2021-07-15 09:31:09 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-21070356 |
| 7/15/2021 |
| |
| CODES IN EFFECT: |
| |
| FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| EDITION 2020 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) A GAS GRILL IS LABELED FOR OUTSIDE USE AND IT SEEMS |
| TO BE IN A COVERED PATIO, IF SO PLEASE PROVIDE |
| MANUFACTURES RECOMMENDATION FOR A VENTILATION HOOD, |
| 2020 FBC FG SEC.G2408.1. |
| 2) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2020 FBC FUEL GAS SEC.410.1 OR 2020 FBC |
| FUEL GAS RES. SEC. G2421.1. |
| 3) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| DRAWN. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 4) A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE |
| OF IGNITION, WPB AMENDMENTS TO THE FBC SEC. 105.1 |
| 5) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR. 2020 FBC FUEL GAS SEC. |
| 409.4, FBC FUEL GAS RES. SEC. G2420.4. |
| 6) NEED A SHUTOFF VALVE AND HARD CAP FOR FUTURE BBQ |
| GRILLS SHOW ON GAS ISOMERIC P-1 APPLIANCE SHUTOFF 2020 |
| FBC FUEL GAS RES. SEC. 409.5, APPLIANCE CONNECTION 2020 |
| FBC FUEL GAS RES. SEC. 404.15, 411. |
| 7) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2020 |
| FBC FUEL GAS SEC. 304.1, 614.5 (CLOTHES DRYERS) OR 2020 |
| FBC FUEL GAS RES. SEC. G2407.1 AND G2439.4 (CLOTHES |
| DRYERS). |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| ATELYO BELISLE |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| AVAILABLE FROM 1:00 PM TO 4:00 PM |
| [email protected] |
| 561-805-6695 |
| |