Plan Review Details - Permit 21071625
Plan Review Stops For Permit 21071625
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2022-04-13 Cont ID  
Sent By cpuell Date 2022-04-13 Time 15:35 Rev Time 0.00
Received By cpuell Date 2022-04-13 Time 15:35 Sent To  
Notes
2022-04-13 15:39:31PRIMARY ADDRESS AGREED AS 1333 S FLAGLER DR, APPLICANT
 INFORMED THAT SEPARATE PCNS ARE REQUIRED FOR FOR EACH
 UNIT. THE FOLLOWING UNIT ADDRESSES HAVE BEEN APPROVED
 (WILL NOT BE ACTIVATED UNTIL THEY HAVE THEIR OWN PCNS):
  
 1333 S FLAGLER DR # 401
 1333 S FLAGLER DR # 402
 1333 S FLAGLER DR # 501
 1333 S FLAGLER DR # 502
 1333 S FLAGLER DR # 601
 1333 S FLAGLER DR # 602
 1333 S FLAGLER DR # 701
 1333 S FLAGLER DR # 702
 1333 S FLAGLER DR # 801
 1333 S FLAGLER DR # 802
 1333 S FLAGLER DR # 901
 1333 S FLAGLER DR # 902
 1333 S FLAGLER DR # 1001
 1333 S FLAGLER DR # 1002
 1333 S FLAGLER DR # 1101
 1333 S FLAGLER DR # 1102
 1333 S FLAGLER DR # 1201
 1333 S FLAGLER DR # 1202
 1333 S FLAGLER DR # 1401
 1333 S FLAGLER DR # 1402
 1333 S FLAGLER DR # 1501
 1333 S FLAGLER DR # 1502
 1333 S FLAGLER DR # 1601
 1333 S FLAGLER DR # 1602
 1333 S FLAGLER DR # 1701
 1333 S FLAGLER DR # 1702
 1333 S FLAGLER DR # 1801
 1333 S FLAGLER DR # 1802
 1333 S FLAGLER DR # 1901
 1333 S FLAGLER DR # 1902
 1333 S FLAGLER DR # 2001
 1333 S FLAGLER DR # 2002
 1333 S FLAGLER DR # 2101
 1333 S FLAGLER DR # 2102
 1333 S FLAGLER DR # 2201
 1333 S FLAGLER DR # 2202
 1333 S FLAGLER DR # 2301
 1333 S FLAGLER DR # 2302
 1333 S FLAGLER DR # 2401
 1333 S FLAGLER DR # 2402
 1333 S FLAGLER DR # 2501
  

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-03-10 Cont ID  
Sent By cpuell Date 2022-03-10 Time 15:41 Rev Time 0.00
Received By cpuell Date 2022-03-10 Time 15:41 Sent To  
Notes
2022-03-10 15:41:23PREVIOUS COMMENTS NOT ADDRESSED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-12-20 Cont ID  
Sent By cpuell Date 2021-12-20 Time 11:52 Rev Time 0.00
Received By cpuell Date 2021-12-20 Time 11:52 Sent To  
Notes
2021-12-20 11:53:42PLEASE COORDINATE WITH [email protected] FOR THE BUILDING
 AND THE APARTMENTS TO BE GIVEN ADDRESSES. PLEASE HAVE
 CONTACT [email protected] OR CALL 561-805-6659 TO ADDRESS
 THIS PROJECT.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 3 Status P Date 2022-06-16 Cont ID  
Sent By scwelter Date 2022-06-16 Time 10:58 Rev Time 0.00
Received By scwelter Date 2022-06-16 Time 10:59 Sent To  
Notes
***NONE***

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 2 Status P Date 2022-06-16 Cont ID  
Sent By scwelter Date 2022-04-04 Time 11:45 Rev Time 0.00
Received By scwelter Date 2022-06-16 Time 10:58 Sent To  
Notes
2022-04-04 11:47:22ART ASSESSMENT COMPLETED
 1% ESCROWED
 PUBLIC ART CONCEPTS/ARTWORKS APPROVED BY CITY
 COMMISSION
  
  
 REQUIRE BOND OR ESCROW - PUBLIC ART REVIEW SCHEDULED
 FOR APRIL 6TH 2022

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status F Date 2021-08-03 Cont ID  
Sent By scwelter Date 2021-08-03 Time 16:03 Rev Time 0.00
Received By scwelter Date 2021-08-03 Time 16:29 Sent To  
Notes
2021-08-03 16:28:48MASTER PERMIT FDN 20030982 -
 PERMIT - 21071625
 JULY 27, 2021 EMAILED STEVE DAVIS TWO ROADS DEVLOPMENT
 AND MIHAELA ZAHARESCU - PUBLIC ART ASSESSMENT
 APPLICATION AND ARTLIFE BOND FORM. ETA WEEK OF AUGUST
 1ST.
  
 AS DISCUSSED WITH BOTH STEVE AND MIHAELA PUBLIC ART
 REQUIREMENT IS "FAIL" UNTIL DOCUMENTS HAVE BEEN
 COMPLETED AND RETURNED.
  
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-09-29 Cont ID  
Sent By rmcphers Date 2022-09-29 Time 11:07 Rev Time 0.00
Received By rmcphers Date 2022-09-29 Time 11:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-08-19 Cont ID  
Sent By rmcphers Date 2022-08-19 Time 10:21 Rev Time 0.00
Received By rmcphers Date 2022-08-19 Time 10:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-06-07 Cont ID  
Sent By rmcphers Date 2022-06-07 Time 14:50 Rev Time 0.00
Received By rmcphers Date 2022-06-07 Time 14:43 Sent To  
Notes
2022-06-07 14:50:47NEW COMMERCIAL BUILDING R2
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) (THE ACOUSTICAL (STC AND IIC) AND FLAME SPREAD TEST
 REPORTS WERE NOT ADDED TO THE "DEFERRED SUBMITTAL "
 LIST ON DRAWING 00.200)
  
 PLEASE SHOW THE UNIT FLOOR FINISHES - FOR OTHER THAN
 CARPET AND PROVIDE THE FOLLOWING ACOUSTICAL TEST
 REPORTS - (CAN BE ADDED TO THE DEFERRED SUBMITTAL LIST)
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-28 Cont ID  
Sent By rmcphers Date 2022-03-28 Time 12:36 Rev Time 0.00
Received By rmcphers Date 2022-03-24 Time 10:18 Sent To  
Notes
2022-03-28 12:36:32NEW COMMERCIAL BUILDING R2
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) REVISED DRAWINGS LS1.108 AND LS1.107 - THE DOORS
 FROM THE UNITS TO THE CORRIDOR LOBBY AND ELEVATOR LOBBY
 DO NOT SHOW THE FIRE RATINGS.
  
 2) DRAWING A1.105 DIMENSIONS OF THE MASTER BATH TOILET
 ROOM IS SHOWN SMALLER THAN THE FHA DRAWING DIMENSIONS
 ON DRAWING A1.314
  
 3) PLEASE SHOW THE POOL BARRIER FOR PENTHOUSE POOL FBC
 454.2.17.1 (PRIVATE POOLS ALSO REQUIRE A POOL BARRIER)
  
 4) DRAWING LS1.102 AND LS1.103 ELEVATOR R2 SHOULD HAVE
 FIRE PROTECTION FROM THE CROSS CORRIDOR - UNLESS THE
 ELEVATORS ARE PRESSURIZED PER FBC 3006.3 (PLEASE
 PROVIDE A NOTE ON THE DRAWINGS IF THE ELEVATOR
 HOISTWAYS ARE PRESSURIZED)
  
 5) PLEASE MARK THE FULLY ACCESSIBLE FHA UNIT RESTROOMS
 ON DRAWING A1.314 AS "TYPE B" - PLEASE SHOW ON THE
 FLOOR PLANS THAT EACH UNIT BATHROOM COMPLIES WITH SPEC.
 A OR B - FBC FHA REQUIREMENT 7. (2)
  
 6) PLEASE SHOW THE UNIT FLOOR FINISHES - FOR OTHER THAN
 CARPET AND PROVIDE THE FOLLOWING ACOUSTICAL TEST
 REPORTS - (CAN BE ADDED TO THE DEFERRED SUBMITTAL LIST)
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 7) (CAN BE ADDED TO THE DEFERRED SUBMITTALS LIST)
 PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, EXTERIOR
 DOORS, ROOFING SYSTEMS, EXTERIOR LOUVERS, EXTERIOR
 CLADDING - ETC. - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD FBC WPB 107.3.4
  
 8) PLEASE PROVIDE A DEFERRED SUBMITTALS LIST ON THE
 DRAWINGS - - ITEMS SUCH AS WINDOW, DOOR AND ROOFING
 PRODUCT APPROVALS, FLOORING/UNDERLAYMENT ACOUSTICAL
 TEST REPORTS - ETC. MAY BE DEFERRED SUBMITTALS BY
 LISTING ITEMS TO BE DEFERRED ON THE CONSTRUCTION
 DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-06 Cont ID  
Sent By rmcphers Date 2022-01-06 Time 11:35 Rev Time 0.00
Received By rmcphers Date 2021-12-30 Time 16:41 Sent To  
Notes
2022-01-04 16:51:57NEW COMMERCIAL BUILDING R2
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A NOTE THAT THE FIRE SERVICE ACCESS
 ELEVATOR LOBBY DOORS COMPLY WITH FBC 3007.6.3 THE FIRE
 DOOR ASSEMBLY SHALL COMPLY WITH THE SMOKE AND DRAFT
 CONTROL DOOR ASSEMBLY REQUIREMENTS OF SECTION
 716.5.3.1, AND BE TESTED IN ACCORDANCE WITH UL 1784
 WITHOUT AN ARTIFICIAL BOTTOM SEAL.
  
 2) EXIT ACCESS DOORS FROM THE 2ND FLOOR POOL DECK
 SHOULD SWING IN THE DIRECTION OF EGRESS FBC 1010.1.2.1
  
 3) STAIR "C" - DOORS IN A SERIES = FBC 1010.1.8 DOOR
 ARRANGEMENT.
 SPACE BETWEEN TWO DOORS IN A SERIES SHALL BE 48 INCHES
 (1219 MM) MINIMUM PLUS THE WIDTH OF A DOOR SWINGING
 INTO THE SPACE.
  
 4) PLEASE SHOW THE POOL BARRIER FOR DECK LEVEL 2 POOL
 AND THE PENTHOUSE POOL FBC 454.1.3.1.9
  
 5) PLEASE SHOW THE SPA STEAM SHOWER AND SAUNA TO BE
 ACCESSIBLE PER - FBC FHA REQUIREMENT 2. (14)
  
 6) PLEASE SHOW THE MEN'S RESTROOM IN THE MEN'S SPA AREA
 TO BE ACCESSIBLE - FBC FHA REQUIREMENT 2. (11)
  
 7) PLEASE SHOW A CLEAR DOOR WIDTH OF 32" FOR WALK-IN
 CLOSETS, WALK-IN PANTRYS, WALK-IN WINE CELLARS, SPA
 STEAM SHOWER AND SPA SAUNA ETC. - FBC FHA REQUIREMENT
 3. (2)
  
 8) ALL FLOOR PLANS NEED TO SHOW THE DOOR DESIGNATION
 NUMBER PER THE DOOR SCHEDULE - SOME ARE SHOWN BUT NOT
 ALL - FBC WPB 107.2.1
  
 9) PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE TOILET IN
 THE TOILET ROOMS WHICH ARE IN THE MASTER BATHROOMS -
 FBC FHA REQUIREMENT 7. (2)
  
 10) PLEASE SHOW ON THE FLOOR PLANS THAT EACH UNIT
 BATHROOM COMPLIES WITH SPEC. A OR B - FBC FHA
 REQUIREMENT 7. (2)
  
 11) PLEASE SHOW THE UNIT FLOOR FINISHES - FOR OTHER
 THAN CARPET AND PROVIDE THE FOLLOWING ACOUSTICAL TEST
 REPORTS -
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 12) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, EXTERIOR
 DOORS, ROOFING SYSTEMS, EXTERIOR LOUVERS, EXTERIOR
 CLADDING - ETC. - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD FBC WPB 107.3.4
  
 13) ITEMS SUCH AS WINDOW, DOOR AND ROOFING PRODUCT
 APPROVALS, FLOORING/UNDERLAYMENT ACOUSTICAL TEST
 REPORTS - ETC. MAY BE DEFERRED SUBMITTALS BY LISTING
 ITEMS TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS -
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 14) A SEPARATE PERMIT SHALL BE REQUIRED FOR - EXISTING
 BUILDING DEMO., SITE PAVING, SITE WALKWAYS, SITE
 LIGHTING, WATER FALLS, FENCING, SIGNS ETC..
  
 15) TO VERIFY THAT THE BUILDING IS NOT IN A FLOOD ZONE
 - PLEASE SHOW THE BUILDING FOOT PRINT (B1 AND B2) ON A
 DRAWING WITH THE FLOOD ZONE - SUCH AS DRAWING C5.00

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-07-07 Cont ID  
Sent By jleahy Date 2022-07-07 Time 09:47 Rev Time 0.00
Received By jleahy Date 2022-07-07 Time 09:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2022-06-23 Cont ID  
Sent By jleahy Date 2022-06-23 Time 15:44 Rev Time 0.00
Received By jleahy Date 2022-06-23 Time 12:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-04-13 Cont ID  
Sent By jleahy Date 2022-04-13 Time 13:38 Rev Time 0.00
Received By jleahy Date 2022-04-12 Time 09:44 Sent To  
Notes
2022-04-13 15:58:24FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO MEANS TO BACK UP THE GENERATOR IS SHOWN ON THESE
 PLANS PER 700.3
  
 2) MAINS NOT LABLED AS 1 OF 6, 2 OF 6 AND SO FORTH.
 230.2.(E) PLEASE IDENTIFY ALL MAINS ON RISER DIAGRAM.
  
 3) LOAD CALCULATION ON DWELLING UNITS SHOW A VERY LIGHT
 LOAD FOR 4 ACS OR 4 HEAT STRIPS IN EACH UNIT. 215.5
  
 4) PANEL SCHEDULES TO BE MORE SPECIFIC. 408.4(A) A NOTE
 ON PLAN WILL BE GOOD.
  
 5) PANEL SCHEDULE NOT SHOWN FOR SUB PANELS (EMERGENCY)
 IN LIVING UNITS. 408.4(A)
  
 6) PLANS NEED TO NOTE SOURCE OF POWER IN ALL PANELS IN
 ALL UNITS AND OTHER SUB PANELS PER 408.4(B)
  
 7) MAINS 1200 AMPERES OR MORE SHALL BE INSTALLED PER
 240.87 FOR ARC ENERGY REDUCTION. 240.87
  
 8) FIRE PUMP WIRING IS INSTALLED WITH THE OTHER
 EMERGENCY WIRING, BUT 695.6(A)(2)(A) STATES ALL FIRE
 PUMP WIRING TO
 BE KEPT ENTIRELY INDEPENDENT OF OTHER WIRING?
  
 9) FIRE PUMP HAS A 450A BREAKER OR FUSE AHEAD OF THE
 CONTROLLER? THE SIZE WAS BASED ON WHAT? 695.4?

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-01-04 Cont ID  
Sent By jleahy Date 2022-01-04 Time 11:50 Rev Time 0.00
Received By jleahy Date 2022-01-03 Time 08:41 Sent To  
Notes
2022-01-04 12:46:45ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 A COMPLETE SET OF PLANS HAS NOT BEEN SUBMITTED,
  
 MISSING SHEETS INCLUDE THE FOLLOWING:
 E4.03, E5.00, E5.01, E5.02, E5.03, E5.04
 E6.00, E6.01, E6.02, E6.03, E6.04, E7.00
 E7.01, E7.02, E7.03, E7.04, E7.05, E7.06
 E2.105S
  
 FOLLOWING SHEETS INCLUDED IN SET BUT NOT LISTED ON PLAN
 INDEX:
  
 E3.00A, E3.207, E3.208, E3.209, E3.210
 E3.300, E3.301, E3.302, E3.303, E3.304, E3.305
  
 MY PLAN REVIEW WILL BE COMPLETE WHEN A FULL SET OF
 PLANS HAS BEEN SUBMITTED.
  
 THE FOLLOWING SYSTEMS ARE REQUIRED TO BE ON SEPARATE
 PERMITS:
 FIRE ALARM, GENERATOR, POOL, LOW VOLTAGE PHONE AND
 DATA, CCTV, ACCESS CONTROL, SITE LIGHTING,
 LIGHTING PROTECTION.

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2022-08-12 Cont ID  
Sent By rrossano Date 2022-08-12 Time   Rev Time 0.00
Received By rrossano Date 2022-08-12 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2022-05-23 Cont ID  
Sent By rrossano Date 2022-05-23 Time   Rev Time 0.00
Received By rrossano Date 2022-05-23 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2022-03-14 Cont ID  
Sent By rrossano Date 2022-03-14 Time   Rev Time 0.00
Received By rrossano Date 2022-03-14 Time   Sent To  
Notes
2022-03-14 13:49:20UNDER FORMAL ENGINEERING SUBMITTAL REVIEW E20080015.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-12-20 Cont ID  
Sent By rrossano Date 2021-12-20 Time   Rev Time  
Received By rrossano Date 2021-12-20 Time   Sent To  
Notes
2021-12-20 14:24:08PROJECT IS UNDER FORMAL ENGINEERING SUBMITTAL REVIEW.
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORDINATOR,
 CITY OF WPB ENGINEERING SERVICES DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING-
 STANDARDS-DETAILS
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-06-02 Cont ID  
Sent By pleduc Date 2022-06-02 Time   Rev Time 0.00
Received By pleduc Date 2022-05-24 Time 16:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-03-22 Cont ID  
Sent By pleduc Date 2022-03-22 Time   Rev Time 0.00
Received By pleduc Date 2022-03-16 Time 15:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-01-03 Cont ID  
Sent By pleduc Date 2022-01-03 Time   Rev Time 0.00
Received By pleduc Date 2021-12-27 Time 13:36 Sent To  
Notes
2021-12-27 13:50:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET LS1 - 102 - THE OUTDOOR AMENITY DECK INDICATES
 A SET OF DOUBLE DOORS OUTSWINGING ALONG THE EGRESS
 ROUTE. THESE DOUBLE DOORS ARE REQUIRED TO SWING IN THE
 DIRECTION OF EGRESS.
  
 NFPA 101, CH 7 MEANS OF EGRESS
  
 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE OF
 THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN
 THE DIRECTION
 OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR MORE,
 EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY
 7.2.4.3.8.1
 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH
 CARE OCCUPANCIES,
 AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS THE
 DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS DIRECTLY
 INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD
 CONTENTS AREA
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 2) THERE ARE INDICATIONS OF AN ELECTIRC FIRE PUMP AND A
 GENERATOR; HOWEVER, THERE IS NO INDICATON THAT THE
 ELECTRIC FIRE PUMP WILL BE POWERED BY THE GENERATOR IN
 THE EVENT OF LOSS OF POWER.
  
 PER NFPA 20
  
 9.3 ALTERNATE POWER.
 9.3.1 EXCEPT FOR AN ARRANGEMENT DESCRIBED IN 9.3.3, AT
 LEAST
 ONE ALTERNATE SOURCE OF POWER SHALL BE PROVIDED WHERE
 THE
 HEIGHT OF THE STRUCTURE IS BEYOND THE PUMPING CAPACITY
 OF THE
 FIRE DEPARTMENT APPARATUS.
 9.3.2* OTHER SOURCES. EXCEPT FOR AN ARRANGEMENT
 DESCRIBED IN
 9.3.3, AT LEAST ONE ALTERNATE SOURCE OF POWER SHALL BE
 PROVIDED
 WHERE THE NORMAL SOURCE IS NOT RELIABLE.
 9.3.3 AN ALTERNATE SOURCE OF POWER FOR THE PRIMARY FIRE
 PUMP
 SHALL NOT BE REQUIRED WHERE A BACKUP ENGINE-DRIVEN FIRE
 PUMP,
 BACKUP STEAM TURBINE-DRIVEN FIRE PUMP, OR BACKUP
 ELECTRIC
 MOTOR?DRIVEN FIRE PUMP WITH INDEPENDENT POWER SOURCE
 MEETING
 9.2.2 IS INSTALLED IN ACCORDANCE WITH THIS STANDARD.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKOWLEDGEMENT TO
 COMPLY ON SHEET FP 11.
  
  
  
 3) THERE ARE NO INDICATIONS OF A BDA SYSTEM
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
  
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
  
 PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC
 SAFETY RADIO SYSTEMS MANAGER, AS OUR RADIOS OPERATE ON
 THEIR SYSTEM FOR DETAILED RADIO FREQUENCY AND
 INSTALLATION INSTRUCTIONS.
  
 THERE IS NO WAY TO DETERMINE IF YOUR BUILDING WOULD
 NEED IT OR NOT WITHOUT PROPER TESTING.
  
 SHOULD YOUR BUILDING NOT PASS THE TESTING/SURVEY, AN
 AMPLIFICATION SYSTEM WOULD BE REQUIRED.
  
 SHOULD YOUR BUILDING PASS THE TESTING/SURVEY I WOULD
 COME IN WITH OUR PORTABLE RADIOS AND CONDUCT AN
 OPERATIONAL TEST TO CONFIRM. IF THE PORTABLE RADIO TEST
 FAILS AN AMPLIFICATION SYSTEM IS REQUIRED.
  
 THE OWNER/CONTRACTOR WOULD BE RESPONSIBLE TO CONDUCT
 THE TESTING/SURVEY BY A QUALIFIED THIRD PARTY.
  
 A BDA PERMIT IS REQUIRED SEPARATE FROM ANY OTHER
 PERMIT.
  
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKOWLEDGEMENT TO
 COMPLY ON SHEET LS 100.
  
  
  
 4) THERE ARE INDICATIONS OF FIRE ALARM DEVICES ON THE
 ELECTRICAL PLAN SHEETS.
  
 ALL FIRE ALARM WORK SHALL BE INSTALLED UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKOWLEDGEMENT TO
 COMPLY ON SHEETS E0 .001 & LS 100.
  
  
  
  
 5) THERE ARE INDICATIONS ON THE CIVIL SHEETS OF
 UNDEGROUND FIRE LINES, INCLUDING THE FDC & DDCV.
  
 ALL FIRE LINE UNDERGROUND WORK INCLUDING THE FDC & DDCV
 SHALL INSTALLED PER NFPA 24 AND UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS .
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT OF
 SHEET C.
  
  
  
 6) THERE ARE INDICATIONS OF ELEVATOR FOYERS/LOBBIES TO
 INDIVIDUAL UNITS WITH NO CLEAR EXIT ACCESS TO AN EXIT.
  
 PER NFPA 101
  
 7.2.1.6.3 ELEVATOR LOBBY EXIT ACCESS DOOR ASSEMBLIES
 LOCKING.
 WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR
 ASSEMBLIES SEPARATING
 THE ELEVATOR LOBBY FROM THE EXIT ACCESS REQUIRED BY
 7.4.1.6.1 SHALL BE PERMITTED
 TO BE ELECTRICALLY LOCKED, PROVIDED THAT ALL THE
 FOLLOWING CRITERIA ARE MET:
 (1) THE ELECTRICAL LOCKING HARDWARE IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
 (2) THE BUILDING IS PROTECTED THROUGHOUT BY A FIRE
 ALARM SYSTEM IN
 ACCORDANCE WITH SECTION 9.6.
 (3) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 9.7.
 (4) WATERFLOW IN THE SPRINKLER SYSTEM REQUIRED BY
 7.2.1.6.3(3) IS
 ARRANGED TO INITIATE THE BUILDING FIRE ALARM SYSTEM.
 (5) THE ELEVATOR LOBBY IS PROTECTED BY AN APPROVED,
 SUPERVISED SMOKE
 DETECTION SYSTEM IN ACCORDANCE WITH SECTION 9.6.
 (6) DETECTION OF SMOKE BY THE DETECTION SYSTEM REQUIRED
 BY
 7.2.1.6.3(5) IS ARRANGED TO INITIATE THE BUILDING FIRE
 ALARM SYSTEM
 AND NOTIFY BUILDING OCCUPANTS.
 (7) INITIATION OF THE BUILDING FIRE ALARM SYSTEM BY
 OTHER THAN MANUAL
 FIRE ALARM BOXES UNLOCKS THE ELECTRICAL LOCKS ON THE
 ELEVATOR LOBBY
 DOOR ASSEMBLY.
 (8) LOSS OF POWER TO THE ELEVATOR LOBBY ELECTRICAL LOCK
 SYSTEM UNLOCKS
 THE ELECTRICAL LOCKS ON THE ELEVATOR LOBBY DOOR
 ASSEMBLIES.
 (9) ONCE UNLOCKED, THE ELEVATOR LOBBY DOOR ASSEMBLIES
 REMAIN ELECTRICALLY
 UNLOCKED UNTIL THE BUILDING FIRE ALARM SYSTEM HAS BEEN
 MANUALLY RESET.
 (10) WHERE THE ELEVATOR LOBBY DOOR ASSEMBLIES REMAIN
 MECHANICALLY
 LATCHED AFTER BEING ELECTRICALLY UNLOCKED,
 LATCH-RELEASING HARDWARE
 IN ACCORDANCE WITH 7.2.1.5.10 IS AFFIXED TO THE DOOR
 LEAVES.
 (11) A TWO-WAY COMMUNICATION SYSTEM IS PROVIDED FOR
 COMMUNICATION
 BETWEEN THE ELEVATOR LOBBY AND A CENTRAL CONTROL POINT
 THAT
 IS CONSTANTLY STAFFED.
 (12) THE CENTRAL CONTROL POINT STAFF REQUIRED BY
 7.2.1.6.3 IS CAPABLE,
 TRAINED, AND AUTHORIZED TO PROVIDE EMERGENCY
 ASSISTANCE.
 (13) THE PROVISIONS OF 7.2.1.6.1 FOR DELAYED-EGRESS
 ELECTRICAL LOCKING
 SYSTEMS ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR
 ASSEMBLIES.
 (14)* THE PROVISIONS OF 7.2.1.6.2 FOR SENSOR-RELEASE OF
 ELECTRICAL LOCKING
 SYSTEMS ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR
 ASSEMBLIES.
  
 PLEASE REVIEW AND PROVIDE A DETAILED SEQUENCE OF
 OPERATION/USE FOR EACH OF THE VARIOUS FOYER/SECONDARY
 VESTIBULE FLOOR PLANS THAT COMPLIES WITH THE ABOVE
 CODE.
  
  
 7) THERE IS NO RATIONAL ANALYSIS DOCUMENT THAT COULD BE
 REVIEWED FOR THE SMOKE CONTROL SYSTEM(S) APPLICABLE
 SEQUENCE OF OPERATION.
  
 SHEET M 8 WAS REVIEWED; HOWEVER, THE INFORMATION
 PROVIDED ON THAT SHEET DOES NOT PROVIDE CLEAR
 INDICATIONS IN A LOGICAL ORDER.
  
 PLEASE REVIEW AND PROVIDE A DETAILED DOCUMENT FOR
 REVIEW.
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-03-31 Cont ID  
Sent By lcrespo Date 2022-03-31 Time 09:31 Rev Time 0.00
Received By lcrespo Date 2022-03-31 Time 09:31 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-01-24 Cont ID  
Sent By lcrespo Date 2022-01-24 Time 12:23 Rev Time 0.00
Received By lcrespo Date 2022-01-24 Time 12:23 Sent To  
Notes
2022-01-24 12:23:5901/24/22 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P5.108 AND P5.109;
  
 A. ON THE CODE NOTES AND 2ND FLOOR NOTE, IT SAYS 2017
 FLORIDA FUEL GAS CODE, AND THE CURRENT IS 2020 FG 7 TH
 EDITION PER THE WPB AMENDMENTS TO FBC 102.3 APPLICATION
 OF REFERENCES.
  
 B. FOR LETTERS A, C, AND D, IT SAYS P5.09 AND NO SUCH
 PAGE. WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 C. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT
 MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202)
 GD, ACCESS.
  
 D. WOULD YOU PLEASE A PLUMBING PLAN INCLUDING A GAS
 ISOMETRIC DRAWING PER THE WPB AMEND TO FBC
 107.3.5.1.3(13).
  
 E. WOULD YOU PLEASE SUBMIT THE LENGTH OF ALL PIPE CUT
 SECTIONS ON THE ISOMETRIC DRAWING PER 2020 FBC FG SECS.
 402.4.1, 402.4.2.
  
 F. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR
 NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 G. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2020 FBC FG
 SEC. 409.4.
  
 H. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC FG SECS.
 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1) THROUGH
 402.4 (37).
  
 I. WOULD YOU PLEASE SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY (GAS METER / MP REGULATOR / LP TANK) TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM PER
 THE 2020 FBC FG SEC. 402.4.1.
  
 J. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC FG SEC.
 305.1.
  
 K. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020
 FBC FG SECS. 402.2 AND 301.3.
  
 L. WOULD YOU PLEASE SHOW THE TYPE OF PIPE MATERIAL
 BEING INSTALLED FOR THE GRILL AND THE PIPE SIZE PER THE
 WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 M. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC FG
 SEC. 410.1.
  
 N. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC FG SEC
 410.2.
  
 O. WOULD YOU, PLEASE LABEL THE SHUTOFF VALVE ON GAS
 ISOMERIC PER THE 2020 FBC FG SEC. 409.5.
  
 P. WOULD YOU PLEASE SHOW DRIP LEG ON EQUIPMENT
 INSTALLED, EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD
 GRILLS PER THE 2020 FBC FG 408.2.
  
 Q. WOULD YOU PLEASE SUBMIT COMBUSTION AIR CALCULATIONS
 FOR THE GAS APPLIANCES ON 2ND, GROUND, AND B1 LEVEL.
 WHERE DOES THE BUILDING?S MECHANICAL VENTILATION SYSTEM
 PROVIDE COMBUSTION AIR? THE SYSTEM SHALL PROVIDE THE
 SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR PER THE 2020 FBC FG SEC.
 304.9.3. COMBINED COMBUSTION AIR AND VENTILATION AIR
 SYSTEM.
  
 R. WOULD YOU PLEASE SUBMIT CALCULATIONS FOR COMBUSTION
 AIR PER THE 2020 FBC FG SEC. 304.1, 614.5 (CLOTHES
 DRYERS),
  
 S. THE CITY OF WEST PALM BEACH WILL REQUIRE THE GAS
 SYSTEM TO BE PURGED AND ADMINISTERED BY A CITY
 INSPECTOR. BEFORE DOING THIS PROCESS, PLEASE HAVE A
 DESCRIPTION OF HOW THE PURGE WILL TAKE PLACE AND WHEN
 SUBMITTED TO THE CHIEF PLUMBING INSPECTOR IN ADVANCE.
 WOULD YOU PLEASE CALL 561-805-6692 FOR FURTHER
 CLARIFICATION?
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-10-14 Cont ID  
Sent By lmarchan Date 2022-10-14 Time 16:44 Rev Time 0.00
Received By lmarchan Date 2022-09-21 Time 06:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-09-16 Cont ID  
Sent By medwards Date 2022-09-16 Time 13:29 Rev Time 0.00
Received By shill Date 2022-08-08 Time 08:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-25 Cont ID  
Sent By shill Date 2022-07-25 Time 17:58 Rev Time 0.00
Received By shill Date 2022-05-22 Time 13:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-18 Cont ID  
Sent By aoliver Date 2022-05-18 Time 06:34 Rev Time 0.00
Received By aoliver Date 2022-03-10 Time 10:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-10 Cont ID  
Sent By lmarchan Date 2022-02-10 Time 07:51 Rev Time 0.00
Received By lmarchan Date 2021-12-17 Time 15:57 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-10-17 Cont ID  
Sent By lmarchan Date 2022-10-17 Time 12:15 Rev Time 0.00
Received By lmarchan Date 2022-08-18 Time 16:05 Sent To  
Notes
2022-10-14 16:45:46RECEIPT MU-2022-039104 - $386,098.73 PAID
2022-08-18 16:06:238/18/22 EMAILED IMPACT FOR REVIEW-AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-01-06 Cont ID  
Sent By rmcphers Date 2022-01-06 Time 10:45 Rev Time 0.00
Received By rmcphers Date 2022-01-06 Time 10:45 Sent To  
Notes
2022-01-06 10:45:57PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2022-09-29 Cont ID  
Sent By medwards Date 2022-09-29 Time 16:16 Rev Time 0.00
Received By medwards Date 2022-09-29 Time 16:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2022-08-22 Cont ID  
Sent By medwards Date 2022-08-22 Time 09:00 Rev Time 0.00
Received By medwards Date 2022-08-22 Time 09:00 Sent To  
Notes
2022-08-22 09:01:074TH REVIEW FMC
 PERMIT: 21071625
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 THANK YOU FOR THE COMMENTS SUBMITTED IN THIS LATEST
 REVIEW CYCLE. I WILL TRY TO EXPLAIN IN THIS RESPONSE
 WHY YOU MUST COMPLY WITH THE CODE SECTION 403.3.1.1 AND
 TABLE 403.3.1.1 OR PROVIDE APPROVED (BY THE CODE
 OFFICIAL) STATISTICAL DATA. A LETTER FROM THE ENGINEER
 AND THE ARCHITECT STATING THAT THESE AREAS ARE PRIVATE
 IS NOT ACCEPTABLE TO THIS REVIEWER AS NEITHER OF YOU
 HAVE CONTROL OF THE USE OF THESE AREAS.
 THIS BUILDING IS A 25 STORY BUILDING OF CONDO?S TO BE
 SOLD. THE OWNER?S OF THESE CONDO?S WILL HAVE FRIENDS
 AND FAMILY OVER. THIS WILL EFFECT THE OCCUPANT COUNT OF
 THESE AREAS. IN THE ENGINEER?S LETTER THE FURNITURE IS
 BEING CALLED PERMANENT. I SEE NO WAY OF CALLING THE
 FURNITURE PERMANENT AS IT IS NOT SECURED IN PLACE AND
 COULD BE MOVED OR ADDED TO. AGAIN THE ARCHITECT OR
 ENGINEER HAS NO CONTROL OF THIS BUILDING AND HOW THE
 FURNITURE WILL BE MAINTAINED.
 THE LOUNGE AREAS SHOW FURNITURE DESIGNS MUCH LIKE YOU
 COULD FIND IN A RESIDENCE. THIS TYPE OF FURNITURE DOES
 WEAR OUT AND WOULD NEED TO BE REPLACED AT SOME POINT.
 THERE IS ROOM IN EACH OF THESE AREAS TO INSTALL MORE
 FURNITURE, MORE FURNITURE EQUALS MORE PEOPLE. THERE ARE
 AREAS IN EACH SPACE WHERE OCCUPANTS COULD STAND.
 AS WE KNOW THE CODE COMMENTARY IS NOT ENFORCEABLE BUT
 ONLY AN EXPLANATION AS TO THE INTENT OF THE CODE. I
 HAVE QUOTED THE 2018 IMC COMMENTARY BELOW THAT STATES
 YOU MUST MEET MINIMUMS TO JUSTIFY NOT USING TABLE
 403.3.1.1, IN THIS LATEST REVIEW CYCLE YOU HAVE NOT
 DONE SO.
  
 IMC CODE COMMENTARY:
 ?THE EXCEPTION ALLOWS THE OCCUPANT LOAD FOR VENTILATION
 TO BE BASED ON THE ACTUAL OCCUPANT FOR WHICH THE SPACE
 IS DESIGNED WHERE IT CAN BE SHOWN TO THE CODE
 OFFICIAL?S SATISFACTION THAT THE OCCUPANT LOAD IS
 REALISTIC. THE OCCUPANT DENSITY ENTRIES IN TABLE
 403.3.1.1 ARE BASED ON EMPIRICAL DATA AND ARE
 REASONABLY ACCURATE FOR THE TYPICAL CASES IN EACH TYPE
 OF OCCUPANCY. SUFFICIENT DOCUMENTATION MUST BE
 SUBMITTED TO THE CODE OFFICIAL TO JUSTIFY ANY DEVIATION
 FROM THE PRESCRIBED OCCUPANT DENSITIES.
  
 2) SHEET M2.102D: THE ADDED EXHAUST FAN EF-8 IN THE
 WARMING KITCHEN, THE TERMINATION LOCATION MUST BE A
 MINIMUM OF 10 FEET FROM THE OUTDOOR AIR INTAKE. FMC
 501.3.1 NUMBER 3
  
 1) PLEASE SEE THE 2ND CYCLE REVIEW COMMENT BELOW:
  
 1) PLEASE USE FMC 403.3.1.1 3RD SENTENCE AND TABLE
 403.3.1.1 TO DETERMINE THE OCCUPANCY CLASSIFICATION
 USED TO PROVIDE THE OUTDOOR AIR FOR EACH USE OF SPACE.
 THE ARCHITECTS EGRESS OCCUPANT COUNT CANNOT BE USED TO
 DETERMINE THE OUTDOOR AIR NEEDED FOR THE OCCUPANCY
 CLASSIFICATION. PLEASE NAME EACH SPACE PER THE CLOSEST
 OCCUPANCY CLASSIFICATION OF TABLE 403.3.1.1 AND PROVIDE
 THE OUTDOOR AIR CALCULATIONS USING THE TABLE 403.3.1.1
 AND NOT THE ARCHITECTS EGRESS OCCUPANT COUNTS. EXAMPLE:
 BUSINESS/MEETING COULD BE A CONFERENCE ROOM WHICH IF
 USING THE CALCULATIONS IN TABLE 403.3.1.1 WOULD REQUIRE
 149 CFM OF OUTDOOR AIR.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-06-01 Cont ID  
Sent By medwards Date 2022-06-01 Time 16:54 Rev Time 0.00
Received By medwards Date 2022-06-01 Time 16:54 Sent To  
Notes
2022-06-01 17:15:041) IF THE ENGINEER OF RECORD WOULD LIKE TO USE THE
 EXCEPTION TO FMC 403.3.1.1 THEY WOULD NEED TO SUBMIT
 THE STATISTICAL DATA TO THE BUILDING OFFICIAL TO
 APPROVE OR DENY.
  
 2) THE TREATMENT ROOM, BARBER AREA WILL NEED 61 CFM?S
 OF EXHAUST. FMC TABLE 403.3.1.1
  
 3) THE DRESSING ROOMS WILL REQUIRE EXHAUST AIR. THE 477
 SQ FT WILL NEED 119 CFM?S AND THE 328 SQ. FT. WILL NEED
 82 CFM?S FMC TABLE 403.3.1.1
  
 4) THE CHANGING ROOMS ON SHEET M2.103D WILL NEED
 EXHAUST. THE 30 SF CHANGING ROOM WILL REQUIRE 8 CFM?S
 EXHAUST AND THE 27SF CHANGING ROOM WILL REQUIRE 7 CFM?S
 EXHAUST. FMC TABLE 403.3.1.1
  
 5) WHY IS THE DINING ROOM BEING CLASSIFIED AS A
 LOBBY/PREFUNCTION? THE DINING ROOM WILL REQUIRE 723
 CFM?S OF OUTDOOR AIR.
  
 6) THE WARMING KITCHEN/BREAKROOM WILL REQUIRE OUTDOOR
 AIR AND EXHAUST.
  
 7) SHEET M2.101D: THE OFFICE AND MAILROOM WILL REQUIRE
 OUTDOOR AIR BUT THE FCU-2 SUPPLYING THIS AREA DOES NOT
 SHOW AN OUTDOOR AIR DUCT AT THE RETURN.
  
 8) THE MEN?S AND WOMEN?S SPAS WILL REQUIRE OUTDOOR AIR.
 FMC 403.3.1.1
 VENTILATION RATES FOR OCCUPANCIES NOT REPRESENTED IN
 TABLE 403.3.1.1 SHALL BE THOSE FOR A LISTED OCCUPANCY
 CLASSIFICATION THAT IS MOST SIMILAR IN TERMS OF
 OCCUPANT DENSITY, ACTIVITIES AND BUILDING
 CONSTRUCTION; OR SHALL BE DETERMINED BY AN APPROVED
 ENGINEERING ANALYSIS.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-04-04 Cont ID  
Sent By medwards Date 2022-04-04 Time 11:03 Rev Time 0.00
Received By medwards Date 2022-04-04 Time 11:03 Sent To  
Notes
2022-04-04 11:03:412ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21071625
  
 CODES IN EFFECT:
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) PLEASE USE FMC 403.3.1.1 3RD SENTENCE AND TABLE
 403.3.1.1 TO DETERMINE THE OCCUPANCY CLASSIFICATION
 USED TO PROVIDE THE OUTDOOR AIR FOR EACH USE OF SPACE.
 THE ARCHITECTS EGRESS OCCUPANT COUNT CANNOT BE USED TO
 DETERMINE THE OUTDOOR AIR NEEDED FOR THE OCCUPANCY
 CLASSIFICATION. PLEASE NAME EACH SPACE PER THE CLOSEST
 OCCUPANCY CLASSIFICATION OF TABLE 403.3.1.1 AND PROVIDE
 THE OUTDOOR AIR CALCULATIONS USING THE TABLE 403.3.1.1
 AND NOT THE ARCHITECT?S EGRESS OCCUPANT COUNTS.
 EXAMPLE: BUSINESS/MEETING COULD BE A CONFERENCE ROOM
 WHICH IF USING THE CALCULATIONS IN TABLE 403.3.1.1
 WOULD REQUIRE 149 CFM OF OUTDOOR AIR.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-01-10 Cont ID  
Sent By medwards Date 2022-01-10 Time 15:22 Rev Time 0.00
Received By medwards Date 2022-01-10 Time 09:05 Sent To  
Notes
2022-01-10 15:22:181ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21071625
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A NOTE ON THE DRAWINGS STATING THAT THE
 GENERATOR WILL REQUIRE A SEPARATE PERMIT AND PLAN
 REVIEW AS IT WILL NOT BE REVIEWED UNDER THIS PERMIT.
 FBC 107.2.1
  
 2) PLEASE SHOW THAT THE CARBON MONOXIDE AND NITROGEN
 DIOXIDE DETECTORS ARE SEPARATE PIECES OF EQUIPMENT AND
 SHOW THE MOUNTING HEIGHTS OF EACH PIECE OF EQUIPMENT
 ACCORDING TO FBC M 404.1. PLEASE PROVIDE A DRAWING
 SHOWING THE LOCATIONS OF EACH CARBON MONOXIDE AND
 NITROGEN DIOXIDE LOCATION PER THE MANUFACTURER?S
 INSTRUCTIONS. FBC 107.2.1
  
 3) SHEET LS1.100 INDICATES FIRE RATED WALLS IN SEVERAL
 LOCATIONS ON BOTH LEVELS OF THE PARKING GARAGE. PLEASE
 SHOW THE REQUIRED PENETRATION PROTECTION AT ALL
 DUCTWORK PENETRATING THESE RATED WALLS. FBC M 607
  
 4) SHEET M2.1B1D: PLEASE SHOW HOW MANY DRYERS ARE IN
 THE LAUNDRY ROOM, ALSO PLEASE PROVIDE A DETAIL OF THE
 DRYER DUCT TERMINATION LOCATION. FBC 504
  
 5) SHEET M2.1B1D: THE DRYER DUCTS ARE PENETRATING RATED
 WALLS, PLEASE PROVIDE PROTECTION FOR THESE
 PENETRATIONS. FBC M 607
  
 6) THE MAKEUP AIR FOR THE LAUNDRY ROOM, STORAGE AND
 EQUIPMENT ROOM CANNOT BE TAKEN FROM THE GARAGE.
  
 7) SHEET M2.1B1D: NOTE 4 OF THE CODE NOTES INDICATES A
 MAKEUP AIR PLENUM ON THE ARCHITECTURAL DRAWINGS, PLEASE
 REFERENCE THE SHEET NUMBER OF THE ARCHITECTURAL DRAWING
 THAT HAS THIS INFORMATION.
  
 8) SHEET M2.1B1P: PLEASE PROVIDE PIPE SIZES FOR THE
 PIPING ON THE PIPING PLAN.
  
 9) PLEASE SHOW THE REQUIRED FIRE DAMPERS ON THE
 DRAWINGS WHERE THE DUCTWORK IS PENETRATING ALL RATED
 WALLS. FBC M607
  
 10) PLEASE SHOW OUTDOOR AIR DAMPERS IN THE OUTDOOR AIR
 DUCTWORK.
  
 11) THE PFSF?S DUCTWORK ARE PENETRATING A RATED WALL,
 PLEASE PROVIDE A DETAIL OF HOW THIS PENETRATION WILL BE
 PROTECTED. FBC M 607
  
 12) PLEASE SHOW THE SMOKE DETECTORS INSIDE THE SUPPLY
 DUCTWORK ACCORDING TO FBC M 606.2.2
  
 13) PLEASE REVISIT THE OUTDOOR AIR CALCULATIONS
 PROVIDED AS IT APPEARS THAT SOME HAVE A LOWER OCCUPANT
 COUNT THAN WHAT FBC M 403.3.1.1 AND TABLE 403.3.1.1
 ALLOWS.
  
 14) SHEET M6.101: THE AIR DEVICE SCHEDULE STOPS AT
 DESIG. M, PLEASE SHOW INFORMATION FOR THE DESIG. P. FBC
 107.2.1
  
 15) PLEASE SHOW THE CONDENSATE PIPING MATERIAL, SIZING
 AND TERMINATION LOCATION. FBC M 307
  
 16) SHEET M5.101: PLEASE IDENTIFY AND INCLUDE
 SPECIFICATIONS FOR THE EXHAUST FANS FOR THE DRYER
 EXHAUST.
  
 17) PLEASE PROVIDE SPECIFICATIONS FOR THE LAUNDRY
 DRYERS INCLUDING THE DUCT LENGTH. FBC M 504
  
 18) PLEASE PROVIDE A DETAIL SHOWING THE DUCT SUPPORTS
 IN THE SHAFTS. FBC M 305
  
 19) SHEET M5.103: PLEASE SHOW THE SPF FOR STAIR B
 PRESSURIZATION ON THIS RISER DETAILS.
  
 20) SHEET M8.101: THE GARAGE CARBON MONOXIDE/NITROGEN
 DIOXIDE SUPPLY/EXHAUST FAN CONTROL SEQUENCE MUST MATCH
 FBC M 404.1- 1 AND 2
  
 21) SHEET M2.101D: PLEASE SHOW THAT THE EF-3 IS A
 CORROSION RESISTANT FAN BECAUSE OF IT?S LOCATION IN THE
 POOL EQUIPMENT ROOM.
  
 22) PLEASE SHOW THAT ALL EXHAUST TERMINATION LOCATIONS
 MEET THE 3 FOOT CLEARANCE FROM OPERABLE OPENINGS INTO
 THE BUILDING. FBC M 501.3
  
 23) FBC M2.125D: PLEASE SIZE THE DUCTWORK ON THE ROOF
 FROM THE SHAFT TO THE DOAS-1 INCLUDING THE DUCT SIZE TO
 THE CSEF-1. FBC 107.2.1
  
 24) PLEASE SHOW DUCT SIZES FOR THE DUCT BOXES LEAVING
 THE FCU?S. FBC 107.2.1
  
 25) COMMON EXHAUST SYSTEM FOR CLOTHES DRYERS LOCATED IN
 MULTISTORY STRUCTURES MUST MEET THE REQUIREMENTS OF
 504.10 1-12.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-05-24 Cont ID  
Sent By rwbrown Date 2022-05-24 Time 13:22 Rev Time 0.00
Received By rwbrown Date 2022-05-24 Time 12:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-03-31 Cont ID  
Sent By lcrespo Date 2022-03-31 Time 09:31 Rev Time 0.00
Received By lcrespo Date 2022-03-16 Time 14:25 Sent To  
Notes
2022-03-31 09:12:3803/31/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE NOW,
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET 00.002; PAGES ARE MISSING FROM THE PLUMBING
 INDEX AS FOLLOWS;
  
 P2.126
 P3.105
 P3.206
 P3.207
 P3.208
 P3.209
 P3.210
 P3.300
 P3.301
 P3.302
 P3.303
 P3.304
 NOT BEEN UPDATED
  
 2. DONE
  
 3. DONE
  
 4. ON SHEET 00.205;
  
 A. SECOND REQUEST, FOR THE COMMENT, SHOWS NUMBER #1 BUT
 NO INFORMATION ON THE 34??THE FHA NOTES TALK ABOUT
 SPECIFICATION B AND NO MENTION ON THE LAV TO BE AT 34"
 PER 7.52 OF THE FHA DESIGN MANUAL.
  
 B. SECOND REQUEST, FOR THE COMMENT, IT SHOWS NUMBER #8
 BUT NO INFORMATION ON THE NOTE?THE PENTHOUSE IS A
 FUTURE BUILD-OUT AND, IN THIS WAY, ESTABLISHED IN THE
 BUILDING DEPARTMENT THAT THE POWDER ROOM IS FOR THE
 CONSTRUCTION WORKER. WOULD YOU PLEASE ADD A NOTE OF
 THIS ON THE PAGE UNDER FAIR HOUSING ITEM #8 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 5. DONE
  
 6. ON SHEET 00.207;
  
 A. DONE
  
 B. DONE
  
 C. DONE
  
 D. SECOND REQUEST, THE DRAWING IS CORRECT, BUT THE
 VERBIAGE IS NOT? ON NUMBER 77, IT REFERS TO THE
 DISPENSER BEING 12 AND SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER PER THE 2017 FBC ACC
 SEC. 604.7. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 E. DONE
  
 F. DONE
  
 G. DONE
  
 I. DONE
  
 7. ON SHEET 00.210;
  
 A. UNDER GENERAL REQUIREMENTS, IT HAS BOTH THE
 GUIDELINES AND THE DESIGN MANUAL, TWO DIFFERENT SAFE
 HARBORS, AND ONLY ONE SHOULD BE NOTED. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS? THERE ARE EIGHT
 SAFE HARBORS FOR COMPLIANCE WITH THE FAIR HOUSING ACT.
 COMPLIANCE WITH ANY ONE OF THE ELEVEN WILL FULFILL THE
 FAIR HOUSING ACT'S ACCESS REQUIREMENTS. IF A PARTICULAR
 SAFE HARBOR IS CHOSEN FOR USE IN A PARTICULAR PROPERTY,
 HOUSING MUST COMPLY WITH ALL OF THE PROVISIONS OF THAT
 SAFE HARBOR FOR THERE TO BE A SAFE HARBOR. SO IT IS
 UNWISE TO PICK AND CHOOSE AMONG THE PROVISIONS OF
 DIFFERENT SAFE HARBOR STANDARDS.
 THIS COMMENT IS NOT ANSWERED, AND PUTTING IT ON THE
 PLAN DOES NOT ANSWER THE COMMENT. PICK THE SAFE HARBOR
 USED FOR FHA AND PUT IT UNDER GENERAL REQUIREMENTS.
  
 B. DONE
  
 C. DONE
  
 D. DONE
  
 8. DONE
  
 9. ON SHEET A1.1B1,
  
 A. DONE
  
 B. DONE
  
 C. DONE
  
 10. ON SHEET A-100;
  
 A. DONE
  
 B. DONE
  
 C. DONE
  
 D. DONE
  
 E. DONE
  
 F. DONE
  
 11. ON SHEET A-101;
  
 A. DONE
  
 B. DONE
  
 12. ON SHEET A-102;
  
 A. DONE
  
 B. DONE
  
 C. DONE
  
 13. ON SHEET A-103;
  
 A. DONE WITH NEW COMMENT-ON THE GUEST ROOM #2 BATH
 SHOWER DOES NOT COMPLY WITH THE 2020 FBC ACC SEC.
 608.2. SHOWER COMPARTMENTS. PLEASE SHOW THE CLEAR FLOOR
 SPACE PER THE 2017 FBC ACC SEC. 606.2. 2 CLEAR FLOOR
 SPACE. HOW WILL THE GRAB BARS COMPLY PER THE 2020 FBC
 ACC SEC. 608.2. PLEASE SHOW THE TURNING RADIUS SPACE OF
 FIVE FEET 603.2.1, 304.3.1 CIRCULAR SPACE.
  
 WHERE IS THE DETAIL FOR THE SHOWER AND GRAB BARS? WOULD
 YOU PLEASE SHOW THE CLEAR FLOOR SPACE IN FRONT OF THE
 SHOWER PER THE 2017 FBC ACC SEC. 608.2.1.
  
 B. DONE
  
 C. DONE
  
 D. DONE
  
 E. DONE
  
 14. ON SHEETS A1.104, 105, AND 124;
  
 A. SECOND REQUEST, WOULD YOU PLEASE IDENTIFY THE FHA
 UNITS AND SHOW THE CLEAR FLOOR SPACE FOR LAV, SHOWER,
 TUB, AND TOILET PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. DONE
  
 15. DONE
  
 16. ON SHEET A1.125;
  
 A. DONE
  
 B. DONE WITH NEW COMMENT. THERE IS A GAS GRILL; PLEASE
 IDENTIFY TANK PROPANE OR A GAS SYSTEM PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WOULD YOU PLEASE PUT THAT THE BBQ WILL BE ELECTRIC PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 C. DONE
  
 17. ON SHEETS A1.204, 205, 206, 207, 208, 209, 210,
 300, 301, 302, 303, AND 304, PLEASE IDENTIFY THE
 BATHROOM WHICH IS THE FHA AND SHOW CLEAR FLOOR SPACE
 FOR ALL FIXTURES PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. WOULD
 YOU PLEASE PROVIDE DIMENSIONS FOR FIXTURES PER THE 2020
 FBC SEC. 405.3.1.
  
 18. ON SHEET A1.306;
  
 A. DONE
  
 B. DONE
  
 C. SECOND REQUEST, WOULD YOU PLEASE SHOW OR POINT TO
 THE PAGE WHERE THE SEAT REINFORCES VERTICAL OR
 HORIZONTAL FORCE OF 250 POUNDS IS APPLIED ON THE SEAT,
 FASTENER, MOUNTING DEVICE, OR SUPPORTING STRUCTURE PER
 THE 2020 FBC ACC SEC. 610.4 STRUCTURAL STRENGTH.
 PLEASE PUT A NOTE ON PLANS PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 D. SECOND REQUEST, ON DETAIL #3, WOULD YOU PLEASE SHOW
 THE GRAB BARS TO THE TOP OF THE GRIPPING SURFACE PER
 THE 2020 FBC ACC SEC. 609.4.
  
 E. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
 NEW COMMENTS A0.207 AND A0.208 DO NOT EXIST; 00.207 AND
 00.208 DO. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 19. ON SHEET A1.306A;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
 NEW COMMENTS A0.207 AND A0.208 DO NOT EXIST, 00.207 AND
 00.208 DO. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
 B. DONE
  
 C. DONE
  
 20. ON SHEET A1.307;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
 NEW COMMENTS A0.207 AND A0.208 DO NOT EXIST, 00.207 AND
 00.208 DO. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
 B. DONE
  
 C. DONE.
  
 21. ON SHEET A1.308;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. DONE
  
 22. ON SHEET A1.309;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
 NEW COMMENTS A0.207 AND A0.208 DO NOT EXIST, 00.207 AND
 00.208 DO. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. DONE
  
 23. ON SHEET A1.310;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
 NEW COMMENTS A0.207 AND A0.208 DO NOT EXIST, 00.207 AND
 00.208 DO. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. DONE
  
 24. ON SHEET A1.311;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
 NEW COMMENTS A0.207 AND A0.208 DO NOT EXIST, 00.207 AND
 00.208 DO. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. DONE
  
 25. ON SHEET A1.312, IT SAYS FOR ADA FIXTURES AND
 ACCESSORIES, REFER TO A0.004 AND A0.005 AND NO SUCH
 PAGE. WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
 NEW COMMENTS A0.207 AND A0.208 DO NOT EXIST, 00.207 AND
 00.208 DO. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 26. ON SHEET A1.313;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
 NEW COMMENTS A0.207 AND A0.208 DO NOT EXIST, 00.207 AND
 00.208 DO. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. DONE WITH NEW COMMENT; ON DETAIL #1, WOULD YOU
 PLEASE SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS FOR THE WATER CLOSET, LAV, AND TURNING SPACE
 PER THE 2020 FBC ACC SEC. 606.2. 2 CLEAR FLOOR SPACE
 AND WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 NEW COMMENT, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE FOR THE SHOWER PER THE 202 FBC SEC. 608.2.1.
  
 C. DONE
  
 27. ON SHEET A1.314;
  
 A. DONE
  
 B. DONE
  
 C. ON DETAILS #7 AND #8. WOULD YOU PLEASE SHOW THE
 CLEAR FLOOR SPACE TO THE TUBS AND SHOWER PER THE FHA
 PAGE 7.43 AND THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. DONE
  
 E. DONE
  
 F. DONE
  
 G. DONE
  
 28. DONE
  
 29. DONE WITH NEW COMMENT. WOULD YOU PLEASE PROVIDE A
 PLUMBING PLAN INCLUDING THE SANITARY, CONDENSATE,
 STORM, AND WATER ISOMETRIC DRAWINGS PER THE WPB AMEND
 TO FBC 107.3.5.1.3(13)?
 NEW COMMENT, ON SHEET P5.104 ON THE THIRD TO
 FOUR-FLOOR, THE WATER, SHOWER ON A HORIZONTAL WET VENT,
 THE KITCHEN, AND THE RISER ON UPSTREAM. WOULD YOU
 PLEASE CORRECT PER THE 2020 FBC SEC. 2020 FBC SEC.
 912.1 HORIZONTAL WET VENT PERMITTED?
 ON SHEET P106, THE DRAINS FOR THE SUMP PIT ARE NOT
 SHOWING A FLOOR DRAIN ON THE GROUND FLOOR.
  
 30. ON SHEET P2.1B2;
  
 A. DONE WITH COMMENT; WOULD YOU PLEASE SHOW THE
 INDIRECT CONNECTION FOR THE ELEVATOR TO THE SANITARY ON
 THE PLUMBING DETAILS AND GIVE A REFERENCE PAGE NUMBER
 FOR IT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 A WASTER RECEPTOR CONSISTS OF A FLOOR OR HUB DRAIN AND
 SHALL HAVE A TRAP AND A PRIMER. THE INDIRECT CONNECTION
 HAS TO BE DRAINED INTO A WASTE RECEPTOR SHALL BE
 TRAPPED AND VENTED, AND SHALL CONNECT TO THE BUILDING
 DRAINAGE SYSTEM PER THE 2017 FBC SEC 802.3. IF THE
 ELEVATOR IS NOT OIL-INDUCED, THEY MAY GO TO THE STORM,
 BUT A LOCAL ORDINANCE MAY NOT ALLOW IT.
  
 B. SECOND REQUEST, WOULD YOU PLEASE LABEL THE STAIRWELL
 AND ELEVATOR PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. DONE.
  
  
 31. ON SHEET P2.1B1;
  
 A. DONE
  
 B. DONE
  
 C. DONE
  
 D. DONE
  
 E. DONE
  
 F. DONE.
  
 32. ON SHEET P2.101;
  
 A. DONE
  
 B. DONE
  
 C. NOT FOUND AS PER COMMENT; HOT WATER LINES LOOPED FOR
 THE RECIRCULATING SYSTEM ARE NOT IN A CONTINUOUS LOOP.
 THERE IS A REQUIREMENT IN THE FLORIDA ENERGY CODE SEC.
 C404.6.1. THERE IS A TABLE THAT LIMITS THE BETWEEN THE
 SOURCE AND THE OUTLET; PLEASE REFER TO TABLE 404.5.1
 FOR THE MAXIMUM ALLOWABLE PIPE LENGTH METHOD AND SIZE
 ACCORDANTLY. THE COMMENT WILL APPLY TO ALL AND WHERE
 THERE IS A LOOP SYSTEM.
  
 33. ON SHEET P2.102;
  
 A. DONE.
  
 B. DONE
  
 C. DONE
  
 34. DONE
  
 35. DONE
  
 36. DONE
  
 37. ON SHEET P4.201;
  
 A. DONE.
  
 B. DONE
  
 C. DONE
  
 38. ON SHEET P5.101;
  
 A. DONE
  
 B. DONE.
  
 39. ON SHEET P5.103;
  
 A. DONE
  
 B. DONE.
  
 C. DONE
  
 D. DONE
  
 E. DONE
  
 40. ON SHEET P5.104;
  
 A. DONE
  
 B. DONE
  
 41. ON SHEET P5.106;
  
 A. DONE
  
 B. DONE
  
 42. DONE
  
 43. DONE
  
 44. ON SHEET P7.102;
  
 A. DONE
  
 B. DONE
  
 PLEASE FEEL FREE TO SET UP A MEETING OR CONTACT ME ON
 ANY OF THE COMMENTS BY PHONE OR ZOOM MEETING IF YOU
 LIKE TO PREVENT FURTHER REVIEWS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-01-26 Cont ID  
Sent By lcrespo Date 2022-01-26 Time 15:59 Rev Time 0.00
Received By lcrespo Date 2022-01-12 Time 07:31 Sent To  
Notes
2022-01-26 16:00:0801/26/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. ON SHEET 00.002; PAGES ON ARE MISSING FROM THE
 PLUMBING INDEX AS FOLLOWS;
  
 P2.126
 P3.105
 P3.206
 P3.207
 P3.208
 P3.209
 P3.210
 P3.300
 P3.301
 P3.302
 P3.303
 P3.304
  
 2. ON SHEET 00.200, UNDER BUILDING TYPE, IT REFERS TO
 FLORIDA BUILDING CODE 2017, WHICH CURRENT IS 2020.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 3. ON SHEET A0.204, UNDER APPLICABLE CODES # 1 AND 2,
 IT REFERS TO FLORIDA BUILDING CODE 2017 AND
 ACCESSIBILITY 2017, WHICH IS CURRENTLY 2020 7 TH
 EDITION. FOR FHA # 5, IF YOU ARE USING THE DESIGN
 MANUAL OR THE GUIDELINES, WOULD YOU PLEASE CLARIFY
 WHICH SAFE HARBOR. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 4. ON SHEET 00.205;
  
 A. THE FHA NOTES TALKS ABOUT SPECIFICATION B AND NO
 MENTION ON THE LAV TO BE AT 34" PER 7.52 OF THE FHA
 DESIGN MANUAL.
  
 B. THE PENTHOUSE IS A FUTURE BUILD-OUT AND, IN THIS
 WAY, ESTABLISHED IN THE BUILDING DEPARTMENT THAT THE
 POWDER ROOM IS FOR THE CONSTRUCTION WORKER. WOULD YOU
 PLEASE ADD A NOTE OF THIS ON THE PAGE UNDER FAIR
 HOUSING ITEM #8 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. ON SHEET 00.206 UNDER LIFE SAFETY # 1 AND 2, IT
 REFERS TO FLORIDA BUILDING CODE 2017 AND ACCESSIBILITY
 2017, WHICH IS CURRENTLY 2020 7 TH EDITION. FOR FHA #
 5, IF YOU ARE USING THE DESIGN MANUAL OR THE
 GUIDELINES, WOULD YOU PLEASE CLARIFY WHICH SAFE HARBOR.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 6. ON SHEET 00.207;
  
 A. ON DETAIL C, THE TOILET SEATS NEED TO BE 17 INCHES
 TO 19 INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT
 PER THE 2020 FBC ACC SEC. 604.4 SEATS.
  
 B. ON DETAIL C AND F, THE FIXED 18 INCHES FROM THE WALL
 IS HAS A MINIMUM AND MAXIMUM PER 2020 FBC ACC SEC.
 604.2 LOCATION.
  
 C. UNDER GENERAL REQUIREMENTS # 1, 13, 14, 15, 16, IT
 REFERS TO FLORIDA BUILDING CODE 2017 AND ACCESSIBILITY
 2017, WHICH IS CURRENTLY 2020 7 TH EDITION. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. ON NUMBER 77, IT REFERS TO THE DISPENSER BEING 12
 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN
 FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF
 DISPENSER PER THE 2020 FBC ACC SEC. 604.7. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 E. ON NUMBER 81 WATER CLOSET IN THE ACCESSIBLE RESTROOM
 SHALL BE TO THE CENTERLINE OF THE WATER CLOSET 16
 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL
 PER THE 2020 FBC ACC. SEC. 604.2 LOCATION. SEATS OF
 WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER 2020 FBC P
 425.3 WATER CLOSET SEATS
  
 F. UNDER URINAL FOR PARTITION, WOULD YOU PLEASE ADD
 THAT THE PARTITIONS TO PROVIDE PRIVACY SHALL EXTEND NOT
 LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR SURFACE
 PER THE 2020 FBC SEC. P 405.3.5 URINAL PARTITIONS.
  
 G. FOR THE LABORATORIES, IT SAYS 29 INCHES BUT A
 MINIMUM OF 27" KNEE CLEARANCE PER THE 2020 FBC SEC.
 306.3.
  
 I. GRAB BARS # 95 ON THE REAR NEED TO BE MEASURED TO
 THE CENTER OF THE WATER CLOSET TO 12 INCHES TO THE WALL
 AND 24 INCHES TO THE OPEN SIDE PER THE 604.5.1 SIDE
 WALL AND 604.5.2 REAR WALL.
  
 7. ON SHEET 00.210;
  
 A. UNDER GENERAL REQUIREMENTS, IT HAS BOTH THE
 GUIDELINES AND THE DESIGN MANUAL, TWO DIFFERENT SAFE
 HARBORS, AND ONLY ONE SHOULD BE NOTED. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS? THERE ARE EIGHT
 SAFE HARBORS FOR COMPLIANCE WITH THE FAIR HOUSING ACT.
 COMPLIANCE WITH ANY ONE OF THE ELEVEN WILL FULFILL THE
 FAIR HOUSING ACT?S ACCESS REQUIREMENTS. IF A PARTICULAR
 SAFE HARBOR IS CHOSEN FOR USE IN A PARTICULAR PROPERTY,
 HOUSING MUST COMPLY WITH ALL OF THE PROVISIONS OF THAT
 SAFE HARBOR IN ORDER FOR THERE TO BE A SAFE HARBOR. SO
 IT IS UNWISE TO PICK AND CHOOSE AMONG THE PROVISIONS OF
 DIFFERENT SAFE HARBOR STANDARDS.
  
 B. THERE ARE TWO DETAILS, 1 AND 3, AND OTHER FHA
 DETAILS THAT ARE NOT NEEDED IN THIS SET OF PLANS. WOULD
 YOU PLEASE REMOVE FOR FIELD CLARITY PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS? THESE IMAGES SEEM TO COME FROM
 THE DESIGN MANUAL, BUT THE VERBIAGE UP TOP SEEMS TO BE
 ON THE GUIDELINES. PLEASE REFER TO THE ABOVE COMMENT
 AND CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. UNDER CHAPTER SIX REQUIREMENTS, IT REFERS TO THE
 ANSI 117.1 STANDARD, WHICH IS NOT MENTIONED UNDER
 APPLICABLE CODES. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS? IT IS IMPORTANT TO NOTE THAT
 THE ANSI A117.1 STANDARD CONTAINS ONLY TECHNICAL
 CRITERIA, WHEREAS THE FAIR HOUSING ACT, THE
 REGULATIONS, AND THE GUIDELINES CONTAIN BOTH SCOPING
 AND TECHNICAL CRITERIA. THEREFORE, IN USING ANY OF THE
 ANSI STANDARDS, IT IS ALSO NECESSARY TO CONSULT THE ACT
 HUD'S REGULATIONS AND THE GUIDELINES.
  
 D. FOR DETAIL TWO AND 11 ON A0.211 FOR THE SPEC B
 BATHROOM USED DOES NOT MATCH THE FLOOR LAYOUT PRESENTED
 IN THESE PLANS. FOR EXAMPLE, THE TUB IS DIFFERENT, AND
 THERE IS IN THE FHA DESIGN MANUAL REINFORCING FOR GRAB
 BARS AT NON-CONVENTIONAL BATHTUBS PAGE 6.10. WOULD YOU
 PLEASE PROVIDE DETAIL FOR BACKING PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 8. ON SHEET LS1.100 AND LS1.101 AND ALL OTHERS, THE
 APPLICABLE CODES IT HAS THE FLORIDA BUILDING AND
 ACCESSIBILITY REFERS TO THE 2017 6 TH EDITION AND THE
 CURRENT IS 2020 7 THE EDITION. WOULD YOU PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS? IF YOU ARE USING
 THE DESIGN MANUAL OR THE GUIDELINES FOR THE FHA, WOULD
 YOU PLEASE CLARIFY WHICH SAFE HARBOR? WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 9. ON SHEET A1.1B1,
  
 A. LEVEL B1 IN THE BREAK ROOM, PLEASE SHOW THE CLEAR
 FLOOR SPACE FOR THE SINK PER THE 2020 FBC ACC SEC.
 602.2.
  
 B. LEVEL B2, THE PUMPROOM DOES NOT SHOW A FLOOR DRAIN,
 AND IT IS NOT REQUIRED BUT RECOMMENDED. WOULD YOU
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. IN STAIRCASE C, THERE IS A FLOOR DRAIN WITH NUMBER
 04 POINTING TO IT AND NOT LABELED. WOULD YOU PLEASE
 CLARIFY OR CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 10. ON SHEET A-100;
  
 A. THE PLANTER SHOW DRAIN BUT NOT LABELED. WOULD YOU
 PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. WOULD YOU PLEASE LABEL ALL ROOMS AND FLOOR DRAIN PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 C. IN. THE MEN'S RESTROOM DOES NOT SHOW THE WATER
 CLOSET. WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 D. IN THE EMPLOYEE RR, THE FIXTURES ARE MISSING. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 E. THE GENERATOR IS SHOWN, AND IT SHOULD BE NOTED THAT
 IT IS BELOW B1. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 F. WOULD YOU PLEASE SHOW ALL CLEAR FLOOR SPACE PER THE
 FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE.
 PLEASE INDICATE THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS PER THE 2020 FBC ACC SEC. 606.2. 2 CLEAR
 FLOOR SPACE AND WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. LAV IN THE OPEN
 AREA ON THE WOMEN'S REQUIRES CLEAR FLOOR SPACE.
  
 11. ON SHEET A-101;
  
 A. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 WOMEN'S RESTROOM FOR THE LAV ON THE OPEN AREA PER THE
 2020 FBC ACC SEC. 602.2. PLEASE INDICATE THE CLEAR
 FLOOR SPACE DIAGRAM AND DIMENSIONS PER THE 2020 FBC ACC
 SEC. 606.2. 2 CLEAR FLOOR SPACE AND WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 B. IN THE JANITOR'S ROOM, THE SERVICE SINK (MOP SINK)
 SURROUNDING THE WALL SHALL BE A NON-ABSORBENT SURFACE
 IN ACCORDANCE WITH THE 2020 FBC BUILDING SEC. 1210.2.2
 AND 2020 FBC SEC. P 310.3. PLEASE MAKE A NOTE ON THIS
 SHEET.
  
 12. ON SHEET A-102;
  
 A. IN THE WARMING KITCHEN, THERE IS S SINK. WOULD YOU
 PLEASE SHOW THE CLEAR FLOOR SPACE PER THE 2020 FBC ACC
 SEC. 602.2. PLEASE INDICATE THE CLEAR FLOOR SPACE
 DIMENSIONS PER THE 2020 FBC ACC SEC. 606.2. 2 CLEAR
 FLOOR SPACE AND WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. WOULD YOU PLEASE LABEL THE JANITOR SINK PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. IN THE MEN'S RESTROOM, THERE IS A LAV IN THE OPEN
 AREA THAT REQUIRES CLEAR FLOOR SPACE PER THE 2020 FBC
 ACC SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 13. ON SHEET A-103;
  
 A. ON THE GUEST ROOM #2 BATH SHOWER DOES NOT COMPLY
 WITH THE 2020 FBC ACC SEC. 608.2. SHOWER COMPARTMENTS.
 PLEASE SHOW THE CLEAR FLOOR SPACE PER THE 2020 FBC ACC
 SEC. 606.2. 2 CLEAR FLOOR SPACE. HOW WILL THE GRAB BARS
 COMPLY PER THE 2020 FBC ACC SEC. 608.2. PLEASE SHOW THE
 TURNING RADIUS SPACE OF FIVE FEET 603.2.1, 304.3.1
 CIRCULAR SPACE.
  
 B. IN WOMEN'S AND MEN'S SPAS, THE OPEN LAVS NEED TO
 SHOW THE CLEAR FLOOR SPACE PER THE 2020 FBC ACC SEC.
 606.2. 2 CLEAR FLOOR SPACE.
  
 C. THE MEN'S RESTROOM NEEDS TO COMPLY WITH THE 2020
 ACCESSIBILITY AND SHOW THE CLEAR FLOOR SPACE FOR LAV,
 TURNING RADIUS, AND TOILET. THE WOMAN'S RESTROOM NEEDS
 TO SHOW THE TURNING SPACE PER THE 2020 FBC ACC SEC.
 612.3 TURNING SPACE.
  
 D. THE MEN'S AND WOMAN'S SAUNA AND STEAM NEED TO SHOW
 THE TURNING SPACE PER THE 2020 FBC ACC SEC. 612.3
 TURNING SPACE.
  
 E. THE TREATMENT ROOM NEEDS TO SHOW THE LAVS CLEAR
 FLOOR SPACE PER THE 2020 FBC ACC SEC. 606.2. 2 CLEAR
 FLOOR SPACE.
  
 14. ON SHEET A1.104, 105, AND 124;
  
 A. WOULD YOU PLEASE IDENTIFY THE FHA UNITS AND SHOW THE
 CLEAR FLOOR SPACE FOR LAV, SHOWER, TUB, AND TOILET PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 B. IT IS SAID THAT SPECIFICATION B IS TO BE USED IN THE
 MASTER, SO PLEASE TELL US HOW THE FHA GRAB BAR BACKING
 WILL COMPLY SINCE IT IS AN OPEN SHOER TO TWO SIDES.
 WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 15. ON SHEET A1.124, THE BUILD-OUT IS FOR THE FUTURE.
 WOULD YOU PLEASE PROVIDE A NOTE ON THIS PAGE STATING
 THE FHA BATHROOM AND ITS COMPLIANCE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 16. ON SHEET A1.125;
  
 A. IN THE POOL EQUIPMENT, THERE IS A SINK AND A HOSE
 BIBB. WOULD YOU PLEASE LABEL PER THE SOLAR COVER
 REQUIRED PER 2020 FBC RE 403.10.3?
  
 B. THERE IS A GAS GRILL; PLEASE IDENTIFY TANK PROPANE
 OR A GAS SYSTEM PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. UNDER ROOF GENERAL NOTES, THERE IS MENTION FOR ROOF
 DRAIN AND OVERFLOW CALCULATION. WOULD YOU PLEASE
 PROVIDE THE PAGE NUMBER WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 17. ON SHEET A1.204, 205, 206, 207, 208, 209, 210, 300,
 301, 302, 303, AND 304, PLEASE IDENTIFY THE BATHROOM
 WHICH IS THE FHA AND SHOW CLEAR FLOOR SPACE FOR ALL
 FIXTURES PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. WOULD YOU PLEASE
 PROVIDE DIMENSIONS FOR FIXTURES PER THE 2020 FBC SEC.
 405.3.1.
  
 18. ON SHEET A1.306;
  
 A. THE SHOWER IS SHOWN AT 2'-11", AND IT SHALL HAVE
 SIZES AND CLEARANCES COMPLYING WITH 2020 FBC ACC SEC.
 608.2.
  
 B. WOULD YOU PLEASE SHOW A CLEAR FLOOR SPACE DIAGRAM
 AND DIMENSIONS FOR ALL FOUR SHOWERS PER THE 2020 FBC
 ACC SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 C. WOULD YOU PLEASE SHOW OR POINT TO THE PAGE WHICH THE
 SEAT REINFORCES VERTICAL OR HORIZONTAL FORCE OF 250
 POUNDS IS APPLIED AT ANY POINT ON THE SEAT, FASTENER,
 MOUNTING DEVICE, OR SUPPORTING STRUCTURE PER THE 2020
 FBC ACC SEC. 610.4 STRUCTURAL STRENGTH.
  
 D. ON DETAIL #3, WOULD YOU PLEASE SHOW THE GRAB BARS TO
 THE TOP OF THE GRIPPING SURFACE PER THE 2020 FBC ACC
 SEC. 609.4.
  
 E. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 19. ON SHEET A1.306A;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. WOULD YOU PLEASE SHOW A CLEAR FLOOR SPACE DIAGRAM
 AND DIMENSIONS FOR THE SINK PER THE 2020 FBC ACC SEC.
 606.2. 2 CLEAR FLOOR SPACE.
  
 C. WOULD YOU PLEASE SHOW THE SINK OF 34 INCHES MAXIMUM
 PER THE 2020 FBC ACC SEC. 606.3.
  
 20. ON SHEET A1.307;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. ON DETAIL # 4, 9, AND 10, WOULD YOU PLEASE SHOW THE
 GRAB BARS TO THE TOP OF THE GRIPPING SURFACE PER THE
 2020 FBC ACC SEC. 609.4.
  
 C. UNDER URINAL FOR PARTITION, WOULD YOU PLEASE ADD
 THAT THE PARTITIONS TO PROVIDE PRIVACY SHALL EXTEND NOT
 LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR SURFACE
 PER THE 2020 FBC SEC. P 405.3.5 URINAL PARTITIONS.
  
 21. ON SHEET A1.308;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. IN WOMEN'S AND MEN'S SPAS, THE OPEN LAVS NEED TO
 SHOW THE CLEAR FLOOR SPACE PER THE 2020 FBC ACC SEC.
 606.2. 2 CLEAR FLOOR SPACE.
  
 22. ON SHEET A1.309;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. ON DETAIL #1, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE DIAGRAM AND DIMENSIONS FOR THE WATER CLOSET, LAV,
 AND TURNING SPACE PER THE 2020 FBC ACC SEC. 606.2. 2
 CLEAR FLOOR SPACE AND WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 23. ON SHEET A1.310;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. ON DETAIL #1, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE DIAGRAM AND DIMENSIONS FOR THE WATER CLOSET, LAV,
 AND TURNING SPACE PER THE 2020 FBC ACC SEC. 606.2. 2
 CLEAR FLOOR SPACE AND WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. THE OPEN
 LAV REQUIRES CLEAR FLOOR SPACE PER THE 2020 FBC ACC
 SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 24. ON SHEET A1.311;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. ON DETAIL #1, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE DIAGRAM AND DIMENSIONS FOR THE WATER CLOSET, LAV,
 AND TURNING SPACE PER THE 2020 FBC ACC SEC. 606.2. 2
 CLEAR FLOOR SPACE AND WPB
  
 25. ON SHEET A1.312, IT SAYS FOR ADA FIXTURES AND
 ACCESSORIES, REFER TO A0.004 AND A0.005 AND NO SUCH
 PAGE. WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 26. ON SHEET A1.313;
  
 A. IT SAYS FOR ADA FIXTURES AND ACCESSORIES, REFER TO
 A0.004 AND A0.005 AND NO SUCH PAGE. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. ON DETAIL #1, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE DIAGRAM AND DIMENSIONS FOR THE WATER CLOSET, LAV,
 AND TURNING SPACE PER THE 2020 FBC ACC SEC. 606.2. 2
 CLEAR FLOOR SPACE AND WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. THE GUEST ROOM #2 BATH SHOWER DOES NOT COMPLY WITH
 THE 2020 FBC ACC SEC. 608.2. SHOWER COMPARTMENTS.
 PLEASE SHOW THE CLEAR FLOOR SPACE PER THE 2020 FBC ACC
 SEC. 606.2. 2 CLEAR FLOOR SPACE. HOW ARE THE GRAB BARS
 GOING TO COMPLY PER THE 2020 FBC ACC SEC. 608.2. PLEASE
 SHOW THE TURNING RADIUS SPACE OF FIVE FEET 603.2.1,
 304.3.1 CIRCULAR SPACE.
  
 27. ON SHEET A1.314;
  
 A. ON THIS PAGE HAS FHA PLANS FOR THE DIFFERENT
 RESTROOMS, BUT SHEET 00.205 SAYS THE MASTER BEDROOM TO
 BE SPECIFICATION B. WHICH ONE IS THE CORRECT ONE, AND
 WOULD YOU LABEL THE ONE PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. ONE OF EACH TYPE OF FIXTURE MUST BE USABLE BY A
 PERSON WITH A DISABILITY IN A SPECIFICATION B BATHROOM
 PER THE FHA PAGE 7.34.
  
 C. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE TO THE
 WATER CLOSET PER THE FHA PAGE 7.43 AND THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. ON DETAIL # 5 ON THE SHOWER, WHERE ARE THE GRAB BARS
 SUPPORTS FOR THE SIDE AND SHOW THE BACKING FOR FRONT
 AND BACK PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. SHOW THE CLEAR
 FLOOR SPACE FOR THE TUB AND WATER CLOSET PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. ONLY ON LAV SHALL COMPLY ON
 SPECIFICATION B.
  
 E. ON DETAIL # 6, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE TO THE WATER CLOSET PER THE FHA PAGE 7.43 AND THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 F. ON DETAIL # 7, IT SHOWS THE CLEAR FLOOR SPACE TO THE
 WATER CLOSET BUT CAN YOU SHOW DIMENSIONS PER THE FHA
 PAGE 7.43 AND THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. FOR THE
 SHOWER, WHERE ARE THE GRAB BARS SUPPORTS FOR THE SIDE,
 AND PLEASE SHOW THE BACKING FOR FRONT AND BACK PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. SHOW THE CLEAR FLOOR SPACE FOR
 THE TUB AND WATER CLOSET PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 ONLY ON LAV SHALL COMPLY ON SPECIFICATION B.
  
 G. ON DETAIL # 8, SHOW THE BACKING FOR SIDE, FRONT, AND
 BACK PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. SHOW THE CLEAR
 FLOOR SPACE FOR THE TUB PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 SHOWS THE CLEAR FLOOR SPACE TO THE WATER CLOSET, TUB,
 AND SHOWER WITH DIMENSIONS PER THE FHA PAGE 7.43 AND
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 28. ON SHEET A1.400, IN THE EMPLOYEE RR, WOULD YOU
 PLEASE SHOW THE TURNING SPACE PER THE 2020 FBC ACC SEC.
 612.3 TURNING SPACE.
  
 29. WOULD YOU PLEASE A PLUMBING PLAN INCLUDING THE
 SANITARY, CONDENSATE, STORM, AND WATER ISOMETRIC
 DRAWINGS PER THE WPB AMEND TO FBC 107.3.5.1.3(13).
  
 30. ON SHEET P2.1B2;
  
 A. WOULD YOU PLEASE SHOW THE INDIRECT CONNECTION FOR
 THE ELEVATOR TO THE SANITARY ON THE PLUMBING DETAILS
 AND GIVE A REFERENCE PAGE NUMBER FOR IT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. WOULD YOU PLEASE LABEL THE STAIR WELL AND ELEVATOR
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. IT IS MOTION ON PLANS HOW THE PIPES SHALL BE
 PROTECTED WATER LINES AND SANITARY WHERE THE VEHICULAR
 PATHWAY IN THE PARKING GARAGE EXPOSED TO DAMAGE AND
 SHALL BE RECESSED INTO THE WALL OR OTHERWISE PROTECTED
 IN AN APPROVED MANNER PER 2020 FBC SEC. P 305.7
 PROTECTION OF COMPONENTS OF THE PLUMBING SYSTEM. PLEASE
 PROVIDE DETAILS OR SHOW BOLLARDS IN FRONT OF PIPES PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 WOULD YOU INCORPORATE A NUMBER ON THE LEGEND PRESENT
 FOR THE BOLLARD LOCATION AND SHOW IT ON B1 AND B2 PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 31. ON SHEET P2.1B1;
  
 A. IT IS MOTION ON PLANS HOW THE PIPES SHALL BE
 PROTECTED WATER LINES AND SANITARY WHERE THE VEHICULAR
 PATHWAY IN THE PARKING GARAGE EXPOSED TO DAMAGE AND
 SHALL BE RECESSED INTO THE WALL OR OTHERWISE PROTECTED
 IN AN APPROVED MANNER PER 2020 FBC SEC. P 305.7
 PROTECTION OF COMPONENTS OF THE PLUMBING SYSTEM. PLEASE
 PROVIDE DETAILS OR SHOW BOLLARDS IN FRONT OF PIPES PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 WOULD YOU INCORPORATE A NUMBER ON THE LEGEND PRESENT
 FOR THE BOLLARD LOCATION AND SHOW IT ON B1 AND B2 PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 B. THERE ARE TWO RPZ'S AND AN FD IN A ROOM. WOULD YOU
 PLEASE LABEL THE ROOM PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. THERE IS A RESTROOM NEXT TO THE SERVICE CORRIDOR,
 THE EMPLOYEE RESTROOM THAT IS NOT LABELED, AND THE
 LAUNDRY ROOM. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 D. WOULD YOU, PLEASE LABEL THE DRAIN IN THE EMPLOYEE
 RESTROOM AND THE LAUNDRY ROOM PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 E. WHERE THE FOUR SHOWERS ARE, WOULD YOU PLEASE LABEL
 THE BREAKROOM, W, AND M LOCKER ROOM PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 F. IN STAIRWELL C, THE SECONDARY STAIRS THAT GO OUTSIDE
 LOOK LIKE A DRAIN AT THE BOTTOM. WOULD YOU PLEASE LABEL
 ALL STAIRWELLS AND IDENTIFY DRAINS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 32. ON SHEET P2.101;
  
 A. THERE ARE DRAINS IN THE FIRE PUMP AND NEXT TO THE
 TRASHING STAGE THAT IS NOT LABELED. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. WOULD YOU PLEASE LABEL THE ROOMS NEXT TO THE TRASH
 STAGING ARE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. HOT WATER LINES LOOPED FOR THE RECIRCULATING SYSTEM
 ARE NOT IN A CONTINUOUS LOOP. THERE IS A REQUIREMENT IN
 THE FLORIDA ENERGY CODE SEC. C404.6.1. THERE IS A TABLE
 THAT LIMITS THE BETWEEN THE SOURCE AND THE OUTLET;
 PLEASE REFER TO TABLE 404.5.1 FOR THE MAXIMUM ALLOWABLE
 PIPE LENGTH METHOD AND SIZE ACCORDANTLY. THE COMMENT
 WILL APPLY TO ALL AND WHERE THERE IS A LOOP SYSTEM.
  
 33. ON SHEET P2.102;
  
 A. THE RESTROOM NEXT TO THE ELEVATOR IS NOT LABELED.
 WOULD YOU PLEASE LABEL PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. DOES THE KITCHEN HAVE AN ICEMAKER OR COFFEE MAKER,
 AND IF SO, IT SHALL BE EQUIPPED WITH AN IN-LINE VACUUM
 BREAKER THAT COMPLIES WITH ASSE 1024 PER THE 2020 FBC
 SEC. 608.13.10.
  
 C. THERE IS A SHOWER FOR THE POOL IS THE DRAIN GOING IN
 A STORM OR TO A DRY WELL. IF RAIN IS COLLECTED, IT
 CANNOT GO INTO THE SANITARY. WOULD YOU PLEASE CLARIFY
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 34. ON SHEET P2.103, THERE IS A DRINKING FOUNTAIN IN
 FRONT OF THE BUSINESS ROOM. WHAT IS THE DISTANCE TO THE
 GYM PER THE 2020 FBC SEC. P 403.5 DRINKING FOUNTAIN
 LOCATION.
  
 35. ON SHEET P2.104 AND P2.124, WOULD YOU PLEASE LABEL
 ALL RESTROOMS, BEDROOMS, AND AMENITY ROOMS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 36. ON SHEETS P3.105, P3.204, P3.205, P3.206, P3.207,
 P3.208, P3.209, P3.210, P3.300, P3.301, P3.302, P3. 303
 AND P3.304 WOULD YOU PLEASE LABEL ROOMS AND RESTROOM
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 37. ON SHEET P4.201;
  
 A. WOULD YOU PLEASE LABEL THE ROOM AND SHOW THE
 SANITARY PIPE FOR THEM PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 C. WOULD YOU PLEASE LABEL THE FLOOR DRAIN IN THE
 RESTROOM PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 38. ON SHEET P5.101;
  
 A. WOULD YOU PLEASE PROVIDE SHUTOFF VALVES ON EACH
 RISER PER THE 2020 FBC SEC. 606.1 (4).
  
 B. IT SHOWS A DOUBLE CHECK VALVE AS BACKFLOW AND
 REDUCED PRESSURE ZONE VALVE REQUIRED PER THE CITY OF
 WEST PALM BEACH AND THE CROSS CONNECTION PROGRAM. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 39. ON SHEET P5.103;
  
 A. RISER 1 SHOWS THE L-3, SH-3 AND WC-3 ARE VENTED
 INCORRECTLY TWICE PER THE 2020 FBC SEC. P 901.2.
  
 B. RISER 2 SHOWS THE DF-1 AND WASHERS ARE VENTED
 INCORRECTLY PER THE 2020 FBC SEC. P 901.2.
  
 C. FOR RISER 2, THE CONTINUATION FOR LETTER F SAYS
 P4.505 THAT PAGE DOES NOT EXIST. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. ON RISER 2, THERE IS A FLOOR DRAIN AND WATER CLOSET
 TOGETHER, AND A VENT IS REQUIRED PER THE 2020 FBC SEC.
 910.1 INDIVIDUAL VENTS PERMITTED.
  
 E. ON RISER 2, THERE IS A VENT WITH NO CONTINUATION
 POINT ON THE GROUND FLOOR AND ON B2 AS WELL. WOULD YOU
 PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 40. ON SHEET P5.104;
  
 A. THE DRAIN PAN IS SHOWN GOING INTO THE SANITARY ON 4
 TH, AND 5 TH DOES THIS DRAIN CARRY CONDENSATE. WOULD
 YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. THE 4 TH FLOOR SHOWS 4 SH 2, 1 SH 1, 1 DP, 1 B-1, 4
 WC-2, AND 1 WC-1 THAT ARE NOT VENTED AND ON THE MAIN
 DRAIN BY THE STACK. WOULD YOU PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 41. ON SHEET P5.106;
  
 A. THE CLEANOUTS ARE REQUIRED IN THE BOTTOM OF THE
 STACK PER THE 2020 FBC SEC. P 1101.8 CLEANOUTS
 REQUIRED.
  
 B. AT GROUND LEVEL, IT SAT TP PODIUM PLATER DRAINAGE.
 WOULD YOU PLEASE GIVE THE CORRESPONDING PAGE NUMBER PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 42. ON SHEETS, P5.106 AND P5.107 SHOW THE TABLES USED
 FOR THE SIZING OF THE STORM PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 43. ON SHEET P5.107, LETTERS A, B, AND C REFER TO
 CONTINUATION FOR P5.06 AND NO SUCH PAGE. WOULD YOU
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 44. ON SHEET P7.102;
  
 A. PLEASE PROVIDE DETAIL ON RIGID SUPPORT SWAY BRACING
 SHALL BE PROVIDED AT CHANGES IN A DIRECTION MORE
 SIGNIFICANT THAN 45 DEGREES FOR PIPE SIZES 4 INCHES AND
 LARGER PER FBC-PLUMBING SEC. 308.6. SUBMIT DETAILS FOR
 THE BRACING.
  
 B. ON DETAIL 4 FOR THE CONDENSATE DRAIN, WOULD YOU
 PLEASE PROVIDE THE LOCATION WHERE THE DRAIN WILL BE
 DISCHARGING PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PLEASE FEEL FREE TO SET UP A MEETING OR CONTACT ME ON
 ANY OF THE COMMENTS BY PHONE OR ZOOM MEETING IF YOU
 LIKE TO PREVENT FURTHER REVIEWS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2022-06-07 Cont ID  
Sent By rmcphers Date 2022-06-07 Time 14:51 Rev Time 0.00
Received By rmcphers Date 2022-06-07 Time 14:51 Sent To  
Notes
2022-06-07 14:51:39ROOFING TO BE DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-03-28 Cont ID  
Sent By rmcphers Date 2022-03-28 Time 12:39 Rev Time 0.00
Received By rmcphers Date 2022-03-28 Time 12:39 Sent To  
Notes
2022-03-28 12:41:39SEE BUILDING PLAN REVIEW - IF THE ROOFING SYSTEM
 PRODUCT APPROVALS ARE TO BE DEFERRED - PLEASE ADD
 ROOFING SYSTEM TO THE DEFERRED LIST ON THE DRAWINGS.
  
 FBC WPB 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES
 OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS
 THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT
 THE TIME OF THE APPLICATION AND THAT ARE TO BE
 SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED
 PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE
 PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-01-06 Cont ID  
Sent By rmcphers Date 2022-01-06 Time 10:46 Rev Time 0.00
Received By rmcphers Date 2022-01-06 Time 10:46 Sent To  
Notes
2022-01-06 10:46:45SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-09-29 Cont ID  
Sent By rmcphers Date 2022-09-29 Time 11:09 Rev Time 0.00
Received By rmcphers Date 2022-09-29 Time 11:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-08-19 Cont ID  
Sent By rmcphers Date 2022-08-19 Time 10:42 Rev Time 0.00
Received By rmcphers Date 2022-08-19 Time 10:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-06-07 Cont ID  
Sent By rmcphers Date 2022-06-07 Time 15:10 Rev Time 0.00
Received By rmcphers Date 2022-06-07 Time 15:10 Sent To  
Notes
2022-06-01 17:17:47DIGITAL SIGNATURES FOR MECHANICAL APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-03-28 Cont ID  
Sent By rmcphers Date 2022-03-28 Time 13:26 Rev Time 0.00
Received By rmcphers Date 2022-03-28 Time 13:26 Sent To  
Notes
2022-03-28 13:26:51SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DOCUMENT LABELED "COMBINED - FLAGLER DESIGN CRITERIA
 & CALCS.PDF " IN PROJECTDOX "SUPPORTING DOC." FOLDER
 DOES NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-01-06 Cont ID  
Sent By rmcphers Date 2022-01-06 Time 14:13 Rev Time 0.00
Received By rmcphers Date 2022-01-06 Time 14:13 Sent To  
Notes
2022-01-06 14:17:32SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DOCUMENT LABELED "COMBINED - FLAGLER DESIGN CRITERIA
 & CALCS.PDF " IN PROJECTDOX "SUPPORTING DOC." FOLDER
 DOES NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2022-06-07 Cont ID  
Sent By rmcphers Date 2022-06-07 Time 15:28 Rev Time 0.00
Received By rmcphers Date 2022-06-07 Time 15:28 Sent To  
Notes
2022-06-07 15:29:10SEE PERMIT 20030982 FOUNDATION

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2022-03-28 Cont ID  
Sent By rmcphers Date 2022-03-28 Time 12:42 Rev Time 0.00
Received By rmcphers Date 2022-03-28 Time 12:42 Sent To  
Notes
2022-03-28 12:49:39THRESHOLD BUILDING
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PLEASE COMPLETE THE FORM WHICH INCLUDES THE
 CONTRACTORS SIGNATURE.
  
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2022-01-06 Cont ID  
Sent By rmcphers Date 2022-01-06 Time 10:40 Rev Time 0.00
Received By rmcphers Date 2022-01-06 Time 10:40 Sent To  
Notes
2022-01-06 10:43:58THRESHOLD BUILDING
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 NOTE: THIS STRUCTURE IS CONSIDERED A THRESHOLD BUILDING
 PER FS 553.71 12) "THRESHOLD BUILDING" MEANS ANY
 BUILDING WHICH IS GREATER THAN THREE STORIES OR 50 FEET
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 1) PLEASE COMPLETE THE FORM WHICH INCLUDES THE
 CONTRACTORS SIGNATURE.
  
 2) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD SHALL CONTAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  

Review Stop Z ZONING
Rev No 5 Status P Date 2022-10-14 Cont ID  
Sent By eschneid Date 2022-10-14 Time 16:37 Rev Time 0.75
Received By eschneid Date 2022-10-14 Time 15:40 Sent To  
Notes
2022-10-14 16:38:121) PROVISO: PRIOR TO ISSUANCE OF THE FIRST CERTIFICATE
 OF OCCUPANCY FOR THE BUILDING, YOU MUST SUBMIT TWO
 COPIES OF THE AS BUILT PLANS FOR THE SHEETS CITED IN
 RESOLUTION 13-19 TO CLOSE OUT THE MINOR PLANNED
 DEVELOPMENT AMENDMENT
  
 2) PROVISO: ANY PERMITS THAT ARE NOT CLOSED WILL NEED
 TO INCLUDE THE MOST RECENT PLANS TO BE SUBMITTED AS
 PART OF A PERMIT REVISION TO ENSURE CONSISTENCY.
  
 3) THE FOLLOWING ITEMS REQUIRE REVIEW AS SEPARATE
 PERMITS WITH PLANS:
  
 A. THE WALLS, FENCES, GATES AND COLUMNS
 B. HARDSCAPE, INCLUDING PAVERS, ARTIFICIAL TURF, DOG
 PARK ITEMS, BENCHES/PLAZA AREA, ETC.
 C. LANDSCAPE
 D. IRRIGATION
 E. GENERATOR
 F. WATER FEATURES
 G. PARKING STRIPING
 H. SITE LIGHTING, INCLUDING BOLLARDS, NOTE: SINCE
 ACACIA ROAD IS A SEPARATE PARCEL, IT REQUIRES ITS OWN
 PERMIT FOR THE LIGHTING, BUT MAY BE INCLUDED ON ONE SET
 OF PLANS FOR BOTH PERMIT NUMBERS. PHOTOMETRIC PLANS ARE
 REQUIRED WITH THE PERMITS.
 I. BICYCLE RACKS, INCLUDES WITHIN THE BICYCLE STORAGE
 ROOM.
 J. EV CHARGING STATIONS
  

Review Stop Z ZONING
Rev No 4 Status F Date 2022-09-16 Cont ID  
Sent By eschneid Date 2022-09-16 Time 10:48 Rev Time 2.00
Received By eschneid Date 2022-09-15 Time 10:06 Sent To  
Notes
2022-09-16 10:49:23FAILED
  
 1) PROVISO: PRIOR TO ISSUANCE OF THE FIRST CERTIFICATE
 OF OCCUPANCY FOR THE BUILDING, YOU MUST SUBMIT TWO
 COPIES OF THE AS BUILT PLANS FOR THE SHEETS CITED IN
 RESOLUTION 13-19 TO CLOSE OUT THE MINOR PLANNED
 DEVELOPMENT AMENDMENT
  
 2) PROVISO: ANY PERMITS THAT ARE NOT CLOSED WILL NEED
 TO INCLUDE THE MOST RECENT PLANS TO BE SUBMITTED AS
 PART OF A PERMIT REVISION TO ENSURE CONSISTENCY.
  
 3) UPDATED COMMENT: THE NORTH/SOUTH INSIDE DIMENSION OF
 LEVEL B2 (SHEET A1.1B1) HAS BEEN REDUCED BY
 APPROXIMATELY 20 INCHES WHEN COMPARED TO THE APPROVED
 FOUNDATION PERMIT AND THE LAST SET OF PLANS THAT STAFF
 REVIEWED AS PART OF THE MINOR PLANNED DEVELOPMENT
 AMENDMENT. THE DIMENSION LINES VERIFYING THE 24-FOOT
 DRIVE AISLE AND 18-FOOT PARKING SPACE DEPTH FOR THE
 ENTIRE GARAGE NEED TO BE INCLUDED ON THE PLAN SO THAT
 STAFF CAN VERIFY THAT THE SPACES AND AISLES STILL MEET
 CODE MINIMUMS.
  
 4) SHEET A1.100 SHOWS THE DIMENSION FROM THE AMENITY
 DECK TO THE EASTERN PROPERTY LINE AS 9 FEET 11.5
 INCHES. THE VARIANCE GRANTED BY RESOLUTION NO. 13-19
 REQUIRES A 10-FOOT SETBACK AT THIS LOCATION. IT APPEARS
 THAT THE PROPERTY LINE GETS CLOSER TO THE BUILDING AT
 THE INSIDE CORNER, WHICH CAUSES IT TO BE LESS THAN 10
 FEET (WHICH IS SHOWN ON SHEET A1.102 AT A FURTHER NORTH
 MEASURE POINT).
  
 5) THERE ARE DISCREPANCIES BETWEEN SHEETS A1.100 AND
 A1.101. EX. SITE LAYOUT AROUND GENERATOR AND MORE FPL
 TRANSFORMERS SHOWN ON SHEET 1.100. ADDITIONALLY, WHERE
 SHOWN, THE SETBACK DIMENSIONS DO NOT MATCH. ALL SHEETS
 MUST SHOW CONSISTENT, CODE COMPLIANT, ACCURATE PLANS.
  
 6) UPDATED COMMENT: THANK YOU FOR PROVIDING THE UPDATED
 ELEVATION DRAWINGS. PLEASE SEE THE ITEMS LISTED BELOW.
 ALL SHEETS MUST SHOW CONSISTENT, CODE COMPLIANT,
 ACCURATE PLANS.
  
 A. SHEET A3.100 (NORTH ELEVATION) SHOWS CONFLICTING
 WESTERN SETBACKS AT LEVEL 2 AND 5. THE LEVEL 2 SETBACK
 DIMENSION DOES NOT COMPLY WITH THE VARIANCE GRANTED BY
 RESOLUTION NO. 13-19.
 B. SHEET A3.102 (WEST AND EAST ELEVATIONS) SHOWS
 AMENITY FLOORS 2 AND 3 SETBACKS NOT COMPLYING WITH THE
 VARIANCE GRANTED BY RESOLUTION NO. 13-19.
 C. SHEET A3.102 (WEST ELEVATION) SHOWS THE GROUND FLOOR
 SETBACK NOT COMPLYING WITH THE VARIANCE GRANTED BY
 RESOLUTION NO. 13-19.
  
 7) THE FOLLOWING ITEMS REQUIRE REVIEW AS SEPARATE
 PERMITS WITH PLANS:
  
 A. THE WALLS, FENCES, GATES AND COLUMNS
 B. HARDSCAPE, INCLUDING PAVERS, ARTIFICIAL TURF, DOG
 PARK ITEMS, BENCHES/PLAZA AREA, ETC.
 C. LANDSCAPE
 D. IRRIGATION
 E. GENERATOR
 F. WATER FEATURES
 G. PARKING STRIPING
 H. SITE LIGHTING, INCLUDING BOLLARDS, NOTE: SINCE
 ACACIA ROAD IS A SEPARATE PARCEL, IT REQUIRES ITS OWN
 PERMIT FOR THE LIGHTING, BUT MAY BE INCLUDED ON ONE SET
 OF PLANS FOR BOTH PERMIT NUMBERS. PHOTOMETRIC PLANS ARE
 REQUIRED WITH THE PERMITS.
 I. BICYCLE RACKS, INCLUDES WITHIN THE BICYCLE STORAGE
 ROOM.
 J. EV CHARGING STATIONS
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2022-07-25 Cont ID  
Sent By eschneid Date 2022-07-25 Time 17:47 Rev Time 2.00
Received By eschneid Date 2022-07-25 Time 14:39 Sent To  
Notes
2022-07-25 17:47:23FAILED
  
 REPEAT COMMENT: PROVIDE WRITTEN RESPONSES TO COMMENTS.
 *** NO WRITTEN RESPONSE PROVIDED.
  
 1) THE PLANS SUBMITTED WITH THIS TOWER PERMIT DO NOT
 MATCH THE PLANS THAT WERE TO BE APPROVED AS PART OF THE
 LATEST MINOR PLANNED DEVELOPMENT AMENDMENT OR THE
 APPROVED FOUNDATION PERMIT. ALL PLANS WILL NEED TO SHOW
 THE LATEST CODE COMPLIANT CONDITIONS AND BE INTERNALLY
 CONSISTENT. DUE TO THE PLAN CHANGES, PLANNING WILL HOLD
 OFF ON THE FORMAL ISSUANCE OF THE MINOR PLANNED
 DEVELOPMENT AMENDMENT UNTIL THE VERTICAL PERMIT PLANS
 ARE APPROVED. AT SUCH TIME, PLANNING WILL REQUEST TWO
 SETS OF THE APPROVED PLANS, INCLUDING AN ELECTRONIC
 COPY, SO THAT THE MINOR PLANNED DEVELOPMENT AMENDMENT
 CAN BE ISSUED.
  
 2) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO.
 13-19, PROVIDE VERIFICATION THAT ALL SURFACES OF THE
 BUILDING'S EXTERIOR FACADE, TO INCLUDE GLAZING, ARE
 DESIGNED OR TREATED TO MINIMIZE THE IMPACTS OF GLARE
 AND REFLECTION OF HIGH INTENSITY LIGHT FROM THE
 BUILDING'S FACADE ONTO SURROUNDING PROPERTIES.
  
 3) REPEAT COMMENT: PROVIDE AN FAA EXTENSION LETTER FOR
 THE BUILDING. THE LETTER THAT STAFF HAS ON FILE EXPIRED
 IN JANUARY 2022.
  
 4) REPEAT COMMENT: SHEET 00.200 REFERENCES SAUNA SQUARE
 FOOTAGE ON THE ROOF LEVEL. ROOFTOP SAUNAS ARE
 CONSIDERED AMENITIES AND ARE NOT PERMITTED TO EXCEED
 THE HEIGHT OF THE ROOF DECK (300 FEET). ALL SAUNA
 REFERENCES AND FACILITIES MUST BE REMOVED FROM THE
 ENTIRE PLAN SET.
  
 5) REPEAT COMMENT: THE SURVEY PROVIDED A S-1-00 IS NOT
 THE LATEST SURVEY THAT WAS SUBMITTED WITH THE
 FOUNDATION PERMIT. THE LATEST, ACCURATE SURVEY IS
 REQUIRED TO BE INCLUDED WITH THE PLANS.
  
 6) REPEAT COMMENT: THE CIVIL PLANS ARE NOT THE VERSION
 THAT WAS SUBMITTED WITH THE APPROVED FOUNDATION PERMIT.
 ALL PERMITS NEED TO INCLUDE THE SAME LATEST, ACCURATE
 PLANS.
  
 7) UPDATED COMMENT: THE PLANS SUBMITTED AS PART OF THE
 MINOR PLANNED DEVELOPMENT AMENDMENT SHOW THE WEST
 SETBACK DIMENSION OF 5 FEET 6 INCHES FOR THE GENERATOR
 PIT, WHICH WAS ALSO REFLECTED ON THE APPROVED
 FOUNDATION PERMIT. THE SHEET 1.100 PROVIDED RECENTLY TO
 PLANNING STAFF SHOWS A SETBACK OF 5 FEET 7 INCHES. THIS
 PERMIT SHOWS A WEST SETBACK OF 5 FEET 3 INCHES (OCCURS
 ON SHEETS A1.100 AND A1.1B1). THE PERMITS AND MINOR
 PLANNED DEVELOPMENT AMENDMENT NEED TO INCLUDE THE SAME
 LATEST, ACCURATE PLANS. NOTE: THE PLAN ORIGINALLY
 APPROVED BY THE CITY COMMISSION SHOWED A SETBACK FOR
 THE GENERATOR PIT OF 5 FEET EVEN.
  
 8) REPEAT COMMENT: SHEET A1.1B1 DOES NOT MATCH THE
 APPROVED FOUNDATION PERMIT RESUBMITTAL. ALL PERMITS
 NEED TO INCLUDE THE SAME LATEST, ACCURATE PLANS. ***
 THE SETBACK DISCREPANCY FROM COMMENT #7 IS ONE EXAMPLE.
  
 9) REPEAT COMMENT: PLEASE EXPLAIN HOW THE BUILDING
 INCREASED FROM A NORTH/SOUTH DIMENSION OF 137 FEET 5
 INCHES ON THE FOUNDATION PLAN TO 137 FEET 9 INCHES ON
 THE TOWER PLAN WITHOUT IMPACTING THE SIDE SETBACKS?
 NOTE THE MINIMUM SETBACKS MUST BE MAINTAINED. SHOWN ON
 SHEET A1.1B1.
  
 10) UPDATED COMMENT: THE ORIGINALLY APPROVED PLANS
 SHOWED THE FIRST FLOOR OF THE BUILDING WITH A FLAT
 EASTERN FACADE. THE MINOR PLANNED DEVELOPMENT AMENDMENT
 SUBMITTAL AND APPROVED FOUNDATION PERMIT LIFE SAFETY
 PLAN SHOW A CURVED EASTERN FACADE. SOME OF THE PLANS
 SUBMITTED WITH THIS PERMIT SHOW THE FLAT EASTERN FACADE
 AGAIN, WHILE OTHERS (EX. PLUMBING). PLEASE CLARIFY
 WHICH VERSION IS CORRECT. ALL PERMITS NEED TO INCLUDE
 THE SAME LATEST, ACCURATE PLANS. IF THE PLAN IS FOR A
 FLAT FACADE, THEN THE FOUNDATION PERMIT SET NEEDS TO BE
 REVISED.
  
 11) REPEAT COMMENT: THE DIMENSION LINES LISTED TO THE
 COLUMNS DO NOT ACTUALLY REACH THE COLUMNS.
  
 12) REPEAT COMMENT: PROVIDE THE SETBACKS FROM THE FACE
 OF GLASS TO THE PROPERTY LINE FOR EACH FLOOR PLAN. THIS
 WAS SHOWN ON THE MINOR PLANNED DEVELOPMENT AMENDMENT
 PLAN.
  
 13) REPEAT COMMENT: THE ELEVATION DRAWINGS DO NOT MATCH
 THE ONES SUBMITTED AS PART OF THE MINOR PLANNED
 DEVELOPMENT AMENDMENT. ALL SUBMITTALS NEED TO INCLUDE
 THE SAME LATEST, ACCURATE PLANS.
  
 14) THE FOLLOWING ITEMS REQUIRE REVIEW AS SEPARATE
 PERMITS WITH PLANS:
  
 A. THE WALLS, FENCES, GATES AND COLUMNS
 B. HARDSCAPE, INCLUDING PAVERS, ARTIFICIAL TURF, DOG
 PARK ITEMS, BENCHES/PLAZA AREA, ETC.
 C. LANDSCAPE
 D. IRRIGATION
 E. GENERATOR
 F. WATER FEATURES
 G. PARKING STRIPING
 H. SITE LIGHTING, INCLUDING BOLLARDS, NOTE: SINCE
 ACACIA ROAD IS A SEPARATE PARCEL, IT REQUIRES ITS OWN
 PERMIT FOR THE LIGHTING, BUT MAY BE INCLUDED ON ONE SET
 OF PLANS FOR BOTH PERMIT NUMBERS. PHOTOMETRIC PLANS ARE
 REQUIRED WITH THE PERMITS.
 I. BICYCLE RACKS, INCLUDES WITHIN THE BICYCLE STORAGE
 ROOM.
 J. EV CHARGING STATIONS
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-05-17 Cont ID  
Sent By eschneid Date 2022-05-17 Time 15:24 Rev Time 2.00
Received By eschneid Date 2022-04-26 Time 17:17 Sent To  
Notes
2022-05-17 15:24:36FAILED
  
 REPEAT COMMENT: PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) THE PLANS SUBMITTED WITH THIS TOWER PERMIT DO NOT
 MATCH THE PLANS THAT HAVE BEEN APPROVED AS PART OF THE
 LATEST MINOR PLANNED DEVELOPMENT AMENDMENT OR THE
 APPROVED FOUNDATION PERMIT. THE REPEAT COMMENTS WILL
 CONTINUE TO BE ISSUED UNTIL THE PLANS ALIGN AND MEET
 ZONING REQUIREMENTS.
  
 2) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO.
 13-19, PROVIDE VERIFICATION THAT ALL SURFACES OF THE
 BUILDING'S EXTERIOR FACADE, TO INCLUDE GLAZING, ARE
 DESIGNED OR TREATED TO MINIMIZE THE IMPACTS OF GLARE
 AND REFLECTION OF HIGH INTENSITY LIGHT FROM THE
 BUILDING'S FACADE ONTO SURROUNDING PROPERTIES.
  
 3) REPEAT COMMENT: IN ACCORDANCE WITH RESOLUTION NO.
 13-19, PROVIDE VERIFICATION THAT THE DEVELOPER HAS
 CONTRACTED WITH AN INDEPENDENT PROFESSIONAL THAT IS
 ACCREDITED IN THE SPECIFIC CERTIFICATION BEING UTILIZED
 TO MEET THIS DEVELOPMENT REGULATION TO ACT AS A GREEN
 DEVELOPMENT REVIEW AGENT TO ENSURE THAT THE BUILDING
 WILL BE CONSTRUCTED IN ACCORDANCE WITH A CERTIFICATION
 PLAN THAT ACHIEVES TO A MINIMUM LEED SILVER LEVEL, OR
 EQUIVALENT GREEN BUILDING STANDARD.
  
 4) REPEAT COMMENT: PROVIDE AN FAA EXTENSION LETTER FOR
 THE BUILDING. THE LETTER THAT STAFF HAS ON FILE EXPIRED
 IN JANUARY 2022.
  
 5) REPEAT COMMENT: SHEET 00.200 REFERENCES SAUNA SQUARE
 FOOTAGE ON THE ROOF LEVEL. ROOFTOP SAUNAS ARE
 CONSIDERED AMENITIES AND ARE NOT PERMITTED TO EXCEED
 THE HEIGHT OF THE ROOF DECK (300 FEET). ALL SAUNA
 REFERENCES AND FACILITIES MUST BE REMOVED FROM THE
 ENTIRE PLAN SET.
  
 6) REPEAT COMMENT: THE SURVEY PROVIDED A S-1-00 IS NOT
 THE LATEST SURVEY THAT WAS SUBMITTED WITH THE
 FOUNDATION PERMIT. THE LATEST, ACCURATE SURVEY IS
 REQUIRED TO BE INCLUDED WITH THE PLANS.
  
 7) REPEAT COMMENT: THE CIVIL PLANS ARE NOT THE LATEST
 VERSION THAT WAS SUBMITTED WITH THE RECENT FOUNDATION
 PERMIT RESUBMITTAL. ALL PERMITS NEED TO INCLUDE THE
 SAME LATEST, ACCURATE PLANS.
  
 8) REPEAT COMMENT: THE PLANS APPROVED AS PART OF THE
 MINOR PLANNED DEVELOPMENT AMENDMENT SHOW THE WEST
 SETBACK DIMENSION OF 5 FEET 6 INCHES FOR THE GENERATOR
 PIT, WHICH WAS ALSO REFLECTED ON THE APPROVED
 FOUNDATION PERMIT. THIS PERMIT SHOWS A 5 FOOT 3 INCH
 WEST SETBACK. ALL PERMITS NEED TO INCLUDE THE SAME
 LATEST, ACCURATE PLANS. (OCCURS ON SHEETS A1.100 AND
 A1.1B1)
  
 9) REPEAT COMMENT: SHEET A1.1B1 IS NOT THE LATEST
 VERSION OF THIS PLAN SUBMITTED WITH THE RECENT
 FOUNDATION PERMIT RESUBMITTAL. ALL PERMITS NEED TO
 INCLUDE THE SAME LATEST, ACCURATE PLANS. *** SEE
 SETBACK COMMENT ABOVE.
  
 10) PLEASE EXPLAIN HOW THE BUILDING INCREASED FROM A
 NORTH/SOUTH DIMENSION OF 137 FEET 5 INCHES ON THE
 FOUNDATION PLAN TO 137 FEET 9 INCHES ON THE TOWER PLAN
 WITHOUT IMPACTING THE SIDE SETBACKS? NOTE THE MINIMUM
 SETBACKS MUST BE MAINTAINED.
  
 11) REPEAT COMMENT: THE GROUND LEVEL BUILDING PLAN DOES
 NOT MATCH THE VERSION APPROVED AS PART OF THE
 FOUNDATION PERMIT (LIFE SAFETY) NOR OF THE PLANS
 APPROVED AS PART OF THE MINOR PLANNED DEVELOPMENT
 AMENDMENT. ALL PERMITS NEED TO INCLUDE THE SAME LATEST,
 ACCURATE PLANS. NOTE: THE DIMENSION LINES LISTED TO THE
 COLUMNS DO NOT ACTUALLY REACH THE COLUMNS.
  
 12) REPEAT COMMENT: PROVIDE THE SETBACKS FROM THE FACE
 OF GLASS TO THE PROPERTY LINE FOR EACH FLOOR PLAN. THIS
 WAS SHOWN ON THE MINOR PLANNED DEVELOPMENT AMENDMENT
 PLAN.
  
 13) REPEAT COMMENT: THE ELEVATION DRAWINGS DO NOT MATCH
 THE ONES APPROVED AS PART OF THE MINOR PLANNED
 DEVELOPMENT AMENDMENT. ALL PERMITS NEED TO INCLUDE THE
 SAME LATEST, ACCURATE PLANS.
  
 14) THE FOLLOWING ITEMS REQUIRE REVIEW AS SEPARATE
 PERMITS WITH PLANS:
  
 A. THE WALLS, FENCES, GATES AND COLUMNS
 B. HARDSCAPE, INCLUDING PAVERS, ARTIFICIAL TURF, DOG
 PARK ITEMS, BENCHES/PLAZA AREA, ETC.
 C. LANDSCAPE
 D. IRRIGATION
 E. GENERATOR
 F. WATER FEATURES
 G. PARKING STRIPING
 H. SITE LIGHTING, INCLUDING BOLLARDS, NOTE: SINCE
 ACACIA ROAD IS A SEPARATE PARCEL, IT REQUIRES ITS OWN
 PERMIT FOR THE LIGHTING, BUT MAY BE INCLUDED ON ONE SET
 OF PLANS FOR BOTH PERMIT NUMBERS. PHOTOMETRIC PLANS ARE
 REQUIRED WITH THE PERMITS.
 I. BICYCLE RACKS, INCLUDES WITHIN THE BICYCLE STORAGE
 ROOM.
 J. EV CHARGING STATIONS
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-02-09 Cont ID  
Sent By av Date 2022-02-09 Time 18:17 Rev Time 5.00
Received By eschneid Date 2022-02-08 Time 11:22 Sent To  
Notes
2022-02-09 18:19:43FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) THE PLAT REQUIRED PRIOR TO BUILDING PERMIT BY
 RESOLUTION NO. 13-19 HAS NOT BEEN RECORDED.
  
 2) IN ACCORDANCE WITH RESOLUTION NO. 13-19, PROVIDE
 VERIFICATION THAT ALL SURFACES OF THE BUILDING'S
 EXTERIOR FACADE, TO INCLUDE GLAZING, ARE DESIGNED OR
 TREATED TO MINIMIZE THE IMPACTS OF GLARE AND REFLECTION
 OF HIGH INTENSITY LIGHT FROM THE BUILDING'S FACADE ONTO
 SURROUNDING PROPERTIES.
  
 3) IN ACCORDANCE WITH RESOLUTION NO. 13-19, PROVIDE
 VERIFICATION THAT THE DEVELOPER HAS CONTRACTED WITH AN
 INDEPENDENT PROFESSIONAL THAT IS ACCREDITED IN THE
 SPECIFIC CERTIFICATION BEING UTILIZED TO MEET THIS
 DEVELOPMENT REGULATION TO ACT AS A GREEN DEVELOPMENT
 REVIEW AGENT TO ENSURE THAT THE BUILDING WILL BE
 CONSTRUCTED IN ACCORDANCE WITH A CERTIFICATION PLAN
 THAT ACHIEVES TO A MINIMUM LEED SILVER LEVEL, OR
 EQUIVALENT GREEN BUILDING STANDARD.
  
 4) PROVIDE AN FAA EXTENSION LETTER FOR THE BUILDING.
 THE LETTER THAT STAFF HAS ON FILE EXPIRED IN JANUARY
 2022.
  
 5) SHEET 00.200 REFERENCES SAUNA SQUARE FOOTAGE ON THE
 ROOF LEVEL. ROOFTOP SAUNAS ARE CONSIDERED AMENITIES AND
 ARE NOT PERMITTED TO EXCEED THE HEIGHT OF THE ROOF DECK
 (300 FEET). ALL SAUNA REFERENCES AND FACILITIES MUST BE
 REMOVED FROM THE ENTIRE PLAN SET.
  
 6) THE SURVEY PROVIDED A S-1-00 IS NOT THE LATEST
 SURVEY THAT WAS SUBMITTED WITH THE FOUNDATION PERMIT.
 THE LATEST, ACCURATE SURVEY IS REQUIRED TO BE INCLUDED
 WITH THE PLANS.
  
 7) THE CIVIL PLANS ARE NOT THE LATEST VERSION THAT WAS
 SUBMITTED WITH THE RECENT FOUNDATION PERMIT
 RESUBMITTAL. ALL PERMITS NEED TO INCLUDE THE SAME
 LATEST, ACCURATE PLANS.
  
 8) THE PLANS APPROVED AS PART OF THE MINOR PLANNED
 DEVELOPMENT AMENDMENT SHOW THE WEST SETBACK DIMENSION
 OF 5 FEET 6 INCHES FOR THE GENERATOR PIT, WHICH WAS
 ALSO REFLECTED ON THE RECENT FOUNDATION PERMIT. THIS
 PERMIT SHOWS A 5 FOOT 3 INCH WEST SETBACK. ALL PERMITS
 NEED TO INCLUDE THE SAME LATEST, ACCURATE PLANS.
  
 9) SHEET A1.1B1 IS NOT THE LATEST VERSION OF THIS PLAN
 SUBMITTED WITH THE RECENT FOUNDATION PERMIT
 RESUBMITTAL. ALL PERMITS NEED TO INCLUDE THE SAME
 LATEST, ACCURATE PLANS.
  
 10) THE GROUND LEVEL BUILDING PLAN DOES NOT MATCH THE
 VERSION SUBMITTED AS PART OF THE FOUNDATION PERMIT NOR
 OF THE PLANS APPROVED AS PART OF THE MINOR PLANNED
 DEVELOPMENT AMENDMENT. ALL PERMITS NEED TO INCLUDE THE
 SAME LATEST, ACCURATE PLANS.
  
 11) PROVIDE THE SETBACKS FROM THE FACE OF GLASS TO THE
 PROPERTY LINE FOR EACH FLOOR PLAN. THIS WAS SHOWN ON
 THE MINOR PLANNED DEVELOPMENT AMENDMENT PLAN.
  
 12) THE ELEVATION DRAWINGS DO NOT MATCH THE ONES
 APPROVED AS PART OF THE MINOR PLANNED DEVELOPMENT
 AMENDMENT. ALL PERMITS NEED TO INCLUDE THE SAME LATEST,
 ACCURATE PLANS.
  
 13) THE BASEMENT PARKING ELECTRIC PLANS DO NOT MATCH
 THE VERSION SUBMITTED AS PART OF THE FOUNDATION PERMIT,
 SPECIFICALLY RELATED TO THE PRE-WIRING OF THE PARKING
 FOR EV. ALL PERMITS NEED TO INCLUDE THE SAME LATEST,
 ACCURATE PLANS.
  
 14) THE FOLLOWING ITEMS REQUIRE REVIEW AS SEPARATE
 PERMITS WITH PLANS:
  
 A. THE WALLS, FENCES, GATES AND COLUMNS
 B. HARDSCAPE, INCLUDING PAVERS, ARTIFICIAL TURF, DOG
 PARK ITEMS, BENCHES/PLAZA AREA, ETC.
 C. LANDSCAPE
 D. IRRIGATION
 E. GENERATOR
 F. WATER FEATURES
 G. PARKING STRIPING
 H. SITE LIGHTING, INCLUDING BOLLARDS, NOTE: SINCE
 ACACIA ROAD IS A SEPARATE PARCEL, IT REQUIRES ITS OWN
 PERMIT FOR THE LIGHTING, BUT MAY BE INCLUDED ON ONE SET
 OF PLANS FOR BOTH PERMIT NUMBERS. PHOTOMETRIC PLANS ARE
 REQUIRED WITH THE PERMITS.
 I. BICYCLE RACKS, INCLUDES WITHIN THE BICYCLE STORAGE
 ROOM.
 J. EV CHARGING STATIONS
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  