Plan Review Details - Permit 21080473
Plan Review Stops For Permit 21080473
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-08-12 Cont ID  
Sent By cpuell Date 2021-08-12 Time 14:59 Rev Time 0.00
Received By cpuell Date 2021-08-12 Time 14:59 Sent To  
Notes
2021-08-12 15:00:35SPOKE WITH OWNER, REAR HALF ADDRESS WILL BE READDRESSED
 AS 323 MALVERNE RD.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-08-11 Cont ID  
Sent By cpuell Date 2021-08-11 Time 10:34 Rev Time 0.00
Received By cpuell Date 2021-08-11 Time 10:34 Sent To  
Notes
2021-08-11 10:35:26PER PERMIT DESCRIPTION WORK BEING DONE ON THE FRONT
 BUILDING WITH AN ADDRESS OF 321 MALVERNE RD, HOWEVER
 THE REAR BUILDING WITH AN ADDRESS OF 321 MALVERNE RD #
 1/2 WILL STILL NEED TO BE READDRESSED, PLEASE HAVE THE
 OWNER CONTACT [email protected] OR CALL 561-805-6659 TO
 READDRESS THE HALF ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-08-23 Cont ID  
Sent By shill Date 2021-08-23 Time 15:50 Rev Time 0.00
Received By shill Date 2021-08-23 Time 15:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-11 Cont ID  
Sent By jbrooks Date 2021-08-11 Time 10:06 Rev Time 0.00
Received By jbrooks Date 2021-08-11 Time 07:40 Sent To  
Notes
2021-08-11 10:06:26JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1 REVISE SUBMITTED ENGINEERING
 CALCULATIONS TO CORRECT PROJECT NAME, REFERENCE NOA
 USED TO INCLUDE NOA NUMBER, ROOFING SYSTEM USED WITH
 PAGE NUMBER AND MAXIMUM DESIGN PRESSURE.
 2. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED ROOF UNDERLAYMENT TO
 BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-23 Cont ID  
Sent By shill Date 2021-08-23 Time 15:50 Rev Time 0.00
Received By shill Date 2021-08-20 Time 08:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-11 Cont ID  
Sent By cpuell Date 2021-08-11 Time 10:35 Rev Time 0.00
Received By cpuell Date 2021-08-11 Time 05:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-20 Cont ID  
Sent By jleahy Date 2021-08-20 Time 10:59 Rev Time 0.00
Received By jleahy Date 2021-08-20 Time 10:59 Sent To  
Notes
2021-08-20 10:59:32SIGNED SUBMITTAL SENT TO STORAGE JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-12 Cont ID  
Sent By lcrespo Date 2021-08-12 Time 13:28 Rev Time 0.00
Received By lcrespo Date 2021-08-12 Time 13:28 Sent To  
Notes
***NONE***