2021-09-07 08:43:19 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 21071626 |
| ADD: 610 CLEMATIS ST. # 632 |
| CONT: TBD/ TO BE DETERMINED |
| TEL: ?? |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. SEPT. 07TH/ 2021 |
| ACTION: DENIED |
| 1) SHEET A-100 DETAIL 2 NOTE # 5 INDICATES NEW FLOORING |
| IN THE LIVING ROOM, MATER BEDROOM & GUEST BEDROOM, TYPE |
| OF FLOORING TO BE SPEC?D WOOD FLOORING WITH ACOUSTICAL |
| UNDERLAYMENT. IN THE MASTER BATH AND GUEST BATH THE |
| NOTE D-3 INDICATES TO REMOVE ALL FLOORING AND BASE NEW |
| WORK STATES ALL NEW FLOOR AND WALL TILE IN SHOWER. THIS |
| REVIEW THERE WERE NO TESTING REPORTS SUBMITTED FOR |
| EITHER THE WOOD FLOORING & UNDERLAYMENT NOR FLOOR TILE |
| AND ASSOCIATED UNDERLAYMENT. |
| FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, |
| STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE |
| HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO |
| THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| |
| 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| |
| 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 2) SHEET A-100 DETAIL 2 NOTE # INDICATES A NEW |
| WATERPROOF WATER MEMBRANE BEHIND THE WALL TILE. PLEASE |
| SHOW COMPLIANCE WITH 2020 FBC-B 2509.2 BASE FOR TILE. |
| MATERIALS USED AS A BASE FOR WALL TILE IN TUB AND |
| SHOWER AREAS AND WALLS AND CEILING PANELS IN SHOWER |
| AREAS SHALL BE OF MATERIALS LISTED IN TABLE 2509.2 AND |
| INSTALLED IN ACCORDANCE WITH MANUFACTURER?S |
| RECOMMENDATIONS. WATER RESISTANT GYPSUM BACKING BOARD |
| SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| GA-216 OR ASTM C840 AND THE MANUFACTURE?S |
| RECOMMENDATIONS. |
| |
| 3) SHEET A-100 DETAIL # 4 SHOWS A DROPPED CEILING/ |
| SOFFIT WITH NOTES C1 & C2 REFERRING TO SHEET A-100 |
| DETAIL #5. DETAIL #5 SHOWS A DROPPED HEADER AND A |
| FLOATING DROPPED CEILING, THE BACKER BOARD IS NOT |
| ATTACHED TO THE DROPPED HEADER, NOR IS THE TYPE OF |
| BACKER BOARD CALLED OUT. THIS DETAIL LACKS THE |
| FOLLOWING INFORMATION, FINISH ELEVATION, GIVEN HEIGHT |
| OF THE EXISTING DROPPED CEILING BUT NOT NEW DROPPED |
| FLOATING CEILING. THE TYPE OF BACKER BOARD AND |
| THICKNESS IS NOT GIVEN. THE TYPE OF MATERIAL USED TO |
| HANG FROM THE EXISTING FLOOR/ CEILING ASSEMBLY, ANCHORS |
| TO THE CONCRETE FLOOR ASSEMBLY, CENTER TO CENTER |
| FRAMING MEMBERS AND FLOATING DROPPED CEILING ASSEMBLY |
| ANCHORS AND SPACING TO THE FRAMING MEMBERS. 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. SECTION / TABLE |
| 2508.1 ASTM C754. |
| |
| 4) SHEET A100 THE GUEST BATH INDICATES THE REMOVAL OF A |
| TUB AND INSTALLATION OF NEW SHOWER AND NEW DRAIN |
| LOCATION. |
| |
| 4A) POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS |
| IF THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO |
| BE REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR |
| SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION |
| CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 4B) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE |
| FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE |
| WITH THE 2020 FBC-B SECTION 714.5.1.2. |
| THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY |
| A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN |
| ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL |
| HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT |
| NOT LESS THAN THE REQUIRED RATING OF THE FLOOR |
| PENETRATED. |
| |
| 4C) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS |
| A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS |
| AND CEILING PANELS IN SHOWER AREAS SHALL BE OF |
| MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN |
| ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER |
| RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE |
| FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN |
| INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND |
| THE MANUFACTURE?S RECOMMENDATIONS. |
| |
| 4D) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER |
| COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS |
| SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A |
| HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET. |
| |
| 4E) SHEET A-100 DETAIL 4 DROPPED CEILING WORK THERE IS |
| A NOTE INDICATING EXISTING SPERINKLER SYSTEM TO REMAIN. |
| NO SPRINKLER WORK PLEASE SHOW THE FIRE SPRINKLER |
| LOCATIONS IN THE GUEST BEDROOM AND DROPPED CEILING |
| AREA. NOTE IS THE ARE CEILING OR SIDE WALL MOUNT. |
| 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. IF WORK |
| IS REQUIRED, FOR LESS THAN 50 HEADS A FIRE SPRINKLER |
| CONTRACTOR CAN DRAW THE PLANS IF THEY ARE THE ONES |
| GETTING THE FIRE SPRINKLER PERMIT. L |
| |
| 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| |
| MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE |
| WORKING FROM CITY HALL. |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |