Plan Review Details - Permit 21080059
Plan Review Stops For Permit 21080059
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-08-23 Cont ID  
Sent By shill Date 2021-08-23 Time 18:16 Rev Time 0.00
Received By shill Date 2021-08-23 Time 18:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-21 Cont ID  
Sent By shill Date 2021-08-21 Time 07:34 Rev Time 0.00
Received By shill Date 2021-08-21 Time 07:34 Sent To  
Notes
2021-08-21 07:35:57****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE PREVIOUS LIST, 3 TEST REPORTS REQUIRED.
  
 STC - NOT PROVIDED
 IIC - OK
 FLAME SPREAD - SUPERSIM 90 FLAME SPREAD REPORT WAS
 SUBMITTED. BECAUSE TILE IS PROPOSED, A LETTER FROM THE
 MANUFACTURER STATING THAT THEY COULD REASONABLY EXPECT
 SIMILAR TEST REPORTS FROM MSC90 WILL BE ACCEPTED.
  
 1. MSC90 UNDERLAYMENT IS PROPOSED BUT SUPER SIM 90 TEST
 REPORTS WERE SUBMITTED. EITHER PROVIDE TEST REPORTS FOR
 MSC90 OR REVISE PLAN TO PROPOSE SUPER SIM 90.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-13 Cont ID  
Sent By rmcdouga Date 2021-08-13 Time 17:49 Rev Time 0.00
Received By shill Date 2021-08-13 Time 17:49 Sent To  
Notes
2021-08-13 17:50:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FOR MSC90, PROVIDE THE FOLLOWING TEST REPORTS.
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-08-09 Cont ID  
Sent By pleduc Date 2021-08-09 Time   Rev Time 0.00
Received By pleduc Date 2021-08-09 Time 09:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-21 Cont ID  
Sent By shill Date 2021-08-21 Time 07:39 Rev Time 0.00
Received By shill Date 2021-08-17 Time 08:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-13 Cont ID  
Sent By shill Date 2021-08-13 Time 17:51 Rev Time 0.00
Received By shill Date 2021-08-05 Time 10:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-08-13 Cont ID  
Sent By shill Date 2021-08-13 Time 17:50 Rev Time 0.00
Received By shill Date 2021-08-13 Time 17:51 Sent To  
Notes
***NONE***