Plan Review Stops For Permit 21071189 |
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
P |
Date |
2021-08-26 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-08-26 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-08-26 |
Time |
15:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2021-08-10 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-08-10 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-08-10 |
Time |
14:11 |
Sent To |
|
|
Notes |
2021-08-10 14:12:41 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | CAN BE FOUND ON THEIR WEBSITE: | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2021-08-26 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-08-26 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-08-26 |
Time |
15:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-08-10 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-08-10 |
Time |
14:12 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-08-10 |
Time |
14:08 |
Sent To |
|
|
Notes |
2021-08-10 14:17:20 | CONDO REMODEL | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - | | | | 1) THE TEST REPORTS PROVIDED INCLUDE A DROP CEILING AS | | PART OF THE ASSEMBLY THAT WAS TESTED - MOST UNITS DO | | NOT HAVE A DROP CEILING WITH INSULATION - PLEASE | | PROVIDE TEST REPORTS THAT INCLUDE ONLY THE CONCRETE | | SLAB, UNDERLAYMENT AND THE TILE - | | | | THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: | | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. | | PROVIDE A COPY OF THE TEST REPORT. | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. | | | | 2). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO | | VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING | | TO PROJECTDOX ( [email protected] ) | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2021-08-06 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-08-06 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-08-06 |
Time |
16:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2021-07-27 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2021-07-27 |
Time |
|
Rev Time |
0.00 |
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2021-07-27 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-07-27 |
Time |
16:27 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-07-27 |
Time |
16:27 |
Sent To |
|
|
Notes |
2021-07-27 16:28:36 | GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN | | THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN | | PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS | | WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE | | RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT | | REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER | | THE WPB AMENDMENTS TO FBC SEC. 107.2.1. | | | | A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR | | FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC | | SEC. 105.1. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-08-26 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-08-26 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-08-24 |
Time |
07:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-08-10 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-08-10 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-07-26 |
Time |
13:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2021-08-09 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-08-09 |
Time |
10:38 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-08-09 |
Time |
10:38 |
Sent To |
|
|
Notes |
2021-08-09 10:40:25 | THE MECHANICAL UNIT IS EXISTING AND THIS PERMIT IS FOR | | CHANGING OF THE DUCTWORK ONLY. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2021-07-27 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-07-27 |
Time |
16:03 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-07-27 |
Time |
16:03 |
Sent To |
|
|
Notes |
2021-07-27 16:04:06 | 07/27/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2021-07-27 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-07-27 |
Time |
12:59 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-07-27 |
Time |
12:59 |
Sent To |
|
|
Notes |
2021-07-27 13:02:45 | ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO | | STORAGE.ME |
|
|