE PROVIDE CONDUCTOR SIZES AND OVERCURRENT
 PROTECTION INSTALLED TO DOCK EQUIPMENT TO DETAIL
 COMPLIANCE WITH NEC 210.19(1) AND NEC 240.4. NO
 CONDUCTOR SIZES OR OVERCURRENT PROTECTION IS SHOWN ON
 ANY PLAN OR SCHEDULE FOR BOAT LIFTS
 210.19 CONDUCTORS ? MINIMUM AMPACITY AND SIZE.
 (A) BRANCH CIRCUITS NOT MORE THAN 600 VOLTS.
 (1) GENERAL. BRANCH-CIRCUIT CONDUCTORS SHALL HAVE AN
 AMPACITY
 NOT LESS THAN THE MAXIMUM LOAD TO BE SERVED. CONDUCTORS
 SHALL BE
 SIZED TO CARRY NOT LESS THAN THE LARGER OF
 210.19(A)(1)(A) OR (B).
 -------------------------------------------------------
 ---------------------------------------------------
 6) PLEASE DETAIL CONDUCTORS/FEEDERS ARE SIZED FOR
 MAXIMUM VOLTAGE DROP AS REQUIRED PER 2020 FBC ENERGY
 CONSERVATION C405.5.3. NO SUPPORTING DOCUMENTATION HAS
 BEEN PROVIDED TO SHOW COMPLIANCE
 C405.5 ELECTRICAL POWER (MANDATORY).
 C405.5.3 VOLTAGE DROP. THE CONDUCTORS FOR FEEDERS AND
 BRANCH CIRCUITS COMBINED SHALL BE SIZED FOR A MAXIMUM
 OF
 5 PERCENT VOLTAGE DROP TOTAL.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-04-20 Cont ID  
Sent By mpeterso Date 2022-04-20 Time 10:56 Rev Time 0.00
Received By mpeterso Date 2022-04-20 Time 10:56 Sent To  
Notes
2022-04-20 10:57:58ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE LOAD CALCULATIONS FOR DOCK PANEL THAT
 CORRECTLY STATE THE LOADS BEING SERVED. I.E. SHORE
 POWER IS LISTED AS 30 AMP, DRAWING DETAILS 50-AMP. NO
 BOAT LIFTS ARE DETAILED. NEC 215.5
 2) PLEASE DETAIL GROUND FAULT PROTECTION AS REQUIRED BY
 NEC 555.3 AND 210.8(C)
 3) PLEASE DETAIL ELECTRIC CONNECTIONS ARE 12? ABOVE
 ELECTRICAL DATUM PLANE AS DETAILED BY NEC 555.2 AND
 555.9
 4) PLEASE DETAIL SHOCK HAZARD SIGNAGE AS REQUIRED BY
 NEC 555.24
 5) PLEASE PROVIDE CONDUCTOR SIZES AND OVERCURRENT
 PROTECTION INSTALLED TO DOCK EQUIPMENT TO DETAIL
 COMPLIANCE WITH NEC 210.19(1) AND NEC 240.4
 6) PLEASE DETAIL CONDUCTORS/FEEDERS ARE SIZED FOR
 MAXIMUM VOLTAGE DROP AS REQUIRED PER 2020 FBC ENERGY
 CONSERVATION C405.5.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-03-14 Cont ID  
Sent By mpeterso Date 2022-03-14 Time 15:14 Rev Time 0.00
Received By mpeterso Date 2022-03-14 Time 15:14 Sent To  
Notes
2022-03-14 15:18:53ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE ELECTRIC DRAWINGS FOR ALL DOCK
 ELECTRIC INCLUDING BOAT LIFTS, COMPLETE RISER DIGRAM
 INCLUDE UPSTREAM PANEL AND LOAD CALCULATIONS,FBC 107.2
 NEC 215.5
 2) LOCATE ALL ELECTRIC EQUIPMENT ON SITE PLAN INCLUDING
 UPSTREAM PANEL. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2022-03-15 Cont ID  
Sent By fmittner Date 2022-03-15 Time 08:08 Rev Time 0.00
Received By fmittner Date 2022-03-15 Time 08:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-30 Cont ID  
Sent By mpeterso Date 2022-06-30 Time 11:28 Rev Time 0.00
Received By mpeterso Date 2022-06-27 Time 13:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-26 Cont ID  
Sent By shill Date 2022-04-26 Time 14:37 Rev Time 0.00
Received By shill Date 2022-04-12 Time 15:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-22 Cont ID  
Sent By vbroglia Date 2022-03-17 Time 16:00 Rev Time 0.00
Received By shill Date 2022-03-09 Time 09:37 Sent To  
Notes
2022-03-29 16:31:34CHANGED STATUS TO "N", CHANGED THIS SUBMITTAL TO A
 PERMIT, APPLICATION ALREADY SUBMITTED
  
2022-03-22 08:43:18THIS WAS SUBMITTED AS A REVISION. YOU CANNOT REVISE A
 DEMO/SITE WALL PERMIT WITH A REVISION. ALL NEW
 CONSTRUCTION REQUIRES A PERMIT.
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status P Date 2022-04-26 Cont ID  
Sent By shill Date 2022-04-26 Time 14:36 Rev Time 0.00
Received By shill Date 2022-04-26 Time 14:36 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2022-04-15 Cont ID  
Sent By aoliver Date 2022-04-15 Time 05:32 Rev Time 0.00
Received By shill Date 2022-04-15 Time 05:32 Sent To  
Notes
2022-04-15 05:35:56A NOTICE TO BUILDING OFFICIAL OF USE OF PRIVATE
 PROVIDER FOR PLAN REVIEW AND INSPECTIONS WAS SUBMITTED
 FOR THE SFD AND ASSOCIATED IMPROVEMENTS. A SEPARATE
 NOTICE TO BUILDING OFFICIAL WAS SUBMITTED FOR
 INSPECTIONS ONLY FOR THE SEAWALL. PER EMAIL FROM THE
 PROPERTY OWNER, HILARY MUSSER, DATED 4/15/22, THE
 INTENT IS THAT THIS DOCK PERMIT BE PRIVATE PROVIDER
 INSPECTIONS ONLY. PROVIDE A NEW NOTICE TO BUILDING
 OFFICIAL FOR THE DOCK, INSPECTIONS ONLY, WITH OTHER
 REQUIRED DOCUMENTATION.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-04-26 Cont ID  
Sent By rmcphers Date 2022-04-26 Time 08:53 Rev Time 0.00
Received By rmcphers Date 2022-04-26 Time 08:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-03-15 Cont ID  
Sent By rmcphers Date 2022-03-15 Time 13:51 Rev Time 0.00
Received By rmcphers Date 2022-03-15 Time 13:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-04-15 Cont ID  
Sent By vbroglia Date 2022-04-15 Time 09:20 Rev Time 0.00
Received By vbroglia Date 2022-04-15 Time 09:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-03-17 Cont ID  
Sent By fmittner Date 2022-03-17 Time 15:49 Rev Time 0.00
Received By vbroglia Date 2022-03-17 Time 15:49 Sent To  
Notes
2022-03-17 16:00:483/17/2022 FAILED
  
 PLEASE SHOW WHERE THE MIDDLE 1/3 OF THE PROPERTY IS
 LOCTED AND THAT THE DOCK IS PLACED WITHIN THE MIDDLE
 1/3 OF THE LOT
  
 PER SECTION 94-313 THE MAXIMUM WIDTH OF A DOCK SHALL
 NOT EXCEED TEN FEET. FINGER PIERS AND TERMINAL
 PLATFORMS WHICH ARE GENERALLY PERPENDICULAR TO THE DOCK
 AND PARALLEL TO THE SEAWALL, BULKHEAD, OR RIPARIAN
 PROPERTY LINE MAY NOT BE GREATER THAN 10 FEET
  
 IF YOU WOULD LIKE A DIAGRAM PLEASE EMAIL ME AND I WILL
 PROVIDE ONE FOR YOU
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  