Plan Review Details - Permit 21070725
Plan Review Stops For Permit 21070725
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-07-30 Cont ID  
Sent By cthroop Date 2021-07-30 Time 16:24 Rev Time 0.00
Received By cthroop Date 2021-07-30 Time 16:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-07-21 Cont ID  
Sent By jleahy Date 2021-07-21 Time 20:02 Rev Time 0.00
Received By jleahy Date 2021-07-21 Time 19:56 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-08-27 Cont ID  
Sent By lcrespo Date 2021-08-27 Time 09:24 Rev Time 0.00
Received By lcrespo Date 2021-08-27 Time 09:24 Sent To  
Notes
2021-08-27 09:25:1708/27/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-07-26 Cont ID  
Sent By ccole Date 2021-07-26 Time 16:28 Rev Time 0.00
Received By ccole Date 2021-07-26 Time 16:04 Sent To  
Notes
2021-07-26 16:29:131ST REVIEW FBC-2020 RES. GAS
 PERMIT- 21070725
 7/26/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER: BASED ON THE PIPE SIZING TABLE ON THE
 DRAWING- TABLE 402.4(1) FBC FG, THE 1-INCH PIPE IS
 UNDERSIZED TO SUPPLY THE TOTAL 594,000 BTUH SYSTEM
 WHICH HAS A TOTAL DEVELOPED LENGTH OF 85 FT. THE PIPE
 SIZE MUCH BE INCREASED, OR THE DELIVERY PRESSURE AT THE
 METER MUST BE INCREASED TO HANDLE THE NEW GENERATOR
 LOAD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-27 Cont ID  
Sent By lcrespo Date 2021-08-27 Time 09:24 Rev Time 0.00
Received By lcrespo Date 2021-08-19 Time 14:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-19 Cont ID  
Sent By lmarchan Date 2021-08-19 Time 12:47 Rev Time 0.00
Received By lmarchan Date 2021-07-15 Time 12:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-08-27 Cont ID  
Sent By lcrespo Date 2021-08-27 Time 09:24 Rev Time 0.00
Received By lcrespo Date 2021-08-27 Time 09:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-07-26 Cont ID  
Sent By ccole Date 2021-07-26 Time 16:29 Rev Time 0.00
Received By ccole Date 2021-07-26 Time 16:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-07-30 Cont ID  
Sent By cthroop Date 2021-07-30 Time 16:24 Rev Time 0.00
Received By cthroop Date 2021-07-30 Time 16:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-08-19 Cont ID  
Sent By rthermid Date 2021-08-19 Time   Rev Time  
Received By rthermid Date 2021-08-19 Time   Sent To I
Notes
***NONE***