Plan Review Details - Permit 21080133
Plan Review Stops For Permit 21080133
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-09-21 Cont ID  
Sent By lcrespo Date 2021-09-21 Time 06:45 Rev Time 0.00
Received By lcrespo Date 2021-09-21 Time 06:45 Sent To  
Notes
2021-09-21 06:45:4709/21/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-08-09 Cont ID  
Sent By lcrespo Date 2021-08-09 Time 16:28 Rev Time 0.00
Received By lcrespo Date 2021-08-09 Time 15:46 Sent To  
Notes
2021-08-09 16:28:5508/09/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH A PERMIT FOR EXISTING
 GAS TO A METER. THE BTU LOAD OF THE EXISTING GAS SYSTEM
 MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES PER THE 2020 FBC RES. SECS.
 G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 2. PLEASE PROVIDE A GAS RISER DIAGRAM PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL
 GAS.
  
 3. PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR. THE GENERATOR SHALL BE LISTED AND APPROVED
 PER THE NFPA 58 SEC. 5.20.1. THE GENERATOR SHALL MEET
 THE REQUIREMENTS OF UL 2200.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-21 Cont ID  
Sent By lcrespo Date 2021-09-21 Time 06:45 Rev Time 0.00
Received By lcrespo Date 2021-08-24 Time 15:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-09 Cont ID  
Sent By lcrespo Date 2021-08-09 Time 16:29 Rev Time 0.00
Received By lcrespo Date 2021-08-03 Time 13:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-09-21 Cont ID  
Sent By lcrespo Date 2021-09-21 Time 06:45 Rev Time 0.00
Received By lcrespo Date 2021-09-21 Time 06:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-08-09 Cont ID  
Sent By lcrespo Date 2021-08-09 Time 16:29 Rev Time 0.00
Received By lcrespo Date 2021-08-09 Time 15:46 Sent To  
Notes
***NONE***