Plan Review Details - Permit 21080195
Plan Review Stops For Permit 21080195
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-08-10 Cont ID  
Sent By cpuell Date 2021-08-10 Time 13:52 Rev Time 0.00
Received By cpuell Date 2021-08-10 Time 13:52 Sent To  
Notes
2021-08-10 13:53:198TH FLOOR SUITE ON THE 8TH FLOOR PARKING GARAGE, GIVEN
 ADDRESS OF 360 S ROSEMARY AVE # 800

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-11-19 Cont ID  
Sent By lmarchan Date 2021-11-19 Time 11:58 Rev Time 0.00
Received By lmarchan Date 2021-11-19 Time 11:58 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-11-01 Cont ID  
Sent By rmcphers Date 2021-11-01 Time 11:37 Rev Time 0.00
Received By rmcphers Date 2021-11-01 Time 11:37 Sent To  
Notes
2021-11-01 11:37:17PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-09-22 Cont ID  
Sent By rmcphers Date 2021-09-22 Time 12:41 Rev Time 0.00
Received By rmcphers Date 2021-09-22 Time 12:41 Sent To  
Notes
2021-09-22 12:42:12PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-11-01 Cont ID  
Sent By rmcphers Date 2021-11-01 Time 11:35 Rev Time 0.00
Received By rmcphers Date 2021-11-01 Time 11:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-22 Cont ID  
Sent By rmcphers Date 2021-09-22 Time 13:28 Rev Time 0.00
Received By rmcphers Date 2021-09-22 Time 10:17 Sent To  
Notes
2021-09-22 13:12:468TH FLOOR ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW ALL FIRE RATED DOORS TO BE SELF CLOSING
 AND SELF LATCHING FBC 716.5.9
 2) DRAWING A4.00 SHOWS A NEW 3' OPENING TO THE STAIRS -
 DRAWING S-1.00 A SHOWS A NEW 6' OPENING - PLEASE
 CLARIFY - OPENINGS SHOULD MATCH.
 3) DRAWING S-1.00A SHOWS A CUT SECTION REFERRING TO
 DRAWING S5.15 - DRAWING S5.15 WAS NOT ADDED TO
 PROJECTDOX.
 4) PLEASE SHOW THE GLAZED DOORS IN THE 1 HOUR FIRE
 BARRIER TO COMPLY WITH REQUIREMENTS - FIRE RATED
 GLAZING, SELF CLOSING, SELF LATCHING ETC PER FBC 716
 5) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS - ALL
 PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE DESIGNER OF RECORD FBC WPB 107
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-09-22 Cont ID  
Sent By jleahy Date 2021-09-22 Time 11:25 Rev Time 0.00
Received By jleahy Date 2021-09-22 Time 11:25 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-12-13 Cont ID  
Sent By jleahy Date 2021-12-13 Time 11:54 Rev Time 0.00
Received By jleahy Date 2021-12-13 Time 11:54 Sent To  
Notes
2021-12-13 11:55:20AC CONTROL WIRING JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-10-22 Cont ID  
Sent By pleduc Date 2021-10-22 Time   Rev Time 0.00
Received By pleduc Date 2021-10-22 Time 15:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-09-21 Cont ID  
Sent By pleduc Date 2021-09-21 Time   Rev Time 0.00
Received By pleduc Date 2021-09-21 Time 09:05 Sent To  
Notes
2021-09-21 15:49:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF A PROPOSED WATER CURTAIN
 AT A GLASS WALL & DOOR.
  
 THIS PROPOSED INSTALLATION A MISAPPLICATION FO THE CODE
 AND IS NOT AAPPROVED.
  
 THERE IS ALSO A GLASS DOOR PROPOSED. THIS GLASS DOOR
 MUST BE ADDRESSED SEPARATELY.
  
  
 PER NFPA 13
  
 8.15.26* SPRINKLER-PROTECTED GLAZING.
 WHERE SPRINKLERS ARE USED IN COMBINATION WITH GLAZING
 AS AN ALTERNATIVE TO A REQUIRED FIRERATED
 WALL OR WINDOW ASSEMBLY, THE SPRINKLER-PROTECTED
 ASSEMBLY SHALL COMPLY WITH THE
 FOLLOWING:
 (1) SPRINKLERS SHALL BE LISTED AS SPECIFIC APPLICATION
 WINDOW SPRINKLERS UNLESS THE STANDARD
 SPRAY SPRINKLERS ARE SPECIFICALLY PERMITTED BY THE
 BUILDING CODE.
 (2) SPRINKLERS SHALL BE SUPPLIED BY A WET-PIPE SYSTEM.
 (3) GLAZING SHALL BE HEAT-STRENGTHENED, TEMPERED, OR
 GLASS CERAMIC AND SHALL BE FIXED.
 (4) WHERE THE ASSEMBLY IS REQUIRED TO BE PROTECTED FROM
 BOTH SIDES, SPRINKLERS SHALL BE
 INSTALLED ON BOTH SIDES OF THE GLAZING.
 (5) THE USE OF SPRINKLER-PROTECTED GLAZING SHALL BE
 LIMITED TO NON-LOAD-BEARING WALLS.
 (6) THE GLAZED ASSEMBLY SHALL NOT HAVE ANY HORIZONTAL
 MEMBERS THAT WOULD INTERFERE WITH UNIFORM
 DISTRIBUTION OF WATER OVER THE SURFACE OF THE GLAZING,
 AND THERE SHALL BE NO OBSTRUCTIONS
 BETWEEN SPRINKLERS AND GLAZING THAT WOULD OBSTRUCT
 WATER DISTRIBUTION.
 (7) THE WATER SUPPLY DURATION FOR THE DESIGN AREA THAT
 INCLUDES THE WINDOW SPRINKLERS SHALL
 NOT BE LESS THAN THE REQUIRED RATING OF THE ASSEMBLY
  
 ADDITIONALLY, THIS PROPOSED GLASS WALL IS A 2HR
 FIREWALL, NOT A FIRE BARRIER. THIS ALTERNATIVE
 PROTECTION IS NOT ALLOWED ON FIREWALLS.
  
 THE FRAME OF THE PROPOSED GLASS WALL MUST ALSO BE
 RATED.
  
 ADDITIONAL INFO:
  
 WHEN IT COMES TO THE GLASS ASSEMBLIES, THERE ARE SIX
 ITEMS THAT MUST BE CONSIDERED. A DESIGN MUST TAKE NOTE
 OF GLASS SIZE, GLAZING TYPE, GLAZING FRAMES, HORIZONTAL
 MULLIONS, AND OPENINGS AND PENETRATIONS.
  
 1. THE SIZE OF THE GLASS IS BASED ON FIRE TESTING AND
 SPRINKLER LIMITATIONS. THE GLASS HEIGHT CANNOT EXCEED
 13 FT, AND THERE IS NO LIMITATION TO THE LENGTH OF THE
 WINDOW AS THE WINDOW SPRINKLER SPACING CAN MEET THE
 INSTALLATION REQUIREMENTS OF THE MANUFACTURER?S
 LISTING.
 2. WINDOWS INTENDED TO BE PROTECTED BY SPRINKLERS MUST
 BE VERTICAL. SLOPED AND CURVED GLASS CANNOT BE
 PROTECTED BY WINDOW SPRINKLERS.
 3. WHEN WINDOW SPRINKLERS ARE UTILIZED IN FIRE
 SEPARATIONS, THE GLASS
 MUST BE 1/4-IN. THICK AND HEAT STRENGTHENED OR
 TEMPERED.
 4. WINDOW FRAMES SHALL BE LISTED WITH THE SAME
 FIRE-RESISTANCE RATING AS THE GLASS; THIS IS OFTEN AN
 OVERLOOKED ITEM.
 5. WHEN DEALING WITH WINDOW SPRINKLERS, HORIZONTAL
 MULLIONS ARE IN ESSENCE AN OBSTRUCTION TO THE
 SPRINKLER?S SPRAY PATTERN AND PREVENT THE ABILITY FOR
 THE WATER TO RUN DOWN THE GLASS FACE. THE INTENT OF A
 WINDOW SPRINKLER IS TO COMPLETELY COAT THE GLASS WITH A
 WATER SPRAY IN ORDER TO KEEP THE GLASS FROM FAILING DUE
 TO HOT SPOTS. (SEE FIGURE 1.)
 6. WINDOW SPRINKLERS ARE ALSO ONLY INTENDED TO PROTECT
 FIXED GLASS. OPERABLE WINDOWS CAN NOT BE PROTECTED.
 DOORS IN THESE FIRE PARTITIONS MUST BE TREATED
 SEPARATELY.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-11-19 Cont ID  
Sent By lmarchan Date 2021-11-19 Time 11:59 Rev Time 0.00
Received By lmarchan Date 2021-11-09 Time 07:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-03 Cont ID  
Sent By lmarchan Date 2021-11-03 Time 09:33 Rev Time 0.00
Received By lmarchan Date 2021-10-21 Time 12:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-01 Cont ID  
Sent By lcrespo Date 2021-10-01 Time 10:45 Rev Time 0.00
Received By lcrespo Date 2021-09-20 Time 16:32 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2021-10-06 Cont ID  
Sent By rmcphers Date 2021-09-22 Time 12:42 Rev Time 0.00
Received By lmarchan Date 2021-09-22 Time 12:42 Sent To  
Notes
2021-10-06 10:53:18RECEIPT MU-2021-046543 - $53448.84 PAID
2021-09-22 12:43:20PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
2021-09-22 10:52:189/22/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-11-12 Cont ID  
Sent By medwards Date 2021-11-12 Time 11:01 Rev Time 0.00
Received By medwards Date 2021-11-12 Time 11:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-10-25 Cont ID  
Sent By medwards Date 2021-10-25 Time 13:51 Rev Time 0.00
Received By medwards Date 2021-10-25 Time 13:51 Sent To  
Notes
2021-10-25 15:36:281) PLEASE PROVIDE THE LOCATION WHERE THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS ARE IN THIS SUBMITTAL AS
 I DID NOT FIND THEM. FBC 107.2.1
  
 2) THE 28 INCH X 18 INCH DUCT LABELED EA FROM THE
 GARAGE INTO THE RETURN OF THE MECHANICAL SYSTEM WILL
 NEED TO BE ELIMINATED AS YOU CANNOT USED THE GARAGE AS
 RETURN AIR FOR THE OFFICE SPACE. FBC M 601.5; 7
  
 3) PLEASE SHOW THE SMOKE MITIGATION ROUTE FROM THE
 OFFICE SPACE TO THE 44 INCH X 48 INCH SMOKE MITIGATION
 DUCT IN THE SHAFT. FBC 107.2.1
  
 4) THE BUILDING CORE WAS NOT DESIGNED FOR THIS OFFICE
 SPACE. PLEASE SHOW THE CALCULATIONS THAT THE BATH
 EXHAUST FANS AND THE SMOKE MITIGATION FANS ARE DESIGNED
 TO HANDLE THIS ADDITIONAL LOAD. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-09-22 Cont ID  
Sent By medwards Date 2021-09-22 Time 11:16 Rev Time 0.00
Received By medwards Date 2021-09-22 Time 11:16 Sent To  
Notes
2021-09-22 11:17:071ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21080195
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.02: PLEASE SHOW THE RATED DAMPERS AT ALL
 LOCATIONS WHERE THE NEW MECHANICAL DUCTS PENETRATE THE
 RATED WALLS. THERE ARE IS ONE MISSING IN THE 38? X 12?
 SA AT THE NEW STORAGE AND PARKING GARAGE RATED
 SEPARATION WALL. ALSO IN THE NEW MECHANICAL ROOM THE
 DUCT WORK PENETRATING THE SHAFT THAT IS PART OF THE
 SMOKE MITIGATION SHOULD HAVE A FIRE/SMOKE DETECTOR. FBC
 M 607
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THIS NEW CONDITIONED SPACE. FBC EC
 C403.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-11-02 Cont ID  
Sent By lcrespo Date 2021-11-02 Time 07:49 Rev Time 0.00
Received By lcrespo Date 2021-11-02 Time 07:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-10-01 Cont ID  
Sent By lcrespo Date 2021-10-01 Time 10:45 Rev Time 0.00
Received By lcrespo Date 2021-09-30 Time 16:10 Sent To  
Notes
2021-10-01 10:42:5010/01/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A4.02, IN THE MEN'S RESTROOM, THE WATER
 CLOSET COMPARTMENT SHALL BE LOCATED IN THE CORNER,
 DIAGONAL TO THE DOOR 2020 FBBC ACC. SEC. 604.8.1.7
 WATER CLOSET.
  
 2. ON SHEET A5.10;
  
 A. DETAIL EIGHT HAS A SECTION VIEW FOR VANITY; IT HAS
 THE 27 INCH KNEE CLEARANCE, BUT THE HEIGHT OF THE TOP
 OF THE COUNTER IS AT 3'-0" THIS SHOULD BE 2'-10" PER
 THE 2020 FBC ACC SEC. 606.3.
  
 B. ON THAT SAME DETAIL, THE REFLECTIVE PART OF THE
 MIRROR NEEDS TO BE 40 INCHES TO THE REFLECTIVE SIDE PER
 THE 2020 FBC ACC SEC. 603.3.
  
 3. ON SHEET A7.10;
  
 A. ON THE GENERAL NOTES, NUMBER FIVE REFERS TO ANSI,
 WHICH MAY NOT APPLY TO THIS DRAWING, AND FOR
 ACCESSIBILITY AND PLUMBING, IT HAS THE 2014 YEAR, WHICH
 IS NOT THE CORRECT YEAR. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 B. ON DETAIL THREE FOR THE REAR WALL FOR THE TOILET
 GRAB BAR SAYS 6 INCHES FROM THE WALL, WHICH IS NOT AN
 ACTUAL NUMBER AS THE TOILET IS 16 INCHES TO 18 INCHES
 TO THE CENTER, AND THAT NUMBER MAY CONFUSE THE
 INSTALLER. WOULD YOU PLEASE CORRECT PER THE 2020 FBC
 ACC SEC. 604.2 LOCATION AND WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. ALSO, ON THAT SAME DETAIL, THE SANITARY NAPKIN SHOWS
 IT NOT SUNK IN THE WALL, WHICH IS IN THE CLEAR FLOOR
 SPACE OF THE WATER CLOSET. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 D. ON THAT SAME DETAIL, IT SHOWS THE FLUSH CONTROLS ON
 THE WRONG SIDE OF THE WATER CLOSET PER THE 2020 ACC
 SEC. 604.6 FLUSH CONTROLS. HANDICAP WATER CLOSET FLUSH
 CONTROL SHALL BE HAND OPERATED OR AUTOMATIC AND SHALL
 BE 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR PER THE
 2020 FBC ACC SEC. 604.9.5.
  
 E. ON DETAIL FOUR, THE PARTITIONS TO PROVIDE PRIVACY
 SHALL EXTEND NOT LESS THAN 60 INCHES ABOVE THE FINISHED
 FLOOR SURFACE PER THE 2020 FBC SEC. P 405.3.5 URINAL
 PARTITIONS.
  
 F. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER
 2020 FBC P 425.3 WATER CLOSET SEATS
  
 H. UNDER MOUNTING HEIGHTS LETTER B, IT SAYS 1'-4"
 MINIMUM FOR ALL; PLEASE ADD 1'-6" MAXIMUM FROM THE SIDE
 WALL PER THE 2020 FBC ACC. SEC. 604.2 LOCATION. ON
 LETTER H THE TOILET PAPER SAYS 36" MAXIMUM FROM THE
 REAR WALL. IT SHOULD BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF DISPENSER PER THE 2020 FBC ACC SEC.
 604.7. ON THE LETTER I, KNEE CLEARANCE IS 29 INCHES,
 AND IT SHALL BE A MINIMUM OF 2 INCHES KNEE CLEARANCE
 PER THE 2020 FBC SEC. 306.3. ON LETTER O, THE
 REFLECTIVE PART OF THE MIRROR NEEDS TO BE 40 INCHES TO
 THE REFLECTIVE SIDE PER THE 2020 FBC ACC SEC. 603.3.
  
 I. DOOR HANDLE HARDWARE SHOULD BE NOTED ON BOTH SIDES
 OF THE DOOR PER THE 2020 FBC ACC SEC. 404.2.7.
  
  
 4. ON SHEET P-4.01;
  
 A. ON THE ISOMETRIC, THE WATER CLOSETS ARE IN A
 HORIZONTAL WET VENT, AND THE DRINKING FOUNTAIN HAS TO
 BE DOWNSTREAM FROM IT PER THE 2020 FBC SEC. P 912.1.
  
 B. THERE ARE TWO FLOOR DRAINS ON THE WOMEN'S AND MEN'S
 RESTROOMS, WITH LABELS COVERING THEM. WOULD YOU PLEASE
 MOVE THEM FOR CLARITY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. ON THE ISOMETRIC, PLEASE SHOW THE TRAP PRIMER FOR
 ALL THREE-FLOOR DRAINS. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 D. WOULD YOU PLEASE SHOW LOCATIONS OF WATER HAMMER
 ARRESTORS IN ALL QUICK CLOSING VALVES ON THE WATER
 DIAGRAM 2020 FBC SEC. P604.9.
  
 E. IN THAT SAME DIAGRAM FOR THE HOT WATER HEAR AND
 PUMP, WOULD YOU PLEASE GIVE A DETAILED REFERENCE FOR
 THE DETAIL ON PAGE P5.01 PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. ON SHEET P5.01;
  
 A. PLEASE PROVIDE THE SIZE FOR THE INSULATION FOR THE
 RECIRCULATING SYSTEM THE PIPING THAT SHALL BE INSULATED
 IN ITS ENTIRETY, INCLUDING THE SUPPLY AND RETURN PIPING
 OF A CIRCULATING PER C404.4 (A) INSULATION OF PIPING.
  
 B. WOULD YOU PLEASE SUBMIT LISTED FIRE-STOPPING DETAILS
 FOR THE PIPPING THROUGH RATED WALLS OR THE FLOORS.
 WOULD YOU PLEASE SUBMIT THE COMPLETE ASSEMBLY DETAILS
 FOR THE SYSTEMS PER THE WPB AMENDMENTS TO FBC SEC.
 107.2.1?
  
 6. WOULD YOU PLEASE PROVIDE DETAIL ON THE ARCHITECTURAL
 SHOWING THE ACCESSIBILITY CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS FOR THE DRINKING FOUNTAIN, URINAL, WATER
 CLOSET, LAVATORY IN THE STALL AND OUTSIDE THE STALL PER
 THE 2020 FBC ACC SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-11-12 Cont ID  
Sent By medwards Date 2021-11-12 Time 11:04 Rev Time 0.00
Received By medwards Date 2021-11-12 Time 11:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-26 Cont ID  
Sent By mpeterso Date 2021-10-26 Time 08:33 Rev Time 0.00
Received By mpeterso Date 2021-10-26 Time 08:32 Sent To  
Notes
2021-10-26 08:33:53REVIEW OF SIGNATURE AND SEAL ON DIGITAL PLANS APPROVED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-09-22 Cont ID  
Sent By medwards Date 2021-09-22 Time 12:45 Rev Time 0.00
Received By medwards Date 2021-09-22 Time 12:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-11-18 Cont ID  
Sent By ckimmerl Date 2021-11-18 Time 16:32 Rev Time 0.00
Received By ckimmerl Date 2021-11-18 Time 16:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2021-11-02 Cont ID  
Sent By ckimmerl Date 2021-11-02 Time 15:13 Rev Time 0.00
Received By ckimmerl Date 2021-11-02 Time 15:03 Sent To  
Notes
2021-11-02 15:13:299/27/21 COMMENTS:
 1. DAC APPROVAL FOR THE TRANSFER OF 15,060 SF OF TDR
 NEEDED BEFORE BUILDING PERMIT CAN BE APPROVED.
 [SATISFIED]
 2. PLEASE REMOVE ANY INDICATION OF CARS BEING PARKED ON
 DRIVE AISLES.
 [SATISFIED]
 3. PLEASE INCLUDE ALL THE INFORMATION APPROVED WITH THE
 MINOR SITE PLAN AMENDMENT ISSUED BY THE CITY ON
 9-21-21, INCLUDING ALL THE UPDATED SITE PLAN
 INFORMATION.
 - DAC APPROVAL FOR THE TRANSFER OF 15,060SF OF
 DEVELOPMENT CAPACITY SHALL BE OBTAINED BEFORE ISSUANCE
 OF A BUILDING PERMIT.
 - PROPOSED ADA PARKING SPACES ON 7TH FLOOR SHALL BE
 RELOCATED TO LOWER FLOORS.
 [NOT SATISFIED] ? DO NOT SEE 7TH FLOOR ADA SPACES/LOWER
 FLOORS IN SUBMITTED DRAWINGS, CANNOT CONFIRM RELOCATION
 OF SPACES.
  
 NEW COMMENTS:
 1. PLEASE INCLUDE ALL THE APPROVED CONDITIONS WITH THE
 MINOR SITE PLAN AMENDMENT ISSUED BY THE CITY ON
 9-21-21.
 - PROPOSED ADA PARKING SPACES ON 7TH FLOOR SHALL BE BE
 RELOCATED TO LOWER FLOORS.
 - PLEASE PROVIDE DRAWINGS OR DETAILS INDICATING THE
 RELOCATED ADA PARKING SPACES.
  
 2. PLEASE MARK/INDICATE THAT THE UPPER LEVEL OF 8TH
 STORY GARAGE SHALL BE VALET SERVICE AND STACKER PARKING
 ONLY, TO CONFIRM THAT THERE IS NO NEED FOR TURNAROUND
 SPACES AT ENDS OF THE GARAGE DRIVE AISLE.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-09-27 Cont ID  
Sent By aaponte Date 2021-09-27 Time 12:10 Rev Time 0.00
Received By aaponte Date 2021-09-27 Time 12:10 Sent To  
Notes
2021-09-27 12:17:071. DAC APPROVAL FOR THE TRANSFER OF 15,060 SF OF TDR
 NEEDED BEFORE BUILDING PERMIT CAN BE APPROVED.
 2. PLEASE REMOVE ANY INDICATION OF CARS BEING PARKED ON
 DRIVE AISLES.
 3. PLEASE INCLUDE ALL THE INFORMATION APPROVED WITH THE
 MINOR SITE PLAN AMENDMENT ISSUED BY THE CITY ON
 9-21-21, INCLUDING ALL THE UPDATED SITE PLAN
 INFORMATION.
 FOR ADDTIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.