Plan Review Details - Permit 21071035
Plan Review Stops For Permit 21071035
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-07-27 Cont ID  
Sent By cpuell Date 2021-07-27 Time 16:45 Rev Time 0.00
Received By cpuell Date 2021-07-27 Time 16:44 Sent To  
Notes
2021-07-27 16:46:02THIS ADDRESS IS CORRECT AS LONG AS THE RESTRAUNT ITS
 REPLACING IS BROTHER JIMMYS BBQ, IF NOT PLEASE CONTACT
 [email protected] OR CALL 561-805-6659

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-08-31 Cont ID  
Sent By lmarchan Date 2021-08-31 Time 10:40 Rev Time 0.00
Received By lmarchan Date 2021-08-31 Time 10:40 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-08-13 Cont ID  
Sent By rmcphers Date 2021-08-13 Time 13:08 Rev Time 0.00
Received By rmcphers Date 2021-08-13 Time 07:37 Sent To  
Notes
2021-08-13 13:08:39PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-10-07 Cont ID  
Sent By rmcphers Date 2021-10-07 Time 07:50 Rev Time 0.00
Received By rmcphers Date 2021-10-07 Time 07:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-10-06 Cont ID  
Sent By rmcphers Date 2021-10-06 Time 14:43 Rev Time 0.00
Received By rmcphers Date 2021-10-06 Time 14:10 Sent To  
Notes
2021-10-06 14:42:34RESTAURANT BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A602 - ACCESSIBLE BAR AREA - THE FOOT RAIL
 SHOWN ON THE "ACCESSIBLE BAR SECTION" WILL NOT COMPLY
 WITH THE REQUIRED TOE CLEARANCE PER FBC A 306.2.2
 MAXIMUM DEPTH.
 TOE CLEARANCE SHALL EXTEND 25 INCHES (635 MM) MAXIMUM
 UNDER AN ELEMENT.
  
 2) ACCESSIBLE RESTROOM - TO AVOID MISPLACEMENT OF THE
 FRAMED MIRROR - PLEASE STATE THAT THE HEIGHT FROM THE
 FINISHED FLOOR TO THE BOTTOM OF THE OF THE MIRROR IS TO
 THE"REFLECTIVE SURFACE" FBC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-09-20 Cont ID  
Sent By rmcphers Date 2021-09-20 Time 13:43 Rev Time 0.00
Received By rmcphers Date 2021-09-20 Time 13:13 Sent To  
Notes
2021-09-20 13:24:28RESTAURANT BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A COMPLETE PRODUCT APPROVAL FOR THE
 SWING DOORS. STORE FRONT DOORS ARE NOT PART OF THE
 PRODUCT APPROVAL (FL14218) FOR THE STOREFRONT WINDOWS.
  
 2) DRAWING A602 HAS NOT BEEN REVISED - THE ACCESSIBLE
 BAR COUNTER CANNOT BE PORTABLE AS SHOWN ON DRAWING A602
 DETAIL 2. (PER THE BUILDING OFFICIALS INTERPRETATION)
 FBC A902
  
 3) REVISED DRAWING A601 IS VERSIONED ON TOP OF A602 IN
 PROJECTDOX - PLEASE CORRECT
  
 4) PLEASE SHOW THE KNEE AND TOE CLEARANCE FOR THE
 ACCESSIBLE SEATING AT THE BARS PER FBC 902.2
  
 5) ACCESSIBLE RESTROOM - PLEASE SHOW THE HEIGHT FROM
 THE FINISHED FLOOR TO THE BOTTOM OF THE "REFLECTIVE
 SURFACE" OF THE MIRROR FBC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 6) ACCESSIBLE RESTROOM - PLEASE SHOW THE PAPER TOWEL
 DISPENSER OUTLET HEIGHT FROM THE FLOOR TO COMPLY WITH
 FBC 308
  
 7) ACCESSIBLE RESTROOM - PLEASE SHOW THE REAR TOILET
 GRAB BAR DIMENSIONS FROM THE CENTER OF THE TOILET PER
 FBC 604.5.2
  
 8) PLEASE SHOW THE CLEAR RAMP LANDING LENGTH (5') AT
 THE TOP OF THE REAR ACCESSIBLE RAMP FBC 405.7
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-13 Cont ID  
Sent By rmcphers Date 2021-08-13 Time 13:00 Rev Time 0.00
Received By rmcphers Date 2021-08-13 Time 07:37 Sent To  
Notes
2021-08-13 12:59:37RESTAURANT BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) DRAWING A251 SHOWS THE EGRESS DOOR SIZING
 INCORRECTLY - SHOULD BE (271 X .15) PER FBC 1005.3.2
 2) DRAWING A601 DETAIL 12, 13, 10 AND 18 - HANDRAIL
 EXTENSIONS AT THE BOTTOM OF THE STAIRS SHOULD CONTINUE
 TO SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER. PER FBC 1014.6
 3) PLEASE SHOW ALL HANDRAIL EXTENSIONS AT STAIRS AND
 RAMPS TO RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE. FBC 1014.6
 4) THE HANDRAIL EXTENSIONS FOR STAIRS AND RAMPS WHERE
 THE STAIR OR RAMP DOES NOT CONTINUE SHOULD BE SHOWN TO
 EXTEND OUT FROM THE STAIR OR RAMP NOT END OR TURN
 AROUND THE CORNER PER FBC 1014.6
 5) PLEASE SHOW THE WALL AND CEILING FINISHES FIRE
 CLASSIFICATION PER FBC 803.1
 6) PLEASE SHOW THAT THE REQUIRED FIRE PROTECTION AND
 HOURLY RATINGS FOR THE STEEL JOIST AND COLUMNS EXISTING
 OR NEW TO COMPLY WITH FBC 601 FOR CONSTRUCTION TYPE
 IIIA.
 7) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE DESIGNER OF RECORD FBC WPB 107.2.1
 8) PLEASE PROVIDE A COMPLETE PRODUCT APPROVAL FOR THE
 SWING DOORS.
 9) PRODUCT APPROVAL FOR THE STOREFRONT WINDOWS
 (FL14218) - PLEASE PROVIDE THE FRONT PAGE OF THE
 FLORIDA PRODUCT APPROVAL (THE INSTALLATION INSTRUCTIONS
 HAVE BEEN PROVIDED).
 10) THE ACCESSIBLE BAR COUNTER CANNOT BE PORTABLE AS
 SHOWN ON DRAWING A602 DETAIL 2. (PER THE BUILDING
 OFFICIALS INTERPRETATION) FBC A902
 11) PLEASE SHOW THE KNEE AND TOE CLEARANCE FOR THE
 ACCESSIBLE SEATING AT THE BARS PER FBC 902.2
 12) ACCESSIBLE RESTROOM - PLEASE SHOW THE HEIGHT FROM
 THE FINISHED FLOOR TO THE BOTTOM OF THE "REFLECTIVE
 SURFACE" OF THE MIRROR FBC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 13) ACCESSIBLE RESTROOM - PLEASE SHOW THE PAPER TOWEL
 DISPENSER OUTLET HEIGHT FROM THE FLOOR TO COMPLY WITH
 FBC 308
 14) ACCESSIBLE RESTROOM - PLEASE SHOW THE REAR TOILET
 GRAB BAR DIMENSIONS FROM THE CENTER OF THE TOILET PER
 FBC 604.5.2
 15) ACCESSIBLE RESTROOM - PLEASE SHOW THE DOOR
 MANEUVERING CLEARANCE TO EXIT THE RESTROOM (18" BESIDE
 THE DOOR) PER FBC 404
 16) PLEASE SHOW THE CLEAR RAMP LANDING LENGTH (5') AT
 THE TOP OF THE REAR ACCESSIBLE RAMP FBC 405.7
 17) PLEASE PROVIDE THE DETAILS (SHOP DRAWINGS) FOR THE
 RAILINGS, ROLLDOWN SHADES, LOUVERED CANOPY SYSTEM ETC.
 - PLEASE LIST ITEMS TO BE DEFERRED ON THE DRAWINGS FBC
 WPB 107.3.4.1
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-09-22 Cont ID  
Sent By jleahy Date 2021-09-22 Time 13:34 Rev Time 0.00
Received By jleahy Date 2021-09-21 Time 15:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-08-13 Cont ID  
Sent By jleahy Date 2021-08-13 Time 08:37 Rev Time 0.00
Received By jleahy Date 2021-08-13 Time 08:37 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2021-07-28 Cont ID  
Sent By mGONZALE Date 2021-07-28 Time   Rev Time 0.00
Received By mgonzale Date 2021-07-28 Time   Sent To Z
Notes
2021-07-28 16:03:53SEWER CONNECTION IN THE ROW WILL BE SUBMITTED AND
 INSPECTED THRU ENGINEERING SERVICES DUE TO EASEMENTS.
 THANK YOU MANNY GONZALEZ (561) 818-1322
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-09-09 Cont ID  
Sent By pleduc Date 2021-09-09 Time   Rev Time 0.00
Received By pleduc Date 2021-09-09 Time 11:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-08-05 Cont ID  
Sent By pleduc Date 2021-08-05 Time   Rev Time 0.00
Received By pleduc Date 2021-07-28 Time 16:20 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-09-22 Cont ID  
Sent By lcrespo Date 2021-09-22 Time 15:03 Rev Time 0.00
Received By lcrespo Date 2021-09-22 Time 08:31 Sent To  
Notes
2021-09-22 15:38:2609/22/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-08-24 Cont ID  
Sent By lcrespo Date 2021-08-24 Time 09:28 Rev Time 0.00
Received By lcrespo Date 2021-08-24 Time 08:01 Sent To  
Notes
2021-08-24 09:28:4808/24/21 2ND LP GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P6.1;
 A. WOULD YOU PLEASE SHOW THE LENGTH OF ALL CUT SECTIONS
 OF PIPE PER 2020 FBC FG SECS. 402.4.1, 402.4.2.
  
 B. THE REFERENCE CODE IS SHOWING 2017, AND THE CURRENT
 IS 2020. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 C. WOULD YOU PLEASE SHOW THE TYPE OF GAS (LP OR
 NATURAL) PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. MOST TANK-LESS UNITS CALL FOR A 10.5 INCHES WATER
 COLUMN, AND THE SERVICE METER DISCHARGES IS A 12 INCH
 WATER COLUMN REQUIRING A REGULATOR FOR THIS UNIT AS PER
 THE MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. 410.1.
  
 E. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF, AND ANCHORING
 DETAILS OF THE GAS VENT(S) FOR TANK-LESS PER THE 2020
 FBC FG SECS. 502 THRU 505.
  
 F. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC FG SEC.
 305.1.
  
 G. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1' (FOOT) OF EITHER SIDE PER THE 2020 FBC FG
 SEC 410.2.
  
 H. WOULD YOU PLEASE LABEL AND SHOW DRIP LEG IS REQUIRED
 BEFORE THE EQUIPMENT IS INSTALLED AT TWO POINTS PER THE
 2020 FBC FG 408.2 OR 2020 FBC RES. SEC. G2419.2.
  
 I. THE EMERGENCY HOOD SHUT DOWN SHUTOFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWNSTREAM OF MANUAL VALVE. SECS.
 10.4, 10.5 OF NFPA 96-08.
  
 K. THERE IS A SECTION OF PIPE THAT DOES NOT HAVE SIZE.
 IS IT 1 1/4 INCHES OR 1 1/2 INCHES? WOULD YOU PLEASE
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-10-06 Cont ID  
Sent By rmcphers Date 2021-10-06 Time 14:52 Rev Time 0.00
Received By rmcphers Date 2021-09-28 Time 08:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-09-22 Cont ID  
Sent By lcrespo Date 2021-09-22 Time 15:38 Rev Time 0.00
Received By lcrespo Date 2021-09-08 Time 12:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-31 Cont ID  
Sent By lmarchan Date 2021-08-31 Time 10:40 Rev Time 0.00
Received By lmarchan Date 2021-08-26 Time 15:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-24 Cont ID  
Sent By lcrespo Date 2021-08-24 Time 09:31 Rev Time 0.00
Received By lcrespo Date 2021-07-27 Time 13:04 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-08-13 Cont ID  
Sent By rmcphers Date 2021-08-13 Time 13:08 Rev Time 0.00
Received By rmcphers Date 2021-08-13 Time 13:08 Sent To  
Notes
2021-08-13 13:09:49RESTAURANT TO RESTAURANT - NO CHANGE OF OCCUPANCY
 CLASSIFICATION

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-09-20 Cont ID  
Sent By medwards Date 2021-09-20 Time 08:26 Rev Time 0.00
Received By medwards Date 2021-09-20 Time 08:26 Sent To  
Notes
2021-09-20 08:29:02APPROVED WITH PRIVISO: THE NEW MAKE UP AIR UNITS ARE
 NOT LISTED ON THE MECHANICAL SCHEDULE SHEET. THESE NEW
 UNITS WILL NEED TO BE SUBMITTED WITH THE KITCHEN HOODS
 SUBMITTAL. THEY MUST MEET MAKE UP AIR TEMPERATURE PER
 FBC M 508.1.1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-08-28 Cont ID  
Sent By medwards Date 2021-08-28 Time 07:50 Rev Time 0.00
Received By medwards Date 2021-08-28 Time 07:50 Sent To  
Notes
2021-08-28 07:52:33THERE IS NO REAPONSE LETTER OR REVISED MECHANICAL
 DRAWINGS SUBMITTED FOR THIS CYCLE OF REVIEW. PLEASE
 PROVIDE A RESPONSE LETTER AND REVISED DRAWINGS
 ADDRESSING THE 1ST CYCLE COMMENTS LISTED BELOW.
  
 1ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21071035
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE
 HOODS WILL REQUIRE A SEPARATE APPLICATION, REVIEW AND
 DRAWINGS. THE HOODS WILL NOT BE REVIEWED UNDER THIS
 PERMIT.
  
 2) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE
 REFRIGERATION WILL REQUIRE A SEPARATE APPLICATION,
 REVIEW AND DRAWINGS. THE REFRIGERATION WILL NOT BE
 REVIEWED UNDER THIS PERMIT.
  
 3) SHEET M2.2: IT APPEARS THAT THE ROOM LABELED CLOSET
 IS BEING USED FOR A RETURN AIR PATH. RETURN AIR SHALL
 NOT BE TAKEN FROM A CLOSET. FBC M 601.5 (7)
  
 4) PLEASE PROVIDE A MECHANICAL FLOOR PLAN FOR THE
 RESTAURANT. FBC 107.2.1
  
 5) THE MINIMUM REQUIRED OUTDOOR AIR FOR THE DINING ROOM
 IS 2504 CFM; THE KITCHEN MINIMUM OUTDOOR AIR IS 434
 CFM. FBC 403.3.1.1 AND TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-16 Cont ID  
Sent By medwards Date 2021-08-16 Time 07:49 Rev Time 0.00
Received By medwards Date 2021-08-16 Time 07:49 Sent To  
Notes
2021-08-16 07:50:231ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21071035
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE
 HOODS WILL REQUIRE A SEPARATE APPLICATION, REVIEW AND
 DRAWINGS. THE HOODS WILL NOT BE REVIEWED UNDER THIS
 PERMIT.
  
 2) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE
 REFRIGERATION WILL REQUIRE A SEPARATE APPLICATION,
 REVIEW AND DRAWINGS. THE REFRIGERATION WILL NOT BE
 REVIEWED UNDER THIS PERMIT.
  
 3) SHEET M2.2: IT APPEARS THAT THE ROOM LABELED CLOSET
 IS BEING USED FOR A RETURN AIR PATH. RETURN AIR SHALL
 NOT BE TAKEN FROM A CLOSET. FBC M 601.5 (7)
  
 4) PLEASE PROVIDE A MECHANICAL FLOOR PLAN FOR THE
 RESTAURANT. FBC 107.2.1
  
 5) THE MINIMUM REQUIRED OUTDOOR AIR FOR THE DINING ROOM
 IS 2504 CFM; THE KITCHEN MINIMUM OUTDOOR AIR IS 434
 CFM. FBC 403.3.1.1 AND TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-09-22 Cont ID  
Sent By lcrespo Date 2021-09-22 Time 15:37 Rev Time 0.00
Received By lcrespo Date 2021-09-22 Time 08:31 Sent To  
Notes
2021-09-22 15:38:0509/22/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-08-23 Cont ID  
Sent By lcrespo Date 2021-08-23 Time 18:04 Rev Time 0.00
Received By lcrespo Date 2021-08-16 Time 18:16 Sent To  
Notes
2021-08-23 18:04:3308/23/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON A001, UNDER GENERAL NOTES, # 1 HAS 2017, AND IT
 SHOULD BE 2020 PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. ON SHEET A003;
  
 A. THE REFLECTIVE PART OF THE MIRROR NEEDS TO BE 4
 INCHES TO THE REFLECTIVE SIDE PER THE 2020 FBC ACC SEC.
 603.3.
  
 B. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER THE 2020 FBC ACC SEC. 609.4.
  
 C. THE TOILET PAPER DISPENSERS SHALL BE 7 INCHES
 MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER PER
 THE 2020 FBC ACC SEC. 604.7.
  
 D. WOULD YOU, PLEASE SHOW THE 30 INCHES BY 48 INCHES
 INSIDE THE RUNNING RADIUS PER THE 2020 FBC ACC SEC. 305
 CLEAR FLOOR OR GROUND SPACE.
  
 3. ON SHEET A150, UNDER GENERAL DEMOLITION NOTES, # 2
 HAS 2017, AND IT SHOULD BE 2020 PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. ON SHEETS A201 A251 AND A 801; THE STALL IN THE
 WOMEN AND MEN'S RESTROOM DOES NOT SHOW A WATER CLOSET;
  
 A. PLEASE PROVIDE THE CLEAR FLOOR SPACE FOR THE TOILET
 THAT WILL BE IN THE TOILET STALL, URINAL, AND LAVS
 OUTSIDE STALL PER THE FLORIDA BUILDING CODE AND FLORIDA
 ACCESSIBILITY CODE.
  
 B. PLEASE SHOW ALL CLEAR FLOOR SPACE DIMENSIONS PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS AND 2020 FBC ACC SEC. 606.2. 2
 CLEAR FLOOR SPACE.
  
 5. ON SHEET A250, UNDER PLUMBING FIXTURES TABLE 2017,
 IT SHOULD BE 2020 PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 THERE ARE TWO OR MORE LOCATIONS WITH 2017 ON AS WELL.
  
 6. ON SHEET A801;
 A. ON FIXTURE ELEVATION, THE TOILET SHALL BE 1 FOOT 6
 INCHES TO 1 FOOT 8 INCHES AND ONLY 1 FOOT 6 INCHES
 SHOW. WOULD YOU PLEASE ADD THE VARIANCE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. THE WATER CLOSET IN THE BACK WALL GRAB BAR SHALL BE
 1 INCHES FROM THE CENTER OF THE WATER CLOSET TO THE
 SIDE OF THE GRAB BAR AND 2 FEET TO THE OTHER SIDE PER
 THE 2020 ACC 604.5.2 REAR WALL.
  
 C. WOULD YOU PLEASE SHOW THE BOTTOM ON THE LAV, WHICH
 SHALL BE A MINIMUM OF 27 INCHES KNEE CLEARANCE PER THE
 2020 FBC SEC. 306.3.
  
 D. THE WATER CLOSET CONTROL FLUSH SHALL BE ON THE OPEN
 SIDE CONTROL PER THE 2020 FBC SEC. 604.6 FLUSH
 CONTROLS.
  
 E. HANDICAP CAP WATER CLOSET FLUSH CONTROL SHALL BE
 HAND OPERATED OR AUTOMATIC AND SHALL BE 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND ON THE OPEN SIDE PER
 THE 2020 FBC ACC SEC. 604.9.5.
  
 F. WOULD YOU, PLEASE SHOW THE CLEAR FLOOR SPACE SHALL
 BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE
 SIDEWALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR
 FROM THE REAR WALL PER THE 2020 FBC ACC. SEC. 604.3.1.
  
 G. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT PER THE 2020 FBC ACC SEC. 606.5.
  
 H. PLEASE SHOW OR MENTION THAT THE DOOR HANDLE HARDWARE
 SHOULD BE ON BOTH SIDES OF THE DOOR PER THE 2020 FBC
 ACC SEC. 404.2.7.
  
 I. WOULD YOU PLEASE SHOW THE HEIGHT OF THE PARTITION OF
 THE URINAL PER THE 2020 FBC SEC. P 405.3.5.
  
 J. WOULD YOU PLEASE SHOW THE HEIGHT OF THE LAV IN THE
 OPEN AREA AT 34 INCHES MAXIMUM PER THE 2020 FBC ACC
 SEC. 606.3.
  
 K. WOULD YOU, PLEASE SHOW THE MIRROR'S REFLECTIVE PART,
 WHICH NEEDS TO BE 4 INCHES TO THE REFLECTIVE SIDE PER
 THE 2020 FBC ACC SEC. 603.3.
  
 L. WATER CLOSET COMPARTMENT SHALL BE LOCATED IN THE
 CORNER, DIAGONAL TO THE DOOR 604.8.1.7 WATER CLOSET.
  
 7. ON SHEET P.01;
 A.. UNDER PLUMBING NOTES 31, IT HAS THE 6 TH EDITION
 MENTION. THE 7 TH EDITION IS THE CORRECT ONE. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET?
  
 C. ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN
 IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER
 THE 2020 FBC SEC. 608.13.10.
  
 D. SODA MACHINES SHALL BE EQUIPPED WITH AN IN-LINE
 VACUUM BREAKER THAT COMPLIES WITH ASSE 1022 PER THE
 2020 FBC SEC. 608.17.1.1.
  
 E. WOULD YOU PLEASE DELETE OR STRIKE THROUGH THE
 ECLECTIC WATER COOLER WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. ON SHEET P0.2;
 A. WOULD YOU PLEASE PROVIDE DETAIL FOR THE FOOD
 HANDLING THREE-COMPARTMENT W/AIR GAP PER THE 2020 FBC
 SEC. P 802.1.1.
  
 B. THE GAS DETAIL SHOWS A CONDENSATE NEUTRALIZER THAT
 IS NOT PERMITTED PER THE AJH IN THE CITY OF WEST PALM
 BEACH AS IT IS NEVER KEPT OR MAINTAINED. WOULD YOU
 PLEASE SHOW WHERE THE CONDENSATE WILL DRAIN AND PLEASE
 SEPARATE CONDENSATE TO DUMP TO A LOCATION IN A SAFE
 PLACE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. WOULD YOU PLEASE SHOW ON THIS PAGE THE ISOMETRIC THE
 SHUT OFF VALVES ON EACH SIDE OF THE RECALCULATING PUMP
 PER THE 2020 FBC SEC. 606.2 LOCATION OF SHUTOFF VALVES.
  
 9. ON SHEET P2-1 AND P3-1;
 A. IN THE BAR AREA SHOWS BAR SINKS AND ICE MACHINES
 INTO THE GREASE INTERCEPTOR THAT IS NOT WASTER AND DO
 NOT REQUIRE TREATMENT AND ARE NOT APPROVED PER THE 2020
 FBC SEC. P1003.2.
  
 B. IN THE RESTAURANT OTHER THAN THE BAR AREA, THERE ARE
 SEVERAL HAND SINKS K 15, B16, B46, K87, AND ICE
 BIN/CUBER K38, B10, AND B4 INTO THE GREASE INTERCEPTOR
 THAT ARE NOT WASTER AND DO NOT REQUIRE TREATMENT, AND
 ARE NOT APPROVED PER THE 2020 FBC SEC. P1003.2.
  
 C. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET?
  
 D. SODA DRINKING BEVERAGE MACHINES SHALL BE PROTECTED
 WITH A DEVICE THAT COMPLIES WITH ASSE 1022 SHALL HAVE
 CARBONATED DISCHARGED TO A SAFE LOCATION PER THE 2020
 FBC SEC. P 608.17.1.1.
  
 E. THE COFFEE MAKER/ICE MAKER REQUIRES AN INLINE VACUUM
 BREAKER THAT COMPLIES WITH THE ASSE 1024 NON-CARBONATED
 PER THE 2020 FBC SEC. 608.17.1.2.
  
 10. ON SHEET P6.1;
 A. HOT WATER LINES NOT IN CONDITION SPACE IN THE GROUND
 NEED TO BE INSULATED WITH A MINIMUM R-3 PER THE 2020
 FBC SEC. RE 403.5.3.
  
 B. THE LINES TO EACH FIXTURE FROM THE RECIRCULATING
 MANIFOLD TO THE HOT WATER LINES SHALL BE SUPPLIED TO
 THE SOURCE; PLEASE REFER TO THE 2020 FBC ENERGY CODE
 TABLE C404.5.1. MAXIMUM ALLOWABLE PIPE LENGTH METHOD.
  
 C. IN THE KEYNOTES, TEMPERED WATER SHALL BE DELIVERED
 THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070 OR CSA B125.3 PER THE 2020
 FBC SEC. 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
  
 D. THE PIPING SHALL BE INSULATED TO LEVELS SHOWN IN
 TABLE C403.2.10 PER THE 2020 FBC EC 404.4 INSULATION OF
 PIPING.
  
 E. IN THE KITCHEN AREA, THERE IS A THREE-COMPARTMENT
 SINK. PLEASE PROVIDE DETAIL ON THE DRAINS TO AN
 INDIRECT WASTE INDEPENDENTLY FROM EACH OTHER PER THE
 2017 FBC SEC. P 802.1.1.
  
 F. THERE IS TWO GAS UNIT FOR GAS UP ON THE MEZZANINE
 THAT MAY REQUIRE VENTING AND CONDENSATION. WOULD YOU
 PROVIDE MANUFACTURE SPECIFICATION ON HOW THESE ITEM IS
 BEING EXTORTED OUT THE STRUCTURE PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 11. ON SHEET A001 IN THE SHEET INDEX, IT CALLS OUT FOR
 SHEET P3.2 MEZZANINE PLUMBING PLAN, AND NONE WAS FOUND.
 WOULD YOU PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 12. IT MENTIONS A GREASE INTERCEPTOR. WOULD YOU PLEASE
 PROVIDE THE CAPACITY OF THE EXISTING INTERCEPTOR IN
 GALLONS?
 A. IS IT SHARED WITH OTHER RESTAURANTS, AND IF SO, WHAT
 IS THEIR VOLUME.
 B. IS IT A PASSIVE HYDRO-MECHANICAL - OR GRAVITY-TYPE
 GREASE INTERCEPTOR MADE OF CONCRETE STEEL OR
 FIBERGLASS?
 C. IF APPLICABLE, WOULD YOU PLEASE PROVIDE THE STANDARD
 BEING USED FOR SIZING OF THE GREASE INTERCEPTOR? THE
 INTERCEPTOR SHALL BE SIZED IN ACCORDANCE WITH ONE OF
 THE STANDARDS LISTED IN 2020 FBC SEC. P 1003.3.5 OR
 RULE 64E-6 OF THE FLORIDA ADMINISTRATIVE CODE AND THE
 CITY OF WEST PALM BEACH STANDARD DETAIL GS-7.
  
 13. SUBMIT LISTED FIRE-STOPPING DETAILS FOR THE PIPPING
 THROUGH RATED WALLS OR THE FLOORS. PLEASE SUBMIT THE
 COMPLETE ASSEMBLY DETAILS FOR THE SYSTEMS PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 PLEASE FEEL FREE TO CONTACT ME ON ANY OF THE COMMENTS
 BY PHONE OR ZOOM MEETING IF YOU LIKE.
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-10-06 Cont ID  
Sent By rmcphers Date 2021-10-06 Time 14:48 Rev Time 0.00
Received By rmcphers Date 2021-10-06 Time 14:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-09-20 Cont ID  
Sent By rmcphers Date 2021-09-20 Time 13:59 Rev Time 0.00
Received By rmcphers Date 2021-09-20 Time 13:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-13 Cont ID  
Sent By rmcphers Date 2021-08-13 Time 13:26 Rev Time 0.00
Received By rmcphers Date 2021-08-13 Time 13:26 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status P Date 2021-10-07 Cont ID  
Sent By rmcphers Date 2021-10-07 Time 15:39 Rev Time 0.00
Received By rmcphers Date 2021-10-07 Time 15:39 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2021-10-06 Cont ID  
Sent By rmcphers Date 2021-10-06 Time 14:49 Rev Time 0.00
Received By rmcphers Date 2021-10-06 Time 14:49 Sent To  
Notes
2021-10-06 14:51:08REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 THRESHOLD BUILDING
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 NOTE: THIS STRUCTURE IS CONSIDERED A THRESHOLD BUILDING
 PER FS 553.71 12) "THRESHOLD BUILDING" MEANS ANY
 BUILDING WHICH IS GREATER THAN THREE STORIES OR 50 FEET
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 1) PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER
 THE "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS".
 YOU CAN E MAIL ME AND ASK FOR A COPY.
  
  
  
  
  
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2021-09-20 Cont ID  
Sent By rmcphers Date 2021-09-20 Time 13:42 Rev Time 0.00
Received By rmcphers Date 2021-09-20 Time 13:39 Sent To  
Notes
2021-09-20 13:42:46REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 THRESHOLD BUILDING
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 NOTE: THIS STRUCTURE IS CONSIDERED A THRESHOLD BUILDING
 PER FS 553.71 12) "THRESHOLD BUILDING" MEANS ANY
 BUILDING WHICH IS GREATER THAN THREE STORIES OR 50 FEET
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 1) PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER
 THE "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS".
 YOU CAN E MAIL ME AND ASK FOR A COPY.
  
 A) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 B) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2021-08-13 Cont ID  
Sent By rmcphers Date 2021-08-13 Time 13:07 Rev Time 0.00
Received By rmcphers Date 2021-08-13 Time 13:00 Sent To  
Notes
2021-08-13 13:07:29REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 THRESHOLD BUILDING
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 NOTE: THIS STRUCTURE IS CONSIDERED A THRESHOLD BUILDING
 PER FS 553.71 12) "THRESHOLD BUILDING" MEANS ANY
 BUILDING WHICH IS GREATER THAN THREE STORIES OR 50 FEET
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER THE
 "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS".
 YOU CAN E MAIL ME AND ASK FOR A COPY.
  
 1) ANY REPAIRS TO THRESHOLD BUILDINGS ARE REQUIRED TO
 COMPLY WITH FS 553.79. THRESHOLD BLDG. REQUIRED
 STATEMENT: W.P.B. AMENDMENT 110.8.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 FLORIDA STATUTES.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD SHALL CONTAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-09-09 Cont ID  
Sent By eschneid Date 2021-09-09 Time 14:44 Rev Time 0.50
Received By eschneid Date 2021-09-09 Time 13:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-08-17 Cont ID  
Sent By eshneide Date 2021-08-17 Time 09:24 Rev Time 0.50
Received By eschneid Date 2021-08-16 Time 16:57 Sent To  
Notes
2021-08-17 09:29:31FAILED
  
 1) THE MEZZANINE AREA ADDS SQUARE FOOTAGE TO THE
 BUILDING AND THUS MUST BE ACCOUNTED FOR IN THE
 CITYPLACE DRI SQUARE FOOTAGE ALLOCATION TABLE. YOU MUST
 PROVIDE THE GROSS SQUARE FOOTAGE OF THE MEZZANINE.
  
 2) THE CITYPLACE DRI REQUIRES THAT ALL ROOFTOP
 MECHANICAL EQUIPMENT BE SCREENED FROM PUBLIC VIEW
 THROUGH ANY COMBINATION OF WALLS AND EQUIPMENT
 LOCATION.
  
 A. PROVIDE THE TOTAL HEIGHT OF THE EQUIPMENT ABOVE THE
 ROOF DECK, THIS INCLUDES THE BASE RACK/CURB.
  
 B. PROVIDE DIMENSIONS FROM THE NEW ROOFTOP EQUIPMENT TO
 THE EDGE OF THE ROOF AND DETAIL THE HEIGHT AND LOCATION
 OF ANY PARAPETS OR WALLS USED TO SCREEN THE PROPOSED
 EQUIPMENT.
  
 C. IF THE EXISTING PARAPETS ARE NOT TALLER THAN THE NEW
 EQUIPMENT, PROVIDE SIGHT LINE OR ELEVATION DRAWING TO
 VERIFY THAT THE PARAPET HEIGHTS SCREEN THE FULL HEIGHT
 OF THE NEW ROOFTOP EQUIPMENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected].
  