Plan Review Details - Permit 21071626
Plan Review Stops For Permit 21071626
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-09-21 Cont ID  
Sent By jwitmer Date 2021-09-21 Time 14:15 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-09-21 14:14:46TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-09-07 Cont ID  
Sent By jwitmer Date 2021-09-07 Time 08:37 Rev Time 0.00
Received By jwitmer Date 2021-09-07 Time 07:49 Sent To  
Notes
2021-09-07 08:03:40TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-09-21 Cont ID  
Sent By jwitmer Date 2021-09-21 Time 14:23 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-07 Cont ID  
Sent By jwitmer Date 2021-09-07 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2021-09-07 Time 07:49 Sent To  
Notes
2021-09-07 08:43:19WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21071626
 ADD: 610 CLEMATIS ST. # 632
 CONT: TBD/ TO BE DETERMINED
 TEL: ??
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 07TH/ 2021
 ACTION: DENIED
 1) SHEET A-100 DETAIL 2 NOTE # 5 INDICATES NEW FLOORING
 IN THE LIVING ROOM, MATER BEDROOM & GUEST BEDROOM, TYPE
 OF FLOORING TO BE SPEC?D WOOD FLOORING WITH ACOUSTICAL
 UNDERLAYMENT. IN THE MASTER BATH AND GUEST BATH THE
 NOTE D-3 INDICATES TO REMOVE ALL FLOORING AND BASE NEW
 WORK STATES ALL NEW FLOOR AND WALL TILE IN SHOWER. THIS
 REVIEW THERE WERE NO TESTING REPORTS SUBMITTED FOR
 EITHER THE WOOD FLOORING & UNDERLAYMENT NOR FLOOR TILE
 AND ASSOCIATED UNDERLAYMENT.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) SHEET A-100 DETAIL 2 NOTE # INDICATES A NEW
 WATERPROOF WATER MEMBRANE BEHIND THE WALL TILE. PLEASE
 SHOW COMPLIANCE WITH 2020 FBC-B 2509.2 BASE FOR TILE.
 MATERIALS USED AS A BASE FOR WALL TILE IN TUB AND
 SHOWER AREAS AND WALLS AND CEILING PANELS IN SHOWER
 AREAS SHALL BE OF MATERIALS LISTED IN TABLE 2509.2 AND
 INSTALLED IN ACCORDANCE WITH MANUFACTURER?S
 RECOMMENDATIONS. WATER RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C840 AND THE MANUFACTURE?S
 RECOMMENDATIONS.
  
 3) SHEET A-100 DETAIL # 4 SHOWS A DROPPED CEILING/
 SOFFIT WITH NOTES C1 & C2 REFERRING TO SHEET A-100
 DETAIL #5. DETAIL #5 SHOWS A DROPPED HEADER AND A
 FLOATING DROPPED CEILING, THE BACKER BOARD IS NOT
 ATTACHED TO THE DROPPED HEADER, NOR IS THE TYPE OF
 BACKER BOARD CALLED OUT. THIS DETAIL LACKS THE
 FOLLOWING INFORMATION, FINISH ELEVATION, GIVEN HEIGHT
 OF THE EXISTING DROPPED CEILING BUT NOT NEW DROPPED
 FLOATING CEILING. THE TYPE OF BACKER BOARD AND
 THICKNESS IS NOT GIVEN. THE TYPE OF MATERIAL USED TO
 HANG FROM THE EXISTING FLOOR/ CEILING ASSEMBLY, ANCHORS
 TO THE CONCRETE FLOOR ASSEMBLY, CENTER TO CENTER
 FRAMING MEMBERS AND FLOATING DROPPED CEILING ASSEMBLY
 ANCHORS AND SPACING TO THE FRAMING MEMBERS. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED. SECTION / TABLE
 2508.1 ASTM C754.
  
 4) SHEET A100 THE GUEST BATH INDICATES THE REMOVAL OF A
 TUB AND INSTALLATION OF NEW SHOWER AND NEW DRAIN
 LOCATION.
  
 4A) POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS
 IF THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO
 BE REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR
 SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION
 CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4B) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE
 FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE
 WITH THE 2020 FBC-B SECTION 714.5.1.2.
 THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY
 A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN
 ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL
 HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT
 NOT LESS THAN THE REQUIRED RATING OF THE FLOOR
 PENETRATED.
  
 4C) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS
 A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 4D) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 4E) SHEET A-100 DETAIL 4 DROPPED CEILING WORK THERE IS
 A NOTE INDICATING EXISTING SPERINKLER SYSTEM TO REMAIN.
 NO SPRINKLER WORK PLEASE SHOW THE FIRE SPRINKLER
 LOCATIONS IN THE GUEST BEDROOM AND DROPPED CEILING
 AREA. NOTE IS THE ARE CEILING OR SIDE WALL MOUNT.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. IF WORK
 IS REQUIRED, FOR LESS THAN 50 HEADS A FIRE SPRINKLER
 CONTRACTOR CAN DRAW THE PLANS IF THEY ARE THE ONES
 GETTING THE FIRE SPRINKLER PERMIT. L
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-10-05 Cont ID  
Sent By fgiaquin Date 2021-10-05 Time 19:16 Rev Time 0.00
Received By fgiaquin Date 2021-10-05 Time 18:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-08-18 Cont ID  
Sent By fgiaquin Date 2021-08-18 Time 21:33 Rev Time 0.00
Received By fgiaquin Date 2021-08-18 Time 19:18 Sent To  
Notes
2021-08-18 21:32:58ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW USING INDUSTRY
 STANDARD SYMBOLS FOR LIGHING, SWITCHES, RECEPTACLES
 ETC. SHOW EXACTLY WHAT IS BEING DONE AND WHERE. PLAN
 PROVIDED ONLY HAS NOTES OF WORK TO BE PERFORMED AND IS
 VAGUE. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-09-15 Cont ID  
Sent By pleduc Date 2021-09-15 Time   Rev Time 0.00
Received By pleduc Date 2021-09-15 Time 14:25 Sent To  
Notes
2021-09-15 14:25:44FIRE PROVISO:
  
 DUE TO THE REMOVAL OF WALLS AND RECONSTRUCTION,
  
 THE FIRE SPRINKLER HEAD COVERAGE REQUIRES A
 REVIEW BY A FS CONTRACTOR FOR CODE COVERAGE.
  
 ALL FS WORK SHALL BE DONE UNDER SEPARATE PERMIT & SHOP
 DRAWINGS.
  
 IF NO FS WORK REQUIRED THE CONTRACTOR WILL NEED TO
 SUBMIT A LETTER
 STATING SUCH FOR THE FIRE INSPECTOR TO REVIEW ON
 INSPECTION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-08-05 Cont ID  
Sent By pleduc Date 2021-08-05 Time   Rev Time 0.00
Received By pleduc Date 2021-08-05 Time 15:18 Sent To  
Notes
2021-08-05 15:22:39FIRE PROVISO:
  
 DUE TO THE REMOVAL OF WALLS AND RECONSTRUCTION,
  
 THE FIRE SPRINKLER HEAD COVERAGE REQUIRES A
 REVIEW BY A FS CONTRACTOR FOR CODE COVERAGE.
  
 ALL FS WORK SHALL BE DONE UNDER SEPARATE PERMIT & SHOP
 DRAWINGS.
  
 IF NO FS WORK REQUIRED THE CONTRACTOR WILL NEED TO
 SUBMIT A LETTER
 STATING SUCH FOR THE FIRE INSPECTOR TO REVIEW ON
 INSPECTION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-05 Cont ID  
Sent By fgiaquin Date 2021-10-05 Time 19:16 Rev Time 0.00
Received By fgiaquin Date 2021-09-14 Time 09:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-07 Cont ID  
Sent By jwitmer Date 2021-09-07 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2021-08-03 Time 06:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-09-22 Cont ID  
Sent By medwards Date 2021-09-22 Time 09:51 Rev Time 0.00
Received By medwards Date 2021-09-22 Time 09:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-08-19 Cont ID  
Sent By medwards Date 2021-08-19 Time 17:12 Rev Time 0.00
Received By medwards Date 2021-08-19 Time 17:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-09-21 Cont ID  
Sent By lcrespo Date 2021-09-21 Time 13:22 Rev Time 0.00
Received By lcrespo Date 2021-09-21 Time 13:22 Sent To  
Notes
2021-09-21 13:22:5309/21/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-08-10 Cont ID  
Sent By lcrespo Date 2021-08-10 Time 12:07 Rev Time 0.00
Received By lcrespo Date 2021-08-10 Time 12:07 Sent To  
Notes
2021-08-10 12:29:0008/10/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS BUILDING WAS CONSTRUCTED UNDER THE FAIR HOUSING
 ACT. WOULD YOU PLEASE INDICATE ON PLANS WHICH DESIGN
 SPECIFICATION ( "A" OR "B" OF THE ACT) WAS USED IN THE
 ORIGINAL DESIGN OF THESE UNITS? TELL US WHICH USABLE
 BATHROOM IN THE DWELLING UNITS AND THE PROPOSED
 ALTERATION IN THE BATHROOM SHALL ALSO COMPLY WITH THE
 FAIR HOUSING ACT.
  
 THIS BUILDING MAY HAVE BEEN DESIGNED UNDER THE FAIR
 HOUSING DESIGN MANUAL OR THE FAIR HOUSING GUIDELINES.
 THIS NEEDS TO BE DETERMINED BY RESEARCHING WHEN THE
 BUILDING WAS BUILT AND REQUESTING PLANS FROM THIS
 CITY'S WEBSITE. THIS MAY INCUR A FEE AND TIME TO
 RETRIEVE ALL THIS INFORMATION. IT IS UP TO THE
 ARCHITECT TO REQUEST THE INFORMATION AND DETERMINE IF
 THE LEVEL OF ACCESSIBILITY IS ALTERED. WE REQUIRE TO
 SHOW THE DIMENSION OF THE CLEAR FLOOR SPACE IN THE
 BATHROOM IN FRONT OF EACH FIXTURE IN THAT BATHROOM. THE
 RESEARCH WILL TELL IF IT'S AN A OR B TYPE BATHROOM.
  
 THE FAIR HOUSING ACT PROVIDES TWO SETS OF
 SPECIFICATIONS TO DESIGN BATHROOMS USABLE BY PEOPLE
 WITH DISABILITIES. THOUGH THERE ARE OTHER DIFFERENCES,
 SPECIFICATION B BATHROOMS OFFER GREATER ACCESS TO THE
 TUB THAN SPECIFICATION A BATHROOMS.
  
 IF THE SPECIFICATION A DESIGN IS SELECTED, ALL
 BATHROOMS IN THE UNIT MUST COMPLY WITH THE
 SPECIFICATION A STANDARD (SECTION 7.14). THIS INCLUDES
 ACCESS TO ALL FIXTURES IN EACH SPECIFICATION A BATHROOM
 (E.G., TWO LAVATORIES IN ONE BATHROOM WOULD BOTH NEED
 TO MEET FHA REGULATIONS).
  
 IF THE SPECIFICATION B DESIGN IS SELECTED, ONLY ONE
 BATHROOM IN THE UNIT AND ONE OF EACH TYPE OF FIXTURE
 WITHIN THE BATHROOM MUST COMPLY WITH SPECIFICATION B
 STANDARDS (SECTION 7.15). ALL OTHER BATHROOMS IN THE
 UNIT MUST MEET THE USABLE BATHROOM REQUIREMENTS
 (SECTION 7.11), EXEMPTING MANEUVERING CLEARANCES, AND
 CLEAR FLOOR SPACE REQUIREMENTS AT FIXTURES.
  
 2. THE CITY OF WEST PALM BEACH BUILDING DEPARTMENT
 PROVIDES AN OPTION FOR CHANGING AN FHA COMPLIANCE
 STRUCTURE. THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE
 THAT THE PROPOSED BATHROOM DESIGN DOES NOT MEET THE
 FAIR HOUSING ACCESSIBILITY GUIDELINES REQUIREMENTS. THE
 OWNER AGREES TO REVERT THE UNIT BACK TO COMPLIANCE AT
 THE TIME OF SALE IF SO, REQUESTED BY THE BUYER. THIS
 WILL BE IN A LETTER-TYPE FORMAT SIGNED AND NOTARIZED BY
 THE OWNER. WE PROVIDE A SAMPLE LETTER, AND IT MUST BE
 SUBMITTED TO THE BUILDING DEPARTMENT OF THE CITY OF
 WPB. IF THIS OPTION IS CHOSEN, PLEASE SEND AN EMAIL TO
 [email protected], AND I WILL SEND A COPY OF THE FAIR
 HOUSING AFFIDAVIT.
  
 YOU MAY CONTACT ME IF YOU HAVE ANY QUESTIONS OR NEED
 HELP WITH THIS PROCESS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-09-22 Cont ID  
Sent By medwards Date 2021-09-22 Time 09:51 Rev Time 0.00
Received By medwards Date 2021-09-22 Time 09:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-19 Cont ID  
Sent By medwards Date 2021-08-19 Time 17:13 Rev Time 0.00
Received By medwards Date 2021-08-19 Time 17:13 Sent To  
Notes
***NONE***