Plan Review Details - Permit 21070688
Plan Review Stops For Permit 21070688
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-10-05 Cont ID  
Sent By jwitmer Date 2021-10-05 Time 16:14 Rev Time 0.00
Received By jwitmer Date 2021-10-05 Time 15:49 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-08-11 Cont ID  
Sent By jwitmer Date 2021-08-11 Time 14:38 Rev Time 0.00
Received By jwitmer Date 2021-08-11 Time 13:50 Sent To  
Notes
2021-08-11 14:38:29COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-10-05 Cont ID  
Sent By jwitmer Date 2021-10-05 Time 16:14 Rev Time 0.00
Received By jwitmer Date 2021-10-05 Time 15:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-11 Cont ID  
Sent By jwitmer Date 2021-08-11 Time 14:37 Rev Time 0.00
Received By jwitmer Date 2021-08-11 Time 13:50 Sent To  
Notes
2021-08-11 14:37:48WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21070688
 ADD: 5600 N FLAGLER DR. # 1604
 CONT: FLAGLER BUILDING SYSTEMS
 TEL: 561-596-3983
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 11TH/ 2021
 ACTION: DENIED
  
 1) SITE SPECIFIC DESIGN PRESSURES REPORT HAS PRESSURES
 FOR WINDOWS 1-3 AND SLIDERS D1 & D2 ON THIS REPORT THEY
 ARE CORRECT. THE SUBMITTED FLOOR PLAN HAS THE SAME
 PRESSURE CHART. THE ISSUE IS ABOVE EACH OPENING THERE
 IS A SECOND SET OF PRESSURES ARE 15 -20 PSF LOWER THAN
 IN THE CHARTS. THE PRESSURES IN THE CHARTS MATCH THAT
 OF FRANK BENNARDO P. E. W/ ENGINEERING EXPRESS.
  
 2) THE CONDO UNIT IT IS ASSUMED IS IN WALL ZONE 4 SINCE
 THERE IS NO FOOTPRINT OF THE BUILDING SHOWING THE UNIT
 WITHIN THE FOOTPRINT. 107.2.1.2 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 3) SHEET 001 NOTES SCOPE OF WORK NOTE # 3 INDICATES
 TILE FLOORING REPLACED W/ WHISPER MAT UNDERLAYMENT PER
 CODE.
 THE NOTE DOES NOT INDICATE WHAT TYPE OF MATERIAL IS
 GOING BACK AS A FINISH FLOOR NOR DOES THE DESIGNER OF
 RECORD IDENTIFY
 WHICH TYPE OF WHISPER MAT CS OR HW TO BE INSTALLED.
 107.2.1.2.
  
 4) PLEASE IDENTIFY IN THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 SILL HEIGTH, TYPE OF GLAZING, MULLION SIZE, LENGTH IF
 UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-10-21 Cont ID  
Sent By fgiaquin Date 2021-10-21 Time 21:33 Rev Time 0.00
Received By fgiaquin Date 2021-10-21 Time 20:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-08-10 Cont ID  
Sent By fgiaquin Date 2021-08-10 Time 22:30 Rev Time 0.00
Received By fgiaquin Date 2021-08-10 Time 22:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-10-04 Cont ID  
Sent By pleduc Date 2021-10-04 Time   Rev Time 0.00
Received By pleduc Date 2021-10-04 Time 14:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-08-05 Cont ID  
Sent By pleduc Date 2021-08-05 Time   Rev Time 0.00
Received By pleduc Date 2021-08-04 Time 16:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-22 Cont ID  
Sent By lcrespo Date 2021-10-22 Time 14:51 Rev Time 0.00
Received By lcrespo Date 2021-10-01 Time 07:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-16 Cont ID  
Sent By medwards Date 2021-08-16 Time 14:54 Rev Time 0.00
Received By medwards Date 2021-07-30 Time 15:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-10-04 Cont ID  
Sent By medwards Date 2021-10-04 Time 10:05 Rev Time 0.00
Received By medwards Date 2021-10-04 Time 10:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-08-16 Cont ID  
Sent By medwards Date 2021-08-16 Time 14:45 Rev Time 0.00
Received By medwards Date 2021-08-16 Time 14:45 Sent To  
Notes
2021-08-16 14:46:09INSTALLATION OF 2 BATHEXHAUST FANS. ME

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-10-22 Cont ID  
Sent By lcrespo Date 2021-10-22 Time 14:51 Rev Time 0.00
Received By lcrespo Date 2021-10-22 Time 14:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-08-10 Cont ID  
Sent By lcrespo Date 2021-08-10 Time 11:52 Rev Time 0.00
Received By lcrespo Date 2021-08-10 Time 11:52 Sent To  
Notes
2021-08-10 11:52:5008/10/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-04 Cont ID  
Sent By medwards Date 2021-10-04 Time 10:07 Rev Time 0.00
Received By medwards Date 2021-10-04 Time 10:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-08-16 Cont ID  
Sent By medwards Date 2021-08-16 Time 14:51 Rev Time 0.00
Received By medwards Date 2021-08-16 Time 14:51 Sent To  
Notes
2021-08-16 14:53:43EACH SHEET EXCEPT THE SITE SPECIFIC DESIGN PRESSURE
 REPORT MUST BE DIGITALLY SIGNED BY THE DESIGNER.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  