Plan Review Details - Permit 21080079
Plan Review Stops For Permit 21080079
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-10-27 Cont ID  
Sent By jgomez Date 2021-10-27 Time 14:55 Rev Time 0.00
Received By jgomez Date 2021-10-27 Time 14:34 Sent To  
Notes
2021-10-27 14:55:32RESIDENTIAL (R2) FOURTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21080079
  
 10/27/21 SENT EMAIL TO ENGINEER AT
 [email protected] STATING THAT THIS PROJECT
 IS BEING DENIED 4 TIMES. JG.
  
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ARCHITECTS WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT
 NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW
  
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 ORIGINAL COMMENT:
 1- DESIGN WIND PRESSURE CALCULATIONS SUBMITTED:
 BASED ON THE AERIAL VIEWS ON THE PROPERTY APPRAISER
 WEBSITE, IT LOOKS LIKE SOME OPENINGS ( WINDOW #6 AND
 SLIDING GLASS DOORS) ARE IN THE END ZONE NOT IN THE
 INTERIOR ZONE AND THE BUILDING DIMENSIONS ARE WRONG.
 THIS IS CRITICAL BECAUSE PRODUCT APPROVALS SUBMITTED
 MAY NOT MEET THE DESIGN PRESSURES. REVISE CALCULATIONS
 SUBMITTED SHOWING THE OPENINGS THAT ARE LOCATED IN THE
 END ZONE OR PROVIDE SITE SPECIFIC DESIGN WIND PRESSURES
 SHOWING THE ACTUAL BUILDING DIMENSIONS AND WALL ZONES.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. REVISED CALCULATIONS SUBMITTED ON
 10/21/21 ARE WRONG. STRUCTURE INFORMATION IS WRONG.
 ENGINEER OF RECORD NEEDS TO SEE THE BUILDING AND REVISE
 THIS INFORMATION TO MATCH ACTUAL BUILDING CONDITIONS.
 AS MENTIONED BEFORE, IT LOOKS LIKE SOME OPENINGS (
 WINDOW #6 AND SLIDING GLASS DOORS) ARE IN THE END ZONE
 NOT IN THE INTERIOR ZONE. REVISE CALCULATIONS SUBMITTED
 SHOWING THE OPENINGS THAT ARE LOCATED IN THE END ZONE
 OR PROVIDE SITE SPECIFIC DESIGN WIND PRESSURES SHOWING
 THE ACTUAL BUILDING DIMENSIONS AND WALL ZONES. SEC.
 107.2.1.2 CITY AMENDMENTS.
  
  
 2- PRODUCT APPROVALS SUBMITTED WILL BE REVIEWED ONCE
 THE DESIGN WIND PRESSURES ARE REVISED. PLEASE CHECK
 PRODUCT APPROVALS SUBMITTED MEET THE REVISED DESIGN
 PRESSURES. OTHERWISE NEW PRODUCT APPROVALS ARE
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- WINDOW MULLIONS PRODUCT APPROVAL SUBMITTED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
 SEC. 107.2.1 CITY AMENDMENTS.
 REPEAT COMMENT.
  
  
 NOTE: SEE SEC. 702.4 FBC-EXISTING BUILDING CODE. WINDOW
 OPENING CONTROL DEVICES IN WINDOW REPLACEMENT ARE
 REQUIRED WHEN THE FOLLOWING APPLY:
 IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING UNITS
 AND ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 WINDOW OPENING CONTROL DEVICES COMPLYING WITH ASTM
 F2090 SHALL BE INSTALLED WHERE AN EXISTING WINDOW IS
 REPLACED AND WHERE ALL OF THE FOLLOWING APPLY TO THE
 REPLACEMENT WINDOW:
 1.THE WINDOW IS OPERABLE;
 2. THE WINDOW REPLACEMENT INCLUDES REPLACEMENT OF THE
 SASH AND THE FRAME;
 3.ONE OF THE FOLLOWING APPLIES:
 3.1.IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING
 UNITS, THE TOP OF THE SILL OF THE WINDOW OPENING IS AT
 A HEIGHT LESS THAN 36 INCHES (915 MM) ABOVE THE
 FINISHED FLOOR; OR
 3.2. IN ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 THE TOP SILL OF THE WINDOW OPENING IS AT A HEIGHT LESS
 THAN 24 INCHES (610 MM) ABOVE THE FINISHED FLOOR;
 4.THE WINDOW WILL PERMIT OPENINGS THAT WILL ALLOW
 PASSAGE OF A 4-INCH-DIAMETER (102 MM) SPHERE WHEN THE
 WINDOW IS IN ITS LARGEST OPENED POSITION; AND
 5.THE VERTICAL DISTANCE FROM THE TOP OF THE SILL OF THE
 WINDOW OPENING TO THE FINISHED GRADE OR OTHER SURFACE
 BELOW, ON THE EXTERIOR OF THE BUILDING, IS GREATER THAN
 72 INCHES (1829 MM).
 THE WINDOW OPENING CONTROL DEVICE, AFTER OPERATION TO
 RELEASE THE CONTROL DEVICE ALLOWING THE WINDOW TO FULLY
 OPEN, SHALL NOT REDUCE THE MINIMUM NET CLEAR OPENING
 AREA OF THE WINDOW UNIT TO LESS THAN THE AREA REQUIRED
 BY THE FLORIDA BUILDING CODE, BUILDING
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-10-18 Cont ID  
Sent By jgomez Date 2021-10-18 Time 09:59 Rev Time 0.00
Received By jgomez Date 2021-10-18 Time 09:26 Sent To  
Notes
2021-10-18 10:00:34RESIDENTIAL (R2) THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21080079
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- DESIGN WIND PRESSURE CALCULATIONS SUBMITTED:
 BASED ON THE AERIAL VIEWS ON THE PROPERTY APPRAISER
 WEBSITE, IT LOOKS LIKE SOME OPENINGS ( WINDOW #6 AND
 SLIDING GLASS DOORS) ARE IN THE END ZONE NOT IN THE
 INTERIOR ZONE AND THE BUILDING DIMENSIONS ARE WRONG.
 THIS IS CRITICAL BECAUSE PRODUCT APPROVALS SUBMITTED
 MAY NOT MEET THE DESIGN PRESSURES. REVISE CALCULATIONS
 SUBMITTED SHOWING THE OPENINGS THAT ARE LOCATED IN THE
 END ZONE OR PROVIDE SITE SPECIFIC DESIGN WIND PRESSURES
 SHOWING THE ACTUAL BUILDING DIMENSIONS AND WALL ZONES.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. CALCULATIONS WERE NOT REVISED. AS
 MENTIONED BEFORE, IT LOOKS LIKE SOME OPENINGS ( WINDOW
 #6 AND SLIDING GLASS DOORS) ARE IN THE END ZONE NOT IN
 THE INTERIOR ZONE. REVISE CALCULATIONS SUBMITTED
 SHOWING THE OPENINGS THAT ARE LOCATED IN THE END ZONE
 OR PROVIDE SITE SPECIFIC DESIGN WIND PRESSURES SHOWING
 THE ACTUAL BUILDING DIMENSIONS AND WALL ZONES. SEC.
 107.2.1.2 CITY AMENDMENTS.
 NOTE: GIVEN THE SHAPE, HEIGHT AND DIMENSIONS OF THIS
 BUILDING AND BASED ON THE LOCATION OF THE OPENINGS, THE
 CONSERVATIVE APPROACH IS TO ASSUME THAT SOME OPENINGS
 ARE LOCATED IN THE END ZONE AS SUGGESTED ON THE WEBSITE
 WHERE CONTRACTOR IS ENTERING THE DATA TO OBTAIN THE
 DESIGN WIND PRESSURES. OTHERWISE SITE SPECIFIC
 ENGINEERING WHERE THE ENGINEER TAKES INTO CONSIDERATION
 THE ACTUAL SHAPE AND BUILDING DIMENSIONS WILL BE
 REQUIRED TO SHOW OPENINGS ARE NOT LOCATED IN THE END
 ZONE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 2- PRODUCT APPROVALS SUBMITTED WILL BE REVIEWED ONCE
 THE DESIGN WIND PRESSURES ARE REVISED. PLEASE CHECK
 PRODUCT APPROVALS SUBMITTED MEET THE REVISED DESIGN
 PRESSURES. OTHERWISE NEW PRODUCT APPROVALS ARE
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- WINDOW MULLIONS PRODUCT APPROVAL SUBMITTED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
 SEC. 107.2.1 CITY AMENDMENTS.
 REPEAT COMMENT.
  
  
 NOTE: SEE SEC. 702.4 FBC-EXISTING BUILDING CODE. WINDOW
 OPENING CONTROL DEVICES IN WINDOW REPLACEMENT ARE
 REQUIRED WHEN THE FOLLOWING APPLY:
 IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING UNITS
 AND ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 WINDOW OPENING CONTROL DEVICES COMPLYING WITH ASTM
 F2090 SHALL BE INSTALLED WHERE AN EXISTING WINDOW IS
 REPLACED AND WHERE ALL OF THE FOLLOWING APPLY TO THE
 REPLACEMENT WINDOW:
 1.THE WINDOW IS OPERABLE;
 2. THE WINDOW REPLACEMENT INCLUDES REPLACEMENT OF THE
 SASH AND THE FRAME;
 3.ONE OF THE FOLLOWING APPLIES:
 3.1.IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING
 UNITS, THE TOP OF THE SILL OF THE WINDOW OPENING IS AT
 A HEIGHT LESS THAN 36 INCHES (915 MM) ABOVE THE
 FINISHED FLOOR; OR
 3.2. IN ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 THE TOP SILL OF THE WINDOW OPENING IS AT A HEIGHT LESS
 THAN 24 INCHES (610 MM) ABOVE THE FINISHED FLOOR;
 4.THE WINDOW WILL PERMIT OPENINGS THAT WILL ALLOW
 PASSAGE OF A 4-INCH-DIAMETER (102 MM) SPHERE WHEN THE
 WINDOW IS IN ITS LARGEST OPENED POSITION; AND
 5.THE VERTICAL DISTANCE FROM THE TOP OF THE SILL OF THE
 WINDOW OPENING TO THE FINISHED GRADE OR OTHER SURFACE
 BELOW, ON THE EXTERIOR OF THE BUILDING, IS GREATER THAN
 72 INCHES (1829 MM).
 THE WINDOW OPENING CONTROL DEVICE, AFTER OPERATION TO
 RELEASE THE CONTROL DEVICE ALLOWING THE WINDOW TO FULLY
 OPEN, SHALL NOT REDUCE THE MINIMUM NET CLEAR OPENING
 AREA OF THE WINDOW UNIT TO LESS THAN THE AREA REQUIRED
 BY THE FLORIDA BUILDING CODE, BUILDING
  
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-10-08 Cont ID  
Sent By jgomez Date 2021-10-08 Time 10:09 Rev Time 0.00
Received By jgomez Date 2021-10-08 Time 10:01 Sent To  
Notes
2021-10-08 10:42:44RESIDENTIAL (R2) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21080079
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- DESIGN WIND PRESSURE CALCULATIONS SUBMITTED:
 BASED ON THE AERIAL VIEWS ON THE PROPERTY APPRAISER
 WEBSITE, IT LOOKS LIKE SOME OPENINGS ARE IN THE END
 ZONE NOT IN THE INTERIOR ZONE AND THE BUILDING
 DIMENSIONS ARE WRONG. THIS IS CRITICAL BECAUSE PRODUCT
 APPROVALS SUBMITTED MAY NOT MEET THE DESIGN PRESSURES.
 REVISE CALCULATIONS SUBMITTED SHOWING THE OPENINGS THAT
 ARE LOCATED IN THE END ZONE OR PROVIDE SITE SPECIFIC
 DESIGN WIND PRESSURES SHOWING THE ACTUAL BUILDING
 DIMENSIONS AND WALL ZONES. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 2- PRODUCT APPROVALS SUBMITTED WILL BE REVIEWED ONCE
 THE DESIGN WIND PRESSURES ARE REVISED. PLEASE CHECK
 PRODUCT APPROVALS SUBMITTED MEET THE REVISED DESIGN
 PRESSURES. OTHERWISE NEW PRODUCT APPROVALS ARE
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- WINDOW MULLIONS PRODUCT APPROVAL SUBMITTED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
 SEC. 107.2.1 CITY AMENDMENTS.
 REPEAT COMMENT.
  
  
 NOTE: SEE SEC. 702.4 FBC-EXISTING BUILDING CODE. WINDOW
 OPENING CONTROL DEVICES IN WINDOW REPLACEMENT ARE
 REQUIRED WHEN THE FOLLOWING APPLY:
 IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING UNITS
 AND ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 WINDOW OPENING CONTROL DEVICES COMPLYING WITH ASTM
 F2090 SHALL BE INSTALLED WHERE AN EXISTING WINDOW IS
 REPLACED AND WHERE ALL OF THE FOLLOWING APPLY TO THE
 REPLACEMENT WINDOW:
 1.THE WINDOW IS OPERABLE;
 2. THE WINDOW REPLACEMENT INCLUDES REPLACEMENT OF THE
 SASH AND THE FRAME;
 3.ONE OF THE FOLLOWING APPLIES:
 3.1.IN GROUP R-2 OR R-3 BUILDINGS CONTAINING DWELLING
 UNITS, THE TOP OF THE SILL OF THE WINDOW OPENING IS AT
 A HEIGHT LESS THAN 36 INCHES (915 MM) ABOVE THE
 FINISHED FLOOR; OR
 3.2. IN ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES
 REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL,
 THE TOP SILL OF THE WINDOW OPENING IS AT A HEIGHT LESS
 THAN 24 INCHES (610 MM) ABOVE THE FINISHED FLOOR;
 4.THE WINDOW WILL PERMIT OPENINGS THAT WILL ALLOW
 PASSAGE OF A 4-INCH-DIAMETER (102 MM) SPHERE WHEN THE
 WINDOW IS IN ITS LARGEST OPENED POSITION; AND
 5.THE VERTICAL DISTANCE FROM THE TOP OF THE SILL OF THE
 WINDOW OPENING TO THE FINISHED GRADE OR OTHER SURFACE
 BELOW, ON THE EXTERIOR OF THE BUILDING, IS GREATER THAN
 72 INCHES (1829 MM).
 THE WINDOW OPENING CONTROL DEVICE, AFTER OPERATION TO
 RELEASE THE CONTROL DEVICE ALLOWING THE WINDOW TO FULLY
 OPEN, SHALL NOT REDUCE THE MINIMUM NET CLEAR OPENING
 AREA OF THE WINDOW UNIT TO LESS THAN THE AREA REQUIRED
 BY THE FLORIDA BUILDING CODE, BUILDING
  
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-03 Cont ID  
Sent By jgomez Date 2021-09-03 Time 14:54 Rev Time 0.00
Received By jgomez Date 2021-09-03 Time 13:52 Sent To  
Notes
2021-09-03 14:55:18RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21080079
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- DESIGN WIND PRESSURE CALCULATIONS SUBMITTED:
 A)BUILDING MEAN ROOF HEIGHT OF 82' IS INCORRECT. THIS
 IS A 10 STORY BUILDING. SEE BUILDING AND REVISE ALL THE
 DESIGN CRITERIA AS REQUIRED, INCLUDING THE VELOCITY
 PRESSURE COEFFICIENT.
 CHAPTER 30 ASCE 7-16.
  
 B) BUILDING DIMENSION OF 60' IS INCORRECT. SEE BUILDING
 AND REVISE THE DESIGN CRITERIA AS REQUIRED, INCLUDING
 THE END ZONE DISTANCE.
 CHAPTER 30 ASCE 7-16.
  
 C) BASED ON THE END ZONE DISTANCE, IT LOOKS LIKE SOME
 WINDOWS, DOORS MAY BE IN THE END ZONE NOT THE INTERIOR
 ZONE. SEE BUILDING AND REVISE CALCULATIONS AS REQUIRED.
 CHAPTER 30 ASCE 7-16
  
 D)ENGINEER TO CLARIFY WHY THE DEVICE CALCULATIONS HAVE
 AN ELEVATION OF 7 FEET?. THIS IS A 10 STORY BUILDING.
 CHAPTER 30 ASCE 7-16
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 E) WIND PRESSURE CALCULATIONS HAVE A COPY OF THE
 ENGINEER'S SEAL/SIGNATURE. NEED ORIGINAL SEAL/SIGNATURE
 AS REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 NOTE: PLANS MAY BE SUBMITTED WITH A DIGITAL SIGNATURE
 OR HARD COPIES WITH LICENSED DESIGN PROFESSIONAL SEAL
 AND SIGNATURE MAY BE DROPPED (OR MAILED) TO CITY HALL
 FOR RECORDS RETENTION.
  
 2- PRODUCT APPROVALS SUBMITTED WILL BE REVIEWED ONCE
 THE DESIGN WIND PRESSURES ARE REVISED. PLEASE CHECK
 PRODUCT APPROVALS SUBMITTED MEET THE REVISED DESIGN
 PRESSURES. OTHERWISE NEW PRODUCT APPROVALS ARE
 REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- WINDOW MULLIONS PRODUCT APPROVAL SUBMITTED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
 SEC. 107.2.1 CITY AMENDMENTS.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-10-27 Cont ID  
Sent By jgomez Date 2021-10-27 Time 15:23 Rev Time 0.00
Received By jgomez Date 2021-10-21 Time 12:58 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-10-18 Cont ID  
Sent By jgomez Date 2021-10-18 Time 10:28 Rev Time 0.00
Received By jgomez Date 2021-10-14 Time 06:34 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-08 Cont ID  
Sent By jgomez Date 2021-10-08 Time 10:43 Rev Time 0.00
Received By jgomez Date 2021-09-27 Time 08:23 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-03 Cont ID  
Sent By jgomez Date 2021-09-03 Time 14:59 Rev Time 0.00
Received By jgomez Date 2021-08-11 Time 10:57 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-10-27 Cont ID  
Sent By jgomez Date 2021-10-27 Time 15:15 Rev Time 0.00
Received By jgomez Date 2021-10-27 Time 15:15 Sent To  
Notes
2021-10-27 15:15:55SIGNATURE REVIEW:
  
 1- WIND PRESSURE CALCULATIONS HAVE A COPY OF THE
 ENGINEER'S SEAL/SIGNATURE. NEED ORIGINAL SEAL/SIGNATURE
 AS REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 NOTE: PLANS MAY BE SUBMITTED WITH A DIGITAL SIGNATURE
 OR HARD COPIES WITH LICENSED DESIGN PROFESSIONAL SEAL
 AND SIGNATURE MAY BE DROPPED (OR MAILED) TO CITY HALL
 FOR RECORDS RETENTION.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-09-29 Cont ID  
Sent By lcrespo Date 2021-09-29 Time 08:56 Rev Time 0.00
Received By lcrespo Date 2021-09-29 Time 08:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-09-03 Cont ID  
Sent By jgomez Date 2021-09-03 Time 14:58 Rev Time 0.00
Received By jgomez Date 2021-09-03 Time 09:52 Sent To  
Notes
2021-09-03 14:59:33SIGNATURE REVIEW:
  
 1- WIND PRESSURE CALCULATIONS HAVE A COPY OF THE
 ENGINEER'S SEAL/SIGNATURE. NEED ORIGINAL SEAL/SIGNATURE
 AS REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 NOTE: PLANS MAY BE SUBMITTED WITH A DIGITAL SIGNATURE
 OR HARD COPIES WITH LICENSED DESIGN PROFESSIONAL SEAL
 AND SIGNATURE MAY BE DROPPED (OR MAILED) TO CITY HALL
 FOR RECORDS RETENTION.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  