Plan Review Stops For Permit 21071362 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-07-30 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2021-07-30 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2021-07-30 |
Time |
16:23 |
Sent To |
|
|
Notes |
2021-07-30 16:56:52 | ****CORRECTIONS**** | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | BUILDING REVIEW DENIED: | | | | FBC B 107.2.1, PLEASE RE-EVALUATE THE OPENING SCHEDULE | | AND IDENTIFIED AREAS OF THE PRODUCT APPROVAL. THE | | STRUCTURE TO RECEIVE SHUTTERS, FRONT AND BACK SIDES, | | APPEARS TO BE FRAMED WITH METAL STUDS. PLEASE CONFIRM, | | AS OUR RECORDS SHOW THE WHITE HALL BUILDINGS WERE BUILT | | WITH CONCRETE ON SIDES AND INNER WALLS BUT FRONT AND | | BACK WALLS WERE CONSTRUCTED OF METAL STUD MATERIAL. |
|
|