Plan Review Details - Permit 21071531
Plan Review Stops For Permit 21071531
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-08-18 Cont ID  
Sent By cthroop Date 2021-08-18 Time 10:21 Rev Time 0.00
Received By cthroop Date 2021-08-18 Time 06:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-11 Cont ID  
Sent By cthroop Date 2021-08-11 Time 11:09 Rev Time 0.00
Received By cthroop Date 2021-08-06 Time 13:51 Sent To  
Notes
2021-08-11 11:13:53PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE AN EXISTING FLOOR PLAN. DOES THE EXISTING
 STORAGE ROOM COMMUNICATE WITH THE HOUSE?
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE DEMENSIONS ON PLANS. IT APPEARS THAT PART OF
 THE STORAGE WILL COMMUNICATE WITH THE CONDITIONED SPACE
 OF THE HOUSE.
 A MECHANICAL REVIEW MAY BE REQUIRED.
 PALM BEACH COUNTY IMPACT FEES MAY APPLY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-08-05 Cont ID  
Sent By jleahy Date 2021-08-05 Time 15:42 Rev Time 0.00
Received By jleahy Date 2021-08-05 Time 15:38 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-08-04 Cont ID  
Sent By lcrespo Date 2021-08-04 Time 17:19 Rev Time 0.00
Received By lcrespo Date 2021-08-04 Time 17:19 Sent To  
Notes
2021-08-04 17:19:53GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-24 Cont ID  
Sent By lcrespo Date 2021-08-24 Time 16:57 Rev Time 0.00
Received By lcrespo Date 2021-08-11 Time 15:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-11 Cont ID  
Sent By cthroop Date 2021-08-11 Time 11:13 Rev Time 0.00
Received By cthroop Date 2021-07-30 Time 06:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-08-24 Cont ID  
Sent By lcrespo Date 2021-08-24 Time 16:50 Rev Time 0.00
Received By lcrespo Date 2021-08-24 Time 16:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-08-04 Cont ID  
Sent By lcrespo Date 2021-08-04 Time 17:18 Rev Time 0.00
Received By lcrespo Date 2021-08-04 Time 17:18 Sent To  
Notes
2021-08-04 18:16:4508/04/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE DIMENSIONS FOR THE NEW RESTROOM OF
 THE INSTALLATION OF FIXTURES (TOILET, SHOWER, LAV)
 SHALL CONFORM TO THE 2020 FBC R 2705.1 GENERAL.
  
 2. THE ISOMERIC DRAWING IS HARD TO READ UNDERSTAND THE
 LOCATION OR DIRECTION OF CONNECTION POINT IN REFERENCE
 TO THE DRAINAGE TO THE OUTSIDE OF HOUSE WHICH CONNECT
 TO THE BUILDING SEWER, PLEASE SHOW CLEANOUT OUTSIDE
 BUILDING PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.3.5.3 (12) RESIDENTIAL PLUMBING.
  
 3. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM
 FOR WATER PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.3.5.3 (12) RESIDENTIAL PLUMBING.
  
 4. THE KITCHEN VENT SHOWS A DRY VENT AND NOT REQUIRED.
 THE VENT IS NOT WASHED BY WATER AND IT MAY CAUSE RODENT
 OR LEAFS TO SADDLE AT THE BASE OF THE STACK. WE SUGGEST
 TO ELIMINATE IT TO PREVENT STOPPAGE.
  
 5. THE ISOMETRIC DRAWN HAS A DIFFERENT SIGNATURE FROM
 THE PLUMBING APPLICATION SO PLEASE HAVE A SIGNATURE ON
 THE ISOMETRIC DRAWING OF THE PERSON DESIGNING THE
 SYSTEM, NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE
 CODE 61G15-23.001, FLORIDA STATUTE 471 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.1 GENERAL.
  
 6. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC. 109.3
 BUILDING PERMIT VALUATIONS. IF IN THE OPINION OF THE
 BUILDING OFFICIAL, THE CLAIMED VALUATION OF THE
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED UNLESS THE APPLICANT CAN SHOW DETAILED, QUANTITY
 ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS (EXCLUDING
 LAND VALUE) TO MEET THE APPROVAL OF THE BUILDING
 OFFICIAL. FOR PERMITTING PURPOSES, THE VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD, AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. THE FINAL BUILDING PERMIT VALUATION SHALL BE
 SET BY THE BUILDING OFFICIAL.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-11 Cont ID  
Sent By cthroop Date 2021-08-11 Time 11:08 Rev Time 0.00
Received By cthroop Date 2021-08-06 Time 13:51 Sent To  
Notes
***NONE***