2021-08-04 18:16:45 | 08/04/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE PROVIDE DIMENSIONS FOR THE NEW RESTROOM OF |
| THE INSTALLATION OF FIXTURES (TOILET, SHOWER, LAV) |
| SHALL CONFORM TO THE 2020 FBC R 2705.1 GENERAL. |
| |
| 2. THE ISOMERIC DRAWING IS HARD TO READ UNDERSTAND THE |
| LOCATION OR DIRECTION OF CONNECTION POINT IN REFERENCE |
| TO THE DRAINAGE TO THE OUTSIDE OF HOUSE WHICH CONNECT |
| TO THE BUILDING SEWER, PLEASE SHOW CLEANOUT OUTSIDE |
| BUILDING PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.3.5.3 (12) RESIDENTIAL PLUMBING. |
| |
| 3. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM |
| FOR WATER PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.3.5.3 (12) RESIDENTIAL PLUMBING. |
| |
| 4. THE KITCHEN VENT SHOWS A DRY VENT AND NOT REQUIRED. |
| THE VENT IS NOT WASHED BY WATER AND IT MAY CAUSE RODENT |
| OR LEAFS TO SADDLE AT THE BASE OF THE STACK. WE SUGGEST |
| TO ELIMINATE IT TO PREVENT STOPPAGE. |
| |
| 5. THE ISOMETRIC DRAWN HAS A DIFFERENT SIGNATURE FROM |
| THE PLUMBING APPLICATION SO PLEASE HAVE A SIGNATURE ON |
| THE ISOMETRIC DRAWING OF THE PERSON DESIGNING THE |
| SYSTEM, NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE |
| CODE 61G15-23.001, FLORIDA STATUTE 471 PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.1 GENERAL. |
| |
| 6. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED |
| CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC. 109.3 |
| BUILDING PERMIT VALUATIONS. IF IN THE OPINION OF THE |
| BUILDING OFFICIAL, THE CLAIMED VALUATION OF THE |
| BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE |
| UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| DENIED UNLESS THE APPLICANT CAN SHOW DETAILED, QUANTITY |
| ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS (EXCLUDING |
| LAND VALUE) TO MEET THE APPROVAL OF THE BUILDING |
| OFFICIAL. FOR PERMITTING PURPOSES, THE VALUATION OF |
| BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE |
| TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, |
| INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND |
| DESIGN FEES, MARKETING COSTS, OVERHEAD, AND PROFIT; |
| EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY |
| INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE |
| CONGRESS. THE FINAL BUILDING PERMIT VALUATION SHALL BE |
| SET BY THE BUILDING OFFICIAL. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |