Plan Review Details - Permit 21070558
Plan Review Stops For Permit 21070558
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-07-20 Cont ID  
Sent By cpuell Date 2021-07-20 Time 09:45 Rev Time 0.00
Received By cpuell Date 2021-07-20 Time 09:45 Sent To  
Notes
2021-07-20 09:46:10ADDRESS CHANGED FROM 5415 MANNING AVE TO 700 54TH ST TH
 NEW BUILDINGS ENTRANCE IS ON 54TH ST.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-07-13 Cont ID  
Sent By cpuell Date 2021-07-13 Time 13:05 Rev Time 0.00
Received By cpuell Date 2021-07-13 Time 13:05 Sent To  
Notes
2021-07-13 13:07:30CORNER LOT, IT APPEARS THAT THE MAIN ENTRANCE WILL NOW
 BE ON 54TH ST. PLEASE HAVE OWNER CONTACT [email protected]
 OR 561-805-6659 TO DISCUSS ADDRESSING OPTIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-04-26 Cont ID  
Sent By rmcphers Date 2022-04-26 Time 17:07 Rev Time 0.00
Received By rmcphers Date 2022-04-26 Time 17:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-02-24 Cont ID  
Sent By rmcphers Date 2022-02-24 Time 12:34 Rev Time 0.00
Received By rmcphers Date 2022-02-24 Time 12:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-12-08 Cont ID  
Sent By rmcphers Date 2021-12-08 Time 11:32 Rev Time 0.00
Received By rmcphers Date 2021-12-08 Time 10:12 Sent To  
Notes
2021-12-08 11:23:03NEW BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC RESIDENTIAL WITH WPB
 CHAPTER 1 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW ATTIC PROTECTION TO COMPLY WITH FBC
 903.2.8.3 GROUP R-4 CONDITION 2.
 AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE
 WITH SECTION 903.3.1.2 SHALL BE PERMITTED IN GROUP R-4
 CONDITION 2 OCCUPANCIES. ATTICS SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 903.2.8.3.1 OR 903.2.8.3.2.
  
 FBC 903.2.8.3.2 ATTICS NOT USED FOR LIVING PURPOSES,
 STORAGE OR FUEL-FIRED EQUIPMENT.
 ATTICS NOT USED FOR LIVING PURPOSES, STORAGE OR
 FUEL-FIRED EQUIPMENT SHALL BE PROTECTED IN ACCORDANCE
 WITH ONE OF THE FOLLOWING:
  
 A).ATTICS PROTECTED THROUGHOUT BY A HEAT DETECTOR
 SYSTEM ARRANGED TO ACTIVATE THE BUILDING FIRE ALARM
 SYSTEM IN ACCORDANCE WITH SECTION 907.2.10.
  
 B).ATTICS CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS.
  
 C).ATTICS CONSTRUCTED OF FIRE-RETARDANT-TREATED WOOD
 FRAMING COMPLYING WITH SECTION 2303.2.
  
 D).THE AUTOMATIC SPRINKLER SYSTEM SHALL BE EXTENDED TO
 PROVIDE PROTECTION THROUGHOUT THE ATTIC SPACE.
  
 2) PLEASE SHOW FIRE SPRINKLER COVERAGE FOR THE PATIOS
 PER FBC 903.3.1.2.1 BALCONIES AND DECKS.
 SPRINKLER PROTECTION SHALL BE PROVIDED FOR EXTERIOR
 BALCONIES, DECKS AND GROUND FLOOR PATIOS OF DWELLING
 UNITS AND SLEEPING UNITS WHERE THE BUILDING IS OF TYPE
 V CONSTRUCTION, PROVIDED THERE IS A ROOF OR DECK ABOVE.
 SIDEWALL SPRINKLERS THAT ARE USED TO PROTECT SUCH AREAS
 SHALL BE PERMITTED TO BE LOCATED SUCH THAT THEIR
 DEFLECTORS ARE WITHIN 1 INCH (25 MM) TO 6 INCHES (152
 MM) BELOW THE STRUCTURAL MEMBERS AND A MAXIMUM DISTANCE
 OF 14 INCHES (356 MM) BELOW THE DECK OF THE EXTERIOR
 BALCONIES AND DECKS THAT ARE CONSTRUCTED OF OPEN WOOD
 JOIST CONSTRUCTION.
  
 3) FENCE AND GENERATOR - EACH REQUIRE A SEPARATE PERMIT
 - WHICH CAN BE SUBMITTED LATER - BEFORE INSTALLATION.
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-01 Cont ID  
Sent By cthroop Date 2021-09-01 Time 12:33 Rev Time 0.00
Received By rmcphers Date 2021-09-01 Time 10:12 Sent To  
Notes
2021-09-01 10:56:56NEW BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC RESIDENTIAL WITH WPB
 CHAPTER 1 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) DRAWING A-1.10 SHOWS R3 "CONGREGATE" LIVING FACILITY
 WITH 5 OCCUPANTS MAXIMUM - DRAWING STATES COMPLIANCE IS
 PER FBC RESIDENTIAL CODE - FBC R310.5.1 ALLOWS "CARE"
 FACILITIES (NOT "CONGREGATE" FACILITIES) WITHIN A
 DWELLING. CARE FACILITIES FOR FIVE OR FEWER PERSONS
 RECEIVING CARE THAT ARE WITHIN A SINGLE-FAMILY DWELLING
 ARE PERMITTED TO COMPLY WITH THE FLORIDA BUILDING CODE,
 // R3 CONGREGATE WILL NEED TO USE THE FBC BUILDING.
 2) PLEASE SHOW DESCRIPTION AS (CONGREGATE (TRANSIENT)
 OR (NON TRANSIENT) ) PER FBC 310.5
 3) PLEASE PROVIDE COMPLETE PRODUCT APPROVALS FOR THE
 EXTERIOR WINDOWS, DOORS, ROOFING SYSTEMS ETC.. ALL
 PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD OR BE
 LISTED BY PRODUCT APPROVAL NUMBER ON THE DRAWINGS. FBC
 WPB 107.2.1
 4) HARDI PLANK SIDING IS SUBJECT TO WIND LOADS - PLEASE
 PROVIDE ATTACHMENT DETAILS OR PRODUCT APPROVALS TO
 COMPLY WITH FBC R703.1.2
 5) PLEASE SHOW THE WOOD EXTERIOR WALLS -WATER RESISTIVE
 BARRIER TO COMPLY WITH FBC R703.2
  
 DRAWINGS WERE REVIEWED BASED ON THE FBC RESIDENTIAL -
 IF CORRECTIONS SUGGEST DESIGN TO BE PER FBC BUILDING
 ADDITIONAL CORRECTIONS MAY BE REQUIRED.
  
  
2021-08-16 17:34:59 
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-08-02 Cont ID  
Sent By fgiaquin Date 2021-08-02 Time 21:25 Rev Time 0.00
Received By fgiaquin Date 2021-07-30 Time 21:48 Sent To  
Notes
2021-08-02 21:24:59SEPARATE PERMIT REQUIRED FOR GENERATOR.
  
 SEPARATE PERMIT AND PLANS SUBMITTAL REQUIRED FOR FIRE
 ALARM.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2023-01-30 Cont ID  
Sent By rrossano Date 2023-01-30 Time   Rev Time 0.00
Received By rrossano Date 2023-01-30 Time   Sent To  
Notes
2023-01-30 11:30:53A FORMAL ENGINEERING SUBMITTAL IS REQUIRED. PLEASE
 EMAIL FOR AN ENGINEERING SUBMITTAL PACKAGE.
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES
 DEPT., 561-494-1098, FAX: 561-494-1116 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-02-11 Cont ID  
Sent By pleduc Date 2022-02-11 Time   Rev Time 0.00
Received By pleduc Date 2022-02-11 Time 13:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2021-11-29 Cont ID  
Sent By pleduc Date 2021-11-29 Time   Rev Time 0.00
Received By pleduc Date 2021-11-29 Time 11:40 Sent To  
Notes
2021-11-29 12:10:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) PREVIOUS COMMENT # 2 WAS NOT ADDRESSED AND REMAINS.
  
 THE PRIMARY MEANS OF ESCAPE WITH THE STAIR OPENING INTO
 THE LVIVING ROOMS DOES NOT MEET THE REQUIREMENTS OF
 NFPA 101 CH 32
  
  
 32.2.2.4.6 IN BUILDINGS THREE OR FEWER STORIES IN
 HEIGHT AND PROTECTED
 BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH 32.2.3.5,
 STAIR ENCLOSURES SHALL NOT BE REQUIRED, PROVIDED THAT
 THERE STILL REMAINS
 A PRIMARY MEANS OF ESCAPE FROM EACH SLEEPING AREA THAT
 DOES NOT REQUIRE
 OCCUPANTS TO PASS THROUGH A PORTION OF A LOWER FLOOR,
 UNLESS THAT ROUTE
 IS SEPARATED FROM ALL SPACES ON THAT FLOOR BY
 CONSTRUCTION HAVING A MINIMUM
 1?2-HOUR FIRE RESISTANCE RATING.
  
 THE PROVISIONS OF 32/33.2.2.4.7 PERMIT A TWO-STORY OPEN
 STAIR
 (AND ITS ASSOCIATED EXPOSURE TO THE AREAS THAT ARE
 OCCUPIED OR FURNISHED,
 OR BOTH, ON THE GROUND FLOOR) TO SERVE AS PRIMARY MEANS
 OF
 ESCAPE FOR NEW SMALL FACILITIES AND EXISTING SMALL
 FACILITIES (NOT
 MORE THAN EIGHT RESIDENTS) WITH PROMPT EVACUATION
 CAPABILITY,
 PROVIDED THAT THE FACILITY IS SPRINKLERED USING
 QUICK-RESPONSE OR
 RESIDENTIAL SPRINKLERS. THIS PROVISION, IN EFFECT,
 EQUATES SUCH A
 BOARD AND CARE FACILITY WITH A ONE- OR TWO-FAMILY
 DWELLING. AN
 UNENCLOSED INTERIOR STAIR MEETING THE CRITERIA OF THIS
 PROVISION IS
 CONSIDERED THE EQUIVALENT OF AN ENCLOSED INTERIOR
 STAIR.
  
  
 PLEASE REVIEW AND CORRECT OR PROVIDE A DETAILED
 NARRATIVE WITH CODE REFERENCES
  
  
  
 *****ADDITIONAL COMMENT****
  
  
 2) THERE IS AN INDICATION OF A RAMP LEADING TO A PUBLIC
 WAY; HOWEVER, THERE ARE OPENINGS ALONG THE RAMP ROUTE
 THAT APPEAR TO BE NORMAL GLAZING.
  
 32.2.2.2 PRIMARY MEANS OF ESCAPE.
  
 32.2.2.2.1 EVERY SLEEPING ROOM AND LIVING AREA SHALL
 HAVE ACCESS TO A
 PRIMARY MEANS OF ESCAPE LOCATED TO PROVIDE A SAFE PATH
 OF TRAVEL TO THE
 OUTSIDE AT STREET LEVEL OR THE FINISHED GROUND LEVEL.
  
 32.2.2.2.2 WHERE SLEEPING ROOMS OR LIVING AREAS ARE
 ABOVE OR BELOW
 THE LEVEL OF EXIT DISCHARGE, THE PRIMARY MEANS OF
 ESCAPE SHALL BE AN
 INTERIOR STAIR IN ACCORDANCE WITH 32.2.2.4, AN EXTERIOR
 STAIR, A HORIZONTAL
 EXIT, OR A FIRE ESCAPE STAIR
  
 32.1.1.3 GENERAL. THE PROVISIONS OF CHAPTER 4, GENERAL,
 SHALL APPLY.
  
 4.5.3 MEANS OF EGRESS.
 4.5.3.1 NUMBER OF MEANS OF EGRESS. TWO MEANS OF EGRESS,
 AS A MINIMUM,
 SHALL BE PROVIDED IN EVERY BUILDING OR STRUCTURE,
 SECTION, AND AREA
 WHERE SIZE, OCCUPANCY, AND ARRANGEMENT ENDANGER
 OCCUPANTS ATTEMPTING
 TO USE A SINGLE MEANS OF EGRESS THAT IS BLOCKED BY FIRE
 OR SMOKE. THE
 TWO MEANS OF EGRESS SHALL BE ARRANGED TO MINIMIZE THE
 POSSIBILITY THAT
 BOTH MIGHT BE RENDERED IMPASSABLE BY THE SAME EMERGENCY
 CONDITION.
  
 4.6.1.2 ANY REQUIREMENTS THAT ARE ESSENTIAL FOR THE
 SAFETY OF BUILDING
 OCCUPANTS AND THAT ARE NOT SPECIFICALLY PROVIDED FOR BY
 THIS CODE SHALL
 BE DETERMINED BY THE AUTHORITY HAVING JURISDICTION.
  
 PER NFPA 101 CH 7 MEANS OF ESCAPE
  
 7.5.3 EXTERIORWAYS OF EXIT ACCESS
  
 7.5.3.3 EXTERIOR EXIT ACCESS BALCONIES SHALL BE
 SEPARATED FROM THE INTERIOR
 OF THE BUILDING BY WALLS AND OPENING PROTECTIVES AS
 REQUIRED FOR CORRIDORS,
 UNLESS THE EXTERIOR EXIT ACCESS BALCONY IS SERVED BY AT
 LEAST TWO
 REMOTE STAIRS THAT CAN BE ACCESSED WITHOUT ANY OCCUPANT
 TRAVELING PAST
 AN UNPROTECTED OPENING TO REACH ONE OF THE STAIRS, OR
 UNLESS DEAD ENDS
 ON THE EXTERIOR EXIT ACCESS DO NOT EXCEED 20 FT
  
 7.5.4 ACCESSIBLE MEANS OF EGRESS.
 7.5.4.1* AREAS ACCESSIBLE TO PEOPLE WITH SEVERE
 MOBILITY IMPAIRMENT,
 OTHER THAN IN EXISTING BUILDINGS, SHALL HAVE NOT LESS
 THAN TWO ACCESSIBLE
 MEANS OF EGRESS, UNLESS OTHERWISE PROVIDED IN 7.5.4.1.2
 THROUGH 7.5.4.1.4
  
 7.5.4.1.2 A SINGLE ACCESSIBLE MEANS OF EGRESS SHALL BE
 PERMITTED FROM
 BUILDINGS OR AREAS OF BUILDINGS PERMITTED TO HAVE A
 SINGLE EXIT.
  
 7.5.4.6 TO BE CONSIDERED PART OF AN ACCESSIBLE MEANS OF
 EGRESS, A SMOKE
 BARRIER IN ACCORDANCE WITH SECTION 8.5 WITH NOT LESS
 THAN A 1-HOUR FIRE
 RESISTANCE RATING, OR A HORIZONTAL EXIT IN ACCORDANCE
 WITH 7.2.4, SHALL
 DISCHARGE TO AN AREA OF REFUGE IN ACCORDANCE WITH
 7.2.12.
  
  
 PERSONS IN WHEELCHAIRS/WALKERS HAVE THEIR SOLE MEANS OF
 ESCAPE VIA THE RAMP. SHOULD FIRE BREACH THOSE WINDOWS,
 THEIR ESCAPE IS BLOCKED.
  
  
 PLEASE REVIEW AND CORRECT OR PROVIDE A DETAILED
 NARRATIVE WITH CODE REFERENCES
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-08-31 Cont ID  
Sent By pleduc Date 2021-08-31 Time   Rev Time 0.00
Received By pleduc Date 2021-08-31 Time 13:32 Sent To  
Notes
2021-08-31 14:17:43THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATION OF WHAT APPEARS TO BE SHOWER
 HANDRAILS; HOWEVER, THERE ARE NO DETAILED INDICATIONS
 OF MEETING THE REQUIRMENTS OF THE FIRE CODE.
  
 PER NFPA 101
  
 32.2.2.7 WHERE BATHTUBS, BATHTUB-SHOWER COMBINATIONS,
 OR SHOWERS ARE
 PRESENT, GRAB BARS SHALL BE PROVIDED IN ACCORDANCE WITH
 THE PROVISIONS
 OF 24.2.8.
  
 24.2.8.2.1* BATHTUB END WALL VERTICAL GRAB BARS. END
 WALL VERTICAL
 GRAB BARS FOR BATHTUBS SHALL COMPLY WITH ALL OF THE
 FOLLOWING:
 (1) VERTICAL GRAB BARS SHALL HAVE A LENGTH OF NOT LESS
 THAN 36 IN.
 (914 MM).
 (2) VERTICAL GRAB BARS SHALL BE LOCATED BETWEEN 24 IN.
 (610 MM) AND
 27 IN. (686 MM) ABOVE THE FINISHED FLOOR, MEASURED TO
 THE LOWER END.
 (3) VERTICAL GRAB BARS SHALL BE INSTALLED AT THE END
 THAT IS LEAST OBSTRUCTED
 FOR ENTRY AND EGRESS.
 (4) VERTICAL GRAB BARS SHALL BE LOCATED BETWEEN 9 IN.
 (228 MM) AND
 12 IN. (305 MM) FROM THE OPEN ENTRY AND EGRESS SIDE OF
 THE BATHTUB
 OR BATHTUB-SHOWER COMBINATION, MEASURED HORIZONTALLY
 FROM THE
 EXTERIOR PLANE OF THE BATHTUB OR BATHTUB-SHOWER
 COMBINATION.
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE.
  
  
  
  
 2) THE PRIMARY MEAND OF ESCAPE FROM THE 2ND FLOOR DOES
 NOT APPEAR TO MEET THE REQUIREMENTS OF UNENCLOSED ON
 THE 1ST FLOOR.
  
 THE 1ST FLOOR PORTION HAS TO BE A 1/2 HOUR PROTECTED
 ARE WITHOUT FURNITURE.
  
 32.2.2.4.2 STAIRS SHALL COMPLY WITH 7.2.2.5.3.
 32.2.2.4.3 THE ENTIRE PRIMARY MEANS OF ESCAPE SHALL BE
 ARRANGED SO THAT
 OCCUPANTS ARE NOT REQUIRED TO PASS THROUGH A PORTION OF
 A STORY ABOVE OR
 A STORY BELOW, UNLESS THAT ROUTE IS SEPARATED FROM ALL
 SPACES ON THAT STORY
 BY CONSTRUCTION HAVING A MINIMUM 1?2-HOUR FIRE
 RESISTANCE RATING.
 32.2.2.4.4 IN BUILDINGS OF CONSTRUCTION OTHER THAN TYPE
 II(000),
 TYPE III(200), OR TYPE V(000), THE SUPPORTING
 CONSTRUCTION SHALL BE
 PROTECTED TO AFFORD THE REQUIRED FIRE RESISTANCE RATING
 OF THE SUPPORTED
 WALL.
 32.2.2.4.5 STAIRS THAT CONNECT A STORY AT STREET LEVEL
 TO ONLY ONE OTHER
 STORY SHALL BE PERMITTED TO BE OPEN TO THE STORY THAT
 IS NOT AT STREET LEVEL.
 32.2.2.4.6 IN BUILDINGS THREE OR FEWER STORIES IN
 HEIGHT AND PROTECTED
 BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH 32.2.3.5,
 STAIR ENCLOSURES SHALL NOT BE REQUIRED, PROVIDED THAT
 THERE STILL REMAINS
 A PRIMARY MEANS OF ESCAPE FROM EACH SLEEPING AREA THAT
 DOES NOT REQUIRE
 OCCUPANTS TO PASS THROUGH A PORTION OF A LOWER FLOOR,
 UNLESS THAT ROUTE
 IS SEPARATED FROM ALL SPACES ON THAT FLOOR BY
 CONSTRUCTION HAVING A MINIMUM
 1?2-HOUR FIRE RESISTANCE RATING.
 32.2.2.4.7 STAIRS SERVING A MAXIMUM OF TWO STORIES IN
 BUILDINGS PROTECTED
 WITH AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH
 32.2.3.5 SHALL BE PERMITTED TO BE UNENCLOSED.
  
 ONE OF THE REQUIREMENTS OF THIS CODE TO USE AN
 UNENCLOSED STAIR IS WITH PROMPT EVACUATION CAPABILITY.
  
 THE PROVISIONS OF 32/33.2.2.4.7 PERMIT A TWO-STORY OPEN
 STAIR
 (AND ITS ASSOCIATED EXPOSURE TO THE AREAS THAT ARE
 OCCUPIED OR FURNISHED,
 OR BOTH, ON THE GROUND FLOOR) TO SERVE AS PRIMARY MEANS
 OF
 ESCAPE FOR NEW SMALL FACILITIES AND EXISTING SMALL
 FACILITIES (NOT
 MORE THAN EIGHT RESIDENTS) WITH PROMPT EVACUATION
 CAPABILITY,
 PROVIDED THAT THE FACILITY IS SPRINKLERED USING
 QUICK-RESPONSE OR
 RESIDENTIAL SPRINKLERS.
  
 32.1.5 ACCEPTABILITY OF MEANS OF EGRESS OR ESCAPE. NO
 MEANS OF
 ESCAPE OR MEANS OF EGRESS SHALL BE CONSIDERED AS
 COMPLYING WITH THE
 MINIMUM CRITERIA FOR ACCEPTANCE, UNLESS EMERGENCY
 EVACUATION DRILLS
 ARE REGULARLY CONDUCTED USING THAT ROUTE IN ACCORDANCE
 WITH THE REQUIREMENTS
 OF 32.7.3
  
 3.3.81.2 PROMPT EVACUATION CAPABILITY. THE ABILITY OF A
 GROUP TO
 MOVE RELIABLY TO A POINT OF SAFETY IN A TIMELY MANNER
 THAT IS EQUIVALENT
 TO THE CAPACITY OF A HOUSEHOLD IN THE GENERAL
 POPULATION.
  
 A.3.3.81 EVACUATION CAPABILITY. THE EVACUATION
 CAPABILITY OF THE
 RESIDENTS AND STAFF IS A FUNCTION OF BOTH THE ABILITY
 OF THE RESIDENTS TO
 EVACUATE AND THE ASSISTANCE PROVIDED BY THE STAFF. IT
 IS INTENDED THAT THE
 EVACUATION CAPABILITY BE DETERMINED BY THE PROCEDURE
 ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. IT IS ALSO INTENDED THAT
 THE TIMING OF DRILLS,
 THE RATING OF RESIDENTS, AND SIMILAR ACTIONS RELATED TO
 DETERMINING THE
 EVACUATION CAPABILITY BE PERFORMED BY PERSONS APPROVED
 BY OR ACCEPTABLE
 TO THE AUTHORITY HAVING JURISDICTION. THE EVACUATION
 CAPABILITY CAN
 BE DETERMINED BY THE USE OF THE DEFINITIONS IN 3.3.81,
 THE APPLICATION OF
 NFPA 101A CHAPTER 6, OR A PROGRAM OF DRILLS (TIMED).
 EVACUATION DOES NOT INCLUDE THE RELOCATION OF OCCUPANTS
 WITHIN A
 BUILDING.
 WHERE DRILLS ARE USED IN DETERMINING EVACUATION
 CAPABILITY, IT IS
 SUGGESTED THAT THE FACILITY CONDUCT AND RECORD FIRE
 DRILLS SIX TIMES PER
 YEAR ON A BIMONTHLY BASIS, WITH A MINIMUM OF TWO DRILLS
 CONDUCTED
 DURING THE NIGHT WHEN RESIDENTS ARE SLEEPING, AND THAT
 THE FACILITY CONDUCT
 THE DRILLS IN CONSULTATION WITH THE AUTHORITY HAVING
 JURISDICTION. RECORDS
 SHOULD INDICATE THE TIME TAKEN TO REACH A POINT OF
 SAFETY, DATE AND TIME
 OF DAY, LOCATION OF SIMULATED FIRE ORIGIN, ESCAPE PATHS
 USED, AND COMMENTS
 RELATING TO RESIDENTS WHO RESISTED OR FAILED TO
 PARTICIPATE IN THE
 DRILLS.
 TRANSLATION OF DRILL TIMES TO EVACUATION CAPABILITY IS
 DETERMINED AS
 FOLLOWS:
 (1) 3 MINUTES OR LESS ? PROMPT
 (2) OVER 3 MINUTES, BUT NOT IN EXCESS OF 13 MINUTES ?
 SLOW
 (3) MORE THAN 13 MINUTES ? IMPRACTICAL
 EVACUATION CAPABILITY, IN ALL CASES, IS BASED ON THE
 TIME OF DAY OR
 NIGHT WHEN EVACUATION OF THE FACILITY WOULD BE MOST
 DIFFICULT, SUCH AS
 WHEN RESIDENTS ARE SLEEPING OR FEWER STAFF ARE PRESENT.
 EVACUATION CAPABILITY DETERMINATION IS CONSIDERED SLOW
 IF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) ALL RESIDENTS ARE ABLE TO TRAVEL TO CENTRALIZED
 DINING FACILITIES WITHOUT
 CONTINUOUS STAFF ASSISTANCE.
 (2) THERE IS CONTINUOUS STAFFING WHENEVER THERE ARE
 RESIDENTS IN THE
 FACILITY.
  
 IT WOULD BE ANTICIPATED THAT THE EVACUATION TIME OF 3
 MINUTES WOULD BE FOR CLIENTS WITH NO OR LIMITED
 PHYISCAL/MENTAL DISABILITES.
  
 PLEASE REVIEW AND PROVIDE DETAILS OF THE PROPOSED
 CLIENTS AND THE ABILITY TO MEET THE PROMPT EVACUATION
 OR CORRECT AND ENLCOSE THE STAIT EITHER AT THE TOP OR
 THE BOTTOM.
  
  
  
  
 3) THERE ARE 2 EXTERIOR DOORS/GATES WITHIN THE EGRESS
 TRAVEL PATH LEADING TO A PUBLIC WAY OR POINT OF SAFETY.
  
 32.2.2.5.5 NO DOOR IN ANY MEANS OF ESCAPE, OTHER THAN
 THOSE MEETING
 THE REQUIREMENT OF 32.2.2.5.5.1, 32.2.2.5.5.2, OR
 32.2.2.5.5.3, SHALL BE
 LOCKED AGAINST EGRESS WHEN THE BUILDING IS OCCUPIED.
  
 PLEASE PROVIDE DETAILS INDICATING HOW THESE DOORS/GATES
 WILL COMPLY WITH THE CODE.
  
  
  
 4) THERE ARE INDICATIONS OF A 13D FIRE SPRINKLER
 SYSTEM; HOWEVER, THERE IS ONLY 1 DOMESTIC WATER LINE
 INDICATED.
  
 PER THE WATER UTILITIES DEPARTMENT, A DEDICATED WATER
 SUPPLY AND WATER METER FOR A FIRE SPRINKLER SYSTEM IS
 REQUIRED.
  
 PLEASE CONTACT THE WATER UTILITIES DEPARTMENT FOR THEIR
 REQUIERMENTS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT
 AND PROVIDE REVISION AS AND WHERE REQUIRED PRIOR TO
 INSTALLATIONS.
  
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-12-09 Cont ID  
Sent By ccole Date 2021-12-09 Time 13:12 Rev Time 0.00
Received By ccole Date 2021-12-09 Time 09:55 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-07-30 Cont ID  
Sent By ccole Date 2021-07-30 Time 12:12 Rev Time 0.00
Received By ccole Date 2021-07-30 Time 11:15 Sent To  
Notes
2021-07-30 12:12:381ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21070558
 7/30/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P401, P701, P801: THE RINNAI RUR WATER HEATERS ARE
 LISTED FOR INDOOR USE, BUT THE PLAN SHOWS THE UNITS ON
 THE EXTERIOR OF THE BUILDING- SECTIONS 305.1 & 624.1
 FBC FG.
  
 2) P401 & P701: SHOW WH CONDENSATE LINES,
 NEUTRALIZATION DEVICE AND CONDENSATE LINE DISPOSAL
 LOCATIONS- SECTION 307.2 FBC FG.
  
 3) P401 & P701: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE WATER HEATERS- SECTION 624.1 FBC FG. PROVIDE A
 BASIC INSTALLATION DIAGRAM ON THE PLAN SHOWING THE
 REQUIRED CLEARANCES FROM THE UNITS TO GRADE, OVERHEAD
 CONSTRUCTION AND TO THE ADJACENT WINDOW OPENING- WATER
 HEATER- SECTIONS 624.1 & 503.8 FBC FG.
  
 4) P601 OR P602: PLEASE PROVIDE A GAS RISER DRAWING-
 SECTION 107.3.5.1.3 WPB. PLEASE NOTE THE GAS DEMAND
 SCHEDULE INDICATES 1-INCH PE BRANCHES TO THE WATER
 HEATERS THAT ARE UNDERSIZED USING THE LONGEST LENGTH
 METHOD AND THE SPECIFIED SIZING TABLE 402.4(21) FBC FG
 AND SECTION 402.4.1 FBC FG. GAS RISER:
  
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 J) PIPE SIZING TABLES.
  
 5) SUBMIT CUT SHEETS FOR ALL EQUIPMENT RELATING TO THE
 GAS INSTALLATION SUCH AS REGULATORS, AND THE GENERATOR
 FLEX CONNECTOR- SECTIONS G2421.2 & G2422.1.2 FBC RES.
  
 6) PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR
 INSTALLATION OF THE GENERATOR- SECTION 105.1 & 107.2.1
 WPB, HOWEVER, IN ORDER TO PERFORM A COMPLETE GAS REVIEW
 AT THIS TIME PLEASE SUBMIT A CUT SHEET FOR THE
 GENERATOR SHOWING THE BTUH LOAD AND INPUT PRESSURE-
 SECTIONS 305.1 & 402.2 FBC FG.
  
 7) SUBMIT A GAS SUB-PERMIT APPLICATION- SECTION 105.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-04-26 Cont ID  
Sent By rmcphers Date 2022-04-26 Time 17:07 Rev Time 0.00
Received By rmcphers Date 2022-04-08 Time 06:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-25 Cont ID  
Sent By medwards Date 2022-02-25 Time 13:39 Rev Time 0.00
Received By medwards Date 2022-02-08 Time 07:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-12-09 Time   Rev Time 0.00
Received By aoliver Date 2021-11-18 Time 16:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-01 Cont ID  
Sent By cthroop Date 2021-09-01 Time 12:42 Rev Time 0.00
Received By rmcphers Date 2021-07-20 Time 06:32 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-09-01 Cont ID  
Sent By cthroop Date 2021-09-01 Time 12:33 Rev Time 0.00
Received By rmcphers Date 2021-09-01 Time 12:33 Sent To  
Notes
2021-09-01 12:34:09PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
2021-08-16 17:36:06 
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-02-25 Cont ID  
Sent By medwards Date 2022-02-25 Time 13:39 Rev Time 0.00
Received By medwards Date 2022-02-25 Time 13:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-12-02 Cont ID  
Sent By medwards Date 2021-12-02 Time 08:22 Rev Time 0.00
Received By medwards Date 2021-12-02 Time 08:22 Sent To  
Notes
2021-12-02 08:24:10REVISED SHEET M701 WAS NOT SUBMITTED IN THIS CYCLE AND
 THERE IS NO DETAIL 5 ON THE ORIGINAL DRAWING.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-04 Cont ID  
Sent By medwards Date 2021-08-04 Time 06:58 Rev Time 0.00
Received By medwards Date 2021-08-04 Time 06:42 Sent To  
Notes
2021-08-04 06:58:321ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21070558
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC
 101.5.1.1.2
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS (DIGITALLY SIGNED BY THE ENGINEER) FBC EC
 R403.7.1
  
 3) PLEASE SHOW THE TIE DOWN METHOD FOR THE CONDENSING
 UNITS. FBC RES M1307.2
  
 4) PLEASE SHOW THE CONDENSATION DRAINS AND THE
 TERMINATION LOCATION. FBC RES M1411.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-02-18 Cont ID  
Sent By ccole Date 2022-02-18 Time 16:39 Rev Time 0.00
Received By ccole Date 2022-02-18 Time 09:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-12-09 Cont ID  
Sent By ccole Date 2021-12-09 Time 13:17 Rev Time 0.00
Received By ccole Date 2021-12-09 Time 09:55 Sent To  
Notes
2021-12-09 13:21:172ND REVIEW FBC-2020 PLUMBING
 PERMIT-21070558
 12/9/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS 2-8 LISTED BELOW
 WERE NOT ADDRESSED. THE CORRECTED PLANS WERE NOT
 UPLOADED FOR REVIEW.
  
 2) P301, P302, & P601: PROVIDE 3-INCH DRAIN STACKS AND
 BRANCH DRAINS FOR THE WASHING MACHINES (WM-1)- SECTION
 406.2 FBC P. PLEASE NOTE THE A/P601 STACK CONTINUATION
 IS UNDERSIZED.
  
 3) P301 & P601: PROVIDE A FLOOR DRAIN FOR THE ICE
 MACHINE (IM-1) IF REQUIRED BY MANUFACTURER?S
 SPECIFICATIONS (NOT PROVIDED)- SECTION 412.2 FBC P.
  
 4) P301 & P601: SHOW THE LOCATION OF THE REQUIRED
 CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND
 SEWER- SECTION 708.1.2 FBC P.
  
 5) P401 & P602: SHOW THE LOCATIONS OF THE MAIN WATER
 DISTRIBUTION SHUTOFF VALVES FOR EACH DWELLING UNIT-
 SECTION 606.1 (2) (6) FBC P.
  
 6) P401, P701, P801: THE RINNAI RUR WATER HEATERS ARE
 LISTED FOR INDOOR USE, BUT THE PLAN SHOWS THE UNITS ON
 THE EXTERIOR OF THE BUILDING- SECTION 502.1 FBC P.
  
 7) P401, P402, P602, P701: THE HWR LINE IS NOT SHOWN IN
 THE WATER HEATER DETAIL- SECTION 607.2 FBC P. PLEASE
 PROVIDE HOT WATER PIPIE INSULATION DETAILS- THICKNESS
 AND R-VALUE- TABLE C403.2.10 FBC EC.
  
 8) P701: THE LOCATION OF THE EXPANSION TANK FOR THE
 TANKLESS WATER HEATER MUST BE IN ACCORDANCE WITH
 MANUFACTURER'S SPECIFICATIONS WHICH HAVE NOT BEEN
 PROVIDED- SECTION 502.1 FBC P. PLEASE NOTE THAT
 EXPANSION TANKS FOR STORAGE TYPE WATER HEATERS SHALL BE
 LOCATED DOWNSTREAM OF ALL CHECK VALVES AND PRESSURE
 REDUCING VALVES- SECTION 607.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-07-30 Cont ID  
Sent By ccole Date 2021-07-30 Time 11:11 Rev Time 0.00
Received By ccole Date 2021-07-29 Time 11:20 Sent To  
Notes
2021-07-30 11:14:551ST REVIEW FBC-2020 PLUMBING
 PERMIT-21070558
 7/30/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1.10 & P000: THE CODE RESEARCH DATA ON A1.10
 INDICATES THE USE AND OCCUPANCY OF THE BUILDING TO BE
 R3 WITH COMPLIANCE UNDER THE FBC RES. 2020, HOWEVER IT
 IS ALSO INDICATING COMPLIANCE WITH THE FBC
 ACCESSIBILITY CODE WHICH IS NOT COVERED IN THE
 RESIDENTIAL CODE. THE PLUMBING COMPLIANCE DATA UNDER
 NOTE #1 (P000) INDICATES COMPLIANCE WITH THE FBC
 PLUMBING WHICH IS THE COMMERCIAL CODE. DUE TO THESE
 CONFLICTS THE FOLLOWING REVIEW WILL BE CONDUCTED WITH
 THE MOST STRINGENT CODES APPLIED.
  
 2) P301, P302, & P601: PROVIDE 3-INCH DRAIN STACKS AND
 BRANCH DRAINS FOR THE WASHING MACHINES (WM-1)- SECTION
 406.2 FBC P. PLEASE NOTE THE A/P601 STACK CONTINUATION
 IS UNDERSIZED.
  
 3) P301 & P601: PROVIDE A FLOOR DRAIN FOR THE ICE
 MACHINE (IM-1) IF REQUIRED BY MANUFACTURER?S
 SPECIFICATIONS (NOT PROVIDED)- SECTION 412.2 FBC P.
  
 4) P301 & P601: SHOW THE LOCATION OF THE REQUIRED
 CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND
 SEWER- SECTION 708.1.2 FBC P.
  
 5) P401 & P602: SHOW THE LOCATIONS OF THE MAIN WATER
 DISTRIBUTION SHUTOFF VALVES FOR EACH DWELLING UNIT-
 SECTION 606.1 (2) (6) FBC P.
  
 6) P401, P701, P801: THE RINNAI RUR WATER HEATERS ARE
 LISTED FOR INDOOR USE, BUT THE PLAN SHOWS THE UNITS ON
 THE EXTERIOR OF THE BUILDING- SECTION 502.1 FBC P.
  
 7) P401, P402, P602, P701: THE HWR LINE IS NOT SHOWN IN
 THE WATER HEATER DETAIL- SECTION 607.2 FBC P. PLEASE
 PROVIDE HOT WATER PIPIE INSULATION DETAILS- THICKNESS
 AND R-VALUE- TABLE C403.2.10 FBC EC.
  
 8) P701: THE LOCATION OF THE EXPANSION TANK FOR THE
 TANKLESS WATER HEATER MUST BE IN ACCORDANCE WITH
 MANUFACTURER'S SPECIFICATIONS WHICH HAVE NOT BEEN
 PROVIDED- SECTION 502.1 FBC P. PLEASE NOTE THAT
 EXPANSION TANKS FOR STORAGE TYPE WATER HEATERS SHALL BE
 LOCATED DOWNSTREAM OF ALL CHECK VALVES AND PRESSURE
 REDUCING VALVES- SECTION 607.3 FBC P.
  
 9) P701: PLEASE PROVIDE A SHOWER FLOOR AND LINER
 DETAIL- SECTION 417.5.2 FBC P.
  
 10) SHEET A-410 ACCESSIBLE PLUMBING FIXTURE DETAILS
 MISSING PER FBC ACC-
 A) CLEAR FLOOR SPACE DIAGRAM DIMENSIONS FOR THE WATER
 CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETER DIMENSION SECTION 304.3.
 D) CLEAR FLOOR SPACE DIAGRAM DIMENSIONS FOR THE SHOWER-
 SECTION 608.2.1
 E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWERS- SECTION 608.3.2.
 PLEASE SEE FIGURE 608.3.2 AND CORRECT THE DRAWING.
 F) VERTICAL GRAB BARS ARE NOT IN COMPLIANCE WITH
 SECTION 609.4 WHICH REQUIRES GRAB BARS TO BE INSTALLED
 IN HORIZONTAL POSITIONS.
 G) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SECTION 608.5.2. WHERE A SEAT IS PROVIDED, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 INSTALLED ON THE BACK WALL ADJACENT TO THE SEAT WALL
 AND SHALL BE LOCATED 27 INCHES MAXIMUM FROM THE SEAT
 WALL.
 H) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6.
 SPECS WERE NOT INCLUDED IN THE FIXTURE SCHEDULE ON
 P801.
 I) ACCESSIBLE SHOWER SEAT DETAILS AND FIGURES- SECTIONS
 610.3 & 610.3.2.
  
 11) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 FBC P.
  
 12) PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 2 Status N Date 2021-12-09 Cont ID  
Sent By ccole Date 2021-12-09 Time 13:12 Rev Time 0.00
Received By ccole Date 2021-12-09 Time 09:55 Sent To  
Notes
2021-12-09 13:15:05SEPARATE PERMIT AND PLANS REQUIRED FOR THE IRRIGATION
 SYSTEM.

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 1 Status F Date 2021-07-30 Cont ID  
Sent By ccole Date 2021-07-30 Time 11:19 Rev Time 0.00
Received By ccole Date 2021-07-30 Time 11:15 Sent To  
Notes
2021-07-30 11:20:141ST REVIEW FBC-2020 IRRIGATION
 PERMIT- 21070558
 7/30/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE IRRIGATION PLANS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2021-12-08 Cont ID  
Sent By rmcphers Date 2021-12-08 Time 11:31 Rev Time 0.00
Received By rmcphers Date 2021-12-08 Time 11:31 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-09-01 Cont ID  
Sent By cthroop Date 2021-09-01 Time 12:34 Rev Time 0.00
Received By rmcphers Date 2021-09-01 Time 12:34 Sent To  
Notes
2021-09-01 12:34:36SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-02-24 Cont ID  
Sent By rmcphers Date 2022-02-24 Time 12:57 Rev Time 0.00
Received By rmcphers Date 2022-02-24 Time 12:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-09 Cont ID  
Sent By ccole Date 2021-12-09 Time 13:27 Rev Time 0.00
Received By ccole Date 2021-12-09 Time 13:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-09-01 Cont ID  
Sent By cthroop Date 2021-09-01 Time 12:42 Rev Time 0.00
Received By rmcphers Date 2021-09-01 Time 12:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2022-04-15 Cont ID  
Sent By llouie Date 2022-04-15 Time   Rev Time 0.00
Received By llouie Date 2022-04-15 Time   Sent To  
Notes
2022-04-15 15:25:57** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED
 PRIOR TO ZONING APPROVAL OF THIS PERMIT. TO DATE, A
 LANDSCAPE PERMIT HAS NOT BEEN SUBMITTED.
  
 [7/27/21 AND 2/16/21 REPEAT COMMENT: NOT ADDRESSED.
 STAFF IS STILL WAITING ON THE SUBMISSION OF A LANDSCAPE
 PERMIT.]
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, FENCING,
 ETC.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  
 * ZONING APPROVAL TO USE PROPERTY AS A GROUP HOME
 SIGNED BY AV.
  

Review Stop Z ZONING
Rev No 3 Status F Date 2022-02-16 Cont ID  
Sent By llouie Date 2022-02-16 Time   Rev Time 0.00
Received By llouie Date 2022-02-16 Time   Sent To  
Notes
2022-02-16 10:32:24** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SIDE CORNER SETBACK HAS BEEN CHANGED AND DOES NOT
 MEET THE MINIMUM CORNER SIDE SETBACK PER THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS). A MINIMUM OF 12.5
 FT. SIDE CORNER SETBACK IS REQUIRED ALONG MANNING
 AVENUE. [ZLDR S.94-72(A.)]
  
 2.) SHOW HEIGHT OF THE BUILDING FROM GRADE (NOT FFE) TO
 THE HIGHEST POINT OF THE STRUCTURE. THE BUILDING CANNOT
 EXCEED 30 FT. IN HEIGHT. [ZLDR S.94-72(A)]
  
 3.) A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED
 PRIOR TO ZONING APPROVAL OF THIS PERMIT. TO DATE, A
 LANDSCAPE PERMIT HAS NOT BEEN SUBMITTED. [REPEAT
 COMMENT: STAFF IS STILL WAITING ON THE SUBMISSION OF A
 LANDSCAPE PERMIT.]
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, FENCING,
 ETC.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  
 * ZONING APPROVAL TO USE PROPERTY AS A GROUP HOME
 SIGNED BY AV

Review Stop Z ZONING
Rev No 2 Status F Date 2021-12-08 Cont ID  
Sent By llouie Date 2021-12-08 Time 16:18 Rev Time 0.00
Received By llouie Date 2021-12-08 Time   Sent To  
Notes
2021-12-08 16:18:24** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) HAS THE PROPOSED USE RECEIVED (PRELIMININARY)
 APPROVAL FOR THE PROPERTY TO BE UTLIZED AS A GROUP HOME
 AS SPECIFIED IN THE PLANS?
  
 2.) A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED
 PRIOR TO ZONING APPROVAL OF THIS PERMIT. TO DATE, A
 LANDSCAPE PERMIT HAS NOT BEEN SUBMITTED.
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, FENCING,
 ETC.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7

Review Stop Z ZONING
Rev No 1 Status F Date 2021-07-27 Cont ID  
Sent By awooten Date 2021-07-27 Time   Rev Time  
Received By llouie Date 2021-07-27 Time   Sent To  
Notes
2021-07-27 15:57:36 
 ** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) ALTHOUGH PROVIDED IN THE SITE DATA TABULAR, PLEASE
 PROVIDE BUILDING SETBACK DIMENSIONS IN THE SITE PLAN TO
 DEMONSTRATE COMPLIANCE WITH THE ZLDRS AND CONSISTENCY
 WITH THE INFORMATION PROVIDED IN THE TABULAR.
  
 2.) PROVIDE SETBACK DIMENSIONS FROM THE PROPOSED
 MECHANICAL EQUIPMENT PAD (FOR GENERATOR AND A/C
 COMPRESSOR UNITS) TO THE PROPERTY LINE(S). PLEASE NOTE
 THAT PER ZLDR S.94-305(B)(4), THE PAD CANNOT PROJECT
 MORE THAN 4 FT. INTO A REQUIRED SETBACK. THE DIMENSIONS
 ARE REQUIRED TO DEMONSTRATE COMPLIANCE.
  
 3.) PROVIDE CALCULATIONS IN THE SITE PLAN THAT
 DEMONSTRATES THAT THERE IS A MINIMUM OF 1,000 SQ. FT.
 OF LANDSCAPED AREA WITHIN THE REQUIRED FRONT SETBACK
 (AREA WITHIN THE FIRST 25 FT. OF 54TH STREET). [ZLDR
 S.94-442(C)(2)]
  
 4.) DRIVEWAY SHALL BE SETBACK A MINIMUM OF 3 FT. FROM
 THE REAR AND CORNER SIDE PROPERTY LINE. [ZLDR
 S.94-482(D)]
  
 5.) DRIVEWAY CANNOT EXCEED 20 FT. IN WIDTH AT THE
 PROPERTY LINE. PROVIDE DIMENSIONS TO DEMONSTATE
 COMPLIANCE. [ZLDR S.94-312(1)]
  
 6.) A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED
 PRIOR TO ZONING APPROVAL OF THIS PERMIT.
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, FENCING,
 ETC.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved