Plan Review Details - Permit 21081141
Plan Review Stops For Permit 21081141
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-02-01 Cont ID  
Sent By rmcdouga Date 2022-02-01 Time 08:14 Rev Time 0.00
Received By rmcdouga Date 2022-02-01 Time 08:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-01-19 Cont ID  
Sent By rmcdouga Date 2022-01-19 Time 07:34 Rev Time 0.00
Received By rmcdouga Date 2022-01-19 Time 07:34 Sent To  
Notes
2022-01-18 17:34:12PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 NEW COMMENTS:
  
 1) THE MEAN ROOF HEIGHT OF THE BUILDING IS USED TO
 DETERMINE THE COMPONENT AND CLADDING PRESSURES. THIS IS
 A TEN STORY BUILDING (APPROXIMATELY 120' IN HEIGHT) THE
 MRH WILL BE GREATER THAN 60 FEET. THE WIND LOAD
 ENGINEERING IS FOR BUILDINGS WITH MEAN ROOF HEIGHTS OF
 60 FEET OR LESS. PLEASE CORRECT. FBC 1609
  
 2) THE EXPOSURE CATEGORY FOR THIS BUILDING IS EXPOSURE
 D. THE SIGNED AND SEALED DRAWING FROM TOMAS PONCE PE
 HAS THE WINDLOAD CRITERIA FOR EXPOSURE C AND IS FOR
 MEAN ROOF HEIGHTS OF 60' OR LESS. PLEASE CORRECT THE
 DATUM. FBC 1609.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-20 Cont ID  
Sent By rmcdouga Date 2021-09-20 Time 14:24 Rev Time 0.00
Received By rmcdouga Date 2021-09-20 Time 10:52 Sent To  
Notes
2021-09-20 14:23:56PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE AN ELEVATION VIEW OF THE WINDOWS. SHOW THE
 CONFIGURATION AND DIMENSIONS OF THE WINDOWS AND THE
 LOCATIONS AND SPANS OF THE MULLIONS. FBC 107.2.1
  
 2) ON PRODUCT APPROVAL FL15816.14 THE DESIGN PRESSURE
 OF +/- 50 PSF IS CIRCLED. THE WINDLOAD SHEET HAS THE DP
 AS 65 FOR THIS FL#. PLEASE CLARIFY. FBC 107.2.1
  
 3) THE PRODUCT HAS TO MEET BOTH THE POSITIVE AND
 NEGATIVE DESIGN PRESSURES. PLEASE SPECIFY BOTH OF THE
 PRESSURES YOUR WIND LOAD SHEET FOR THIS PROJECT. FBC
 107.2.1

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-01 Cont ID  
Sent By rmcdouga Date 2022-02-01 Time 08:14 Rev Time 0.00
Received By rmcdouga Date 2022-01-26 Time 10:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-19 Cont ID  
Sent By rmcdouga Date 2022-01-19 Time 07:35 Rev Time 0.00
Received By rmcdouga Date 2021-12-23 Time 08:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-20 Cont ID  
Sent By rmcdouga Date 2021-09-20 Time 14:24 Rev Time 0.00
Received By rmcdouga Date 2021-08-23 Time 13:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-02-01 Cont ID  
Sent By rmcdouga Date 2022-02-01 Time 08:14 Rev Time 0.00
Received By rmcdouga Date 2022-02-01 Time 08:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-01-19 Cont ID  
Sent By rmcdouga Date 2022-01-19 Time 07:34 Rev Time 0.00
Received By rmcdouga Date 2022-01-19 Time 07:34 Sent To  
Notes
2022-01-19 07:35:52THE ENGINEER'S SIGNATURE WILL NEED TO BE REVIEWED WHEN
 THE CORRECTED DOCUMENTS ARE SUBMITTED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-09-20 Cont ID  
Sent By rmcdouga Date 2021-09-20 Time 10:39 Rev Time 0.00
Received By rmcdouga Date 2021-09-20 Time 10:39 Sent To  
Notes
2021-09-20 10:51:34ENGINEERING IS REQUIRED TO HAVE THE ENGINEER'S DIGITAL
 SIGNATURE IF SUBMITTED ELECTRONICALLY. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 487 & 61G1 OR FS 471 & 61G15