Plan Review Details - Permit 21070522
Plan Review Stops For Permit 21070522
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-07-23 Cont ID  
Sent By pvalenti Date 2021-07-23 Time 12:55 Rev Time 0.00
Received By pvalenti Date 2021-07-23 Time 12:55 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-07-22 Cont ID  
Sent By pvalenti Date 2021-07-22 Time 06:18 Rev Time 0.00
Received By pvalenti Date 2021-07-21 Time 16:17 Sent To  
Notes
2021-07-22 06:19:08****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-07-27 Cont ID  
Sent By dbattles Date 2021-07-27 Time 10:09 Rev Time 0.00
Received By dbattles Date 2021-07-27 Time 10:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-07-23 Cont ID  
Sent By pvalenti Date 2021-07-23 Time 13:03 Rev Time 0.00
Received By pvalenti Date 2021-07-23 Time 12:55 Sent To  
Notes
2021-07-23 13:05:59PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT
 APPLICATION TO BUILDING DIVISION);
 SCHEDULE A FINAL PLUMBING #703, INSPECTION, FOR PERMIT
 # 21070589

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-22 Cont ID  
Sent By pvalenti Date 2021-07-22 Time 06:19 Rev Time 0.00
Received By pvalenti Date 2021-07-21 Time 16:17 Sent To  
Notes
2021-07-22 06:40:55****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING
 CODE, BUILDING 3303:
  
 1.OK
  
 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS)
 RELEASE OF SERVICE CONFIRMATION
 (PROVIDE BUILDING NUMBERS ON FORM)
  
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON
 THEIR FORM "DEMOLITION APPLICATION"
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF A WATER TRUCK IS DESIRED, PROVIDE INFORMATION AS TO
 THE WATER TANK CAPACITY AND REQUIREMENT THAT ONLY
 POTABLE WATER WILL BE USED AND WILL COME FROM OFF-SITE
 LOCATIONS ONLY.
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE
 NOTED ON THEIR FORM.
 BACKFLOW - BEFORE SCHEDULING THE 703, THE BACKFLOW
 DEVICE NEEDS TO BE TESTED AND CERTIFIED BY THE CITY?S
 UTILITIES DEPT, 561-822-2244.
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT
 APPLICATION TO BUILDING DIVISION);
 SCHEDULE A FINAL PLUMBING #703 FOR PERMIT # 21070589.
  
 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST
 CONTROL COMPANY STATING THAT
 DEMOLITION ADDRESS HAS BEEN INSPECTED AND/OR TREATED
 FOR RODENTS.
 (PROVIDE BUILDING NUMBERS ON FORM)
  
 6. COMPLETE THE DEMO DEBRIS FORM:
 (PROVIDE BUILDING NUMBERS ON FORM)
  
 7. OK
  
 8. PROVIDE A STORMWATER POLLUTION PREVENTION PLAN.
  
 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING
 ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2021-07-19 Cont ID  
Sent By rrossano Date 2021-07-19 Time   Rev Time  
Received By rrossano Date 2021-07-19 Time   Sent To  
Notes
2021-07-19 11:39:23PASSED WITH PROVISO:
  
 PER CHAPTER 556 OF THE FLORIDA STATE STATUTES, YOU MUST
 CALL 811 FOR UTILITY LOCATES AT LEAST TWO FULL BUSINESS
 DAYS IN ADVANCE OF ANY CONSTRUCTION OR DEMOLITION WORK.
 INFORMATION CAN BE FOUND HERE:
 HTTP://WWW.SUNSHINE811.COM/
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-07-24 Cont ID  
Sent By fmittner Date 2021-07-24 Time 12:03 Rev Time 0.00
Received By fmittner Date 2021-07-24 Time 12:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-26 Cont ID  
Sent By lmarchan Date 2021-07-26 Time 08:36 Rev Time 0.00
Received By lmarchan Date 2021-07-12 Time 14:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-07-22 Cont ID  
Sent By pvalenti Date 2021-07-22 Time 06:18 Rev Time 0.00
Received By pvalenti Date 2021-07-21 Time 16:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-07-24 Cont ID  
Sent By fmittner Date 2021-07-24 Time 12:03 Rev Time 0.00
Received By fmittner Date 2021-07-24 Time 12:02 Sent To  
Notes
***NONE***