Plan Review Details - Permit 21071518
Plan Review Stops For Permit 21071518
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-04-10 Cont ID  
Sent By shill Date 2022-04-10 Time 15:57 Rev Time 0.00
Received By shill Date 2022-04-10 Time 15:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-01-19 Cont ID  
Sent By shill Date 2022-01-19 Time 07:00 Rev Time 0.00
Received By shill Date 2022-01-19 Time 07:00 Sent To  
Notes
2022-01-19 07:02:47****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FYI THE MAJORITY OF FILES IN THIS SUBMITTAL HAVE BEEN
 LOCKED AS THEY DO NOT MEET DESIGN PRESSURE
 REQUIREMENTS.
  
 1. FBC B 1609, FROM PREVIOUS LISTS:
  
 MARK PRODUCT APPROVALS TO SHOW OPTION SELECTED, BUT
 OPTIONS MUST MEET THE DESIGN PRESSURES SPECIFIED BY THE
 ENGINEER. NOTE IF THE OPTION IS FOR ZONE 4 OR ZONE 5 AS
 IT APPEARS THAT THERE ARE OPENINGS FOR FIXED, SINGLE
 HUNG, AND SGD IN BOTH ZONES.
  
 2. SEE SGD FL251-R33, IT IS NOT CLEAR WHAT DESIGN
 PRESSURE OPTION IS PROPOSED AND NONE MEET THE
 REQUIREMENT FOR ZONE 5. PRESSURES REQUIRED PER
 ENGINEER:
  
 ZONE 4 +59.79/-62.18
 ZONE 5 +56.01/-93.54
  
 OPTIONS ON PAGES 6 AND 7 HAVE DP LIMITATION OF +-60,
 OPTIONS ON PAGE 8 HAVE DP LIMITATION OF +-90, SEE ALSO
 TABLE 1A, 2A, 3A.
  
 2. SEE FIXED WINDOW FL26095, SHEET 4 OF 5 HAS +55/-59.3
 HIGHLIGHTED. THIS DOES NOT MEET PRESSURES REQUIRED BY
 THE ENGINEER:
  
 ZONE 4 +62.01/-66.97
 ZONE 5 +66.97/-122.79
  
 3. SINGLE HUNG FL9064 APPEARS OK.
  
 4. IT APPEARS THAT MULLIONS ARE REQUIRED, BUT HAVE NOT
 BEEN SUBMITTED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-11-01 Cont ID  
Sent By shill Date 2021-11-01 Time 14:39 Rev Time 0.00
Received By shill Date 2021-11-01 Time 14:39 Sent To  
Notes
2021-11-01 15:00:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, FROM PREVIOUS LIST:
  
 MARK PRODUCT APPROVALS TO SHOW OPTION SELECTED, BUT
 OPTIONS MUST MEET THE DESIGN PRESSURES SPECIFIED BY THE
 ENGINEER. NOTE IF THE OPTION IS FOR ZONE 4 OR ZONE 5 AS
 IT APPEARS THAT THERE ARE OPENINGS FOR FIXED, SINGLE
 HUNG, AND SGD IN BOTH ZONES.
  
 2ND REVIEW - THE SGD PRODUCT APPROVAL IS NOT MARKED. A
 NEW PRODUCT APPROVAL WAS UPLOADED NOTHING IS MARKED.
  
 FIXED WINDOW OPTION OK FOR THE MOST CURRENT DOCUMENT
 UPLOADED ON 10/21 BUT THE PRODUCT APPROVAL UPLOADED
 (NAMED NOA.PDF) IS INCOMPLETE; IT IS MISSING THE FIRST
 PAGE. THERE ARE TWO OTHER DOCUMENTS FOR A FIXED WINDOW
 NAMED "NOA FIXED.PDF" AND "PRODUCT APPROVAL - WINDOWS
 FIXED FL26095-R3.PDF" AND "PRODUCT APPROVAL.PDF". IT IS
 NOT CLEAR WHICH OF THE THREE IS PROPOSED; PLEASE ADVISE
 WHICH THREE SHOULD BE DELETED. IT APPEARS THAT
 "NOA.PDF" IS THE MOST CURRENT DOCUMENT AND THE OTHER
 THREE SHOULD BE DELETED, PLEASE CONFIRM.
  
 IT DOES NOT APPEAR A NEW PRODUCT APPROVAL FOR SINGLE
 HUNG WINDOW WAS NOT SUBMITTED.
  
 2. SEE SHEET A1.0, ALUMINUM WINDOWS AND SGD ARE
 PROPOSED, BUT VINYL PRODUCT APPROVALS WERE SUBMITTED.
 REVISE. THE SCHEDULE DOES NOT APPEAR TO CORRELATE WITH
 THE PRODUCT APPROVAL SUBMITTED, PLEASE ADVISE WHICH
 PRODUCT APPROVALS SHOULD BE DELETED. THERE SHOULD BE
 THREE PRODUCT APPROVALS (SGD, FIXED, S/H) BUT 8 WERE
 UPLOADED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-15 Cont ID  
Sent By shill Date 2021-09-15 Time 17:19 Rev Time 0.00
Received By shill Date 2021-09-15 Time 17:19 Sent To  
Notes
2021-09-15 17:20:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 PLAN REVIEW IN PROGRESS
  
 1. FBC B 1609, ENGINEER'S CALCULATIONS ARE VERY LENGTHY
 AND COMPLIANCE IS NOT CLEAR, DESIGN PRESSURES ON A1 DO
 NOT ALWAYS CORRELATE WITH THE ENGINEER'S CALCULATIONS.
 SEE PAGE 7-8 OF CALCULATIONS. A1.0 SHOWS ZONE 4 AS
 +66.97/-66.97, ENGINEER'S CALCS SHOW +62.01/-66.97.
  
 THE PRODUCT APPROVALS ARE NOT MARKED AS TO OPTIONS
 PROPOSED.
  
 THE FIXED PRODUCT APPROVAL FL 26095 OPTION ON DRAWING
 SHEET 4 OF 5 FOR OPTION MEETING DESIGN PRESSURE OF
 +55/-59.3, BUT DESIGN PRESSURES FOR ZONE 4 ARE HIGHER
 THAN THAT PER ENGINEERING.
  
 TO RESOLVE:
  
 CONFIRM THAT ALL DESIGN PRESSURES IN THE CALCULATIONS
 EXACTLY CORRELATE WITH THOSE SHOWN ON A1.0
 MARK PRODUCT APPROVALS TO SHOW OPTION SELECTED, BUT
 OPTIONS MUST MEET THE DESIGN PRESSURES SPECIFIED BY THE
 ENGINEER. NOTE IF THE OPTION IS FOR ZONE 4 OR ZONE 5 AS
 IT APPEARS THAT THERE ARE OPENINGS FOR FIXED, SINGLE
 HUNG, AND SGD IN BOTH ZONES.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-04-10 Cont ID  
Sent By shill Date 2022-04-10 Time 15:57 Rev Time 0.00
Received By shill Date 2022-03-15 Time 07:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-19 Cont ID  
Sent By shill Date 2022-01-19 Time 07:34 Rev Time 0.00
Received By shill Date 2021-12-09 Time 07:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-01 Cont ID  
Sent By shill Date 2021-11-01 Time 15:01 Rev Time 0.00
Received By shill Date 2021-10-22 Time 09:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-15 Cont ID  
Sent By shill Date 2021-09-15 Time 18:17 Rev Time 0.00
Received By shill Date 2021-09-13 Time 14:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-04-10 Cont ID  
Sent By shill Date 2022-04-10 Time 15:57 Rev Time 0.00
Received By shill Date 2022-04-10 Time 15:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-01-19 Cont ID  
Sent By shill Date 2022-01-19 Time 07:34 Rev Time 0.00
Received By shill Date 2022-01-19 Time 07:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-11-01 Cont ID  
Sent By shill Date 2021-11-01 Time 15:01 Rev Time 0.00
Received By shill Date 2021-11-01 Time 15:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-09-15 Cont ID  
Sent By shill Date 2021-09-15 Time 18:14 Rev Time 0.00
Received By shill Date 2021-09-15 Time 18:14 Sent To  
Notes
2021-09-15 18:17:06SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 CALCULATIONS OK (DIGITALLY SIGNED BY ENGINEER)
 DRAWING PAGE 1.0 PREPARED BY MANUEL SIQUES, PE HAS A
 SCAN OF THE ENGINEER'S SIGNATURE AND SEAL.
 DEMO PLAN WILL NOT BE ISSUED; PREPARED BY ENGINEER BUT
 SHOWS WORK NOT IN THIS SCOPE. DEMO PLAN NOT NEEDED FOR
 A WINDOW PERMIT.
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A SIGNED
 PLAN IS NOT CONSIDERED AN ORIGINAL.
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION.
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
  