Plan Review Details - Permit 21070246
Plan Review Stops For Permit 21070246
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-08-17 Cont ID  
Sent By rmcphers Date 2021-08-17 Time 13:49 Rev Time 0.00
Received By rmcphers Date 2021-08-17 Time 13:19 Sent To  
Notes
2021-08-17 13:49:47PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-17 Cont ID  
Sent By rmcphers Date 2021-08-17 Time 14:08 Rev Time 0.00
Received By rmcphers Date 2021-08-17 Time 13:19 Sent To  
Notes
2021-08-17 14:08:38BUSINESS REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) DRAWING S-1 "OCCUPANCY NOTES" SHOWS A ROOM LEGEND -
 THE LEGEND ROOM DESIGNATION DOES NOT MATCH THE FLOOR
 PLAN - PLEASE CORRECT.
 2) PLEASE SHOW THE WALL FINISH AROUND THE MOP SINK TO
 COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE).
 3) PLEASE SHOW THE DOOR MANEUVERING CLEARANCE (18"
 BESIDE THE LATCH SIDE OF THE DOOR) FOR THE DOOR FROM
 THE BACK ROOMS TO THE FRONT ROOM FBC A404.2.4
 4) PLEASE SHOW THE ACCESSIBLE SEATING PER FBC A226.1
 GENERAL.
 WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION
 OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING
 SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL
 COMPLY WITH 902.
 5) PLEASE SHOW THE COUNTER HEIGHT AND CLEAR FLOOR SPACE
 FOR THE SALES AND SERVICE COUNTERS TO COMPLY WITH FBC
 A904.4
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-08-20 Cont ID  
Sent By jleahy Date 2021-08-20 Time 15:15 Rev Time 0.00
Received By jleahy Date 2021-08-20 Time 15:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-07-19 Cont ID  
Sent By pleduc Date 2021-07-19 Time   Rev Time 0.00
Received By pleduc Date 2021-07-19 Time 13:01 Sent To  
Notes
2021-07-19 13:08:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET S 1 - THERE IS AN INDICATION FOR DOOR 1 COMING
 OUT OF THE KITCHEN OPENS INTO THE EXIT CORRIDOR.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR,
 A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF
 THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR
 LEAF IS EQUIPPED
 WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT
 REQUIRED BY THE PROVISIONS
 OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL.
  
 PLEASE REVIEW AND CORRECT. *****THE DOOR CAN BE CHANGED
 TO SWING IN OR THE EXIT SIGN OVER DOOR E FROM THE LOBBY
 AREA CAN BE REMOVED AS IT APPEARS A 2ND EXIT
 FROM THE LOBBY AREA IS NOT REQUIRED****UNDER 50
 OCCUPANCY LOAD IS MERCANTILE PER NFPA 101 AND 1 EXIT
 CAN BE USED FROM THAT AREA WITH THE REAR EXIT SERVING
 THOSE AREAS.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-20 Cont ID  
Sent By jleahy Date 2021-08-20 Time 15:15 Rev Time 0.00
Received By jleahy Date 2021-07-16 Time 12:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-19 Cont ID  
Sent By medwards Date 2021-08-19 Time 13:21 Rev Time 0.00
Received By medwards Date 2021-08-19 Time 13:21 Sent To  
Notes
2021-08-19 13:21:501ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21070246
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE MECHANICAL DRAWINGS. FBC 107.2.1
  
 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE
 OF SPACE FOR THIS RESTAURANT ACCORDING TO FBC M
 403.3.1.1 AND TABLE 403.3.1.1
  
 3) PLEASE ADD A NOTE ON THE MECHANICAL DRAWINGS STATING
 THAT THE HOOD SYSTEM WILL NOT BE REVIEWED UNDER THIS
 PERMIT. A SEPARATE PERMIT, DRAWINGS AND REVIEW WILL BE
 REQUIRED FOR THE HOOD SYSTEM.
  
 4) PLEASE SHOW THE KITCHEN EXHAUST PER FBC M 507.1
 EXCEPTION 2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-08-11 Cont ID  
Sent By tklarge Date 2021-08-11 Time 10:51 Rev Time 0.00
Received By tklarge Date 2021-08-06 Time 14:52 Sent To  
Notes
2021-08-11 09:59:281) SHT. S-1 CALLS OUT THIS OCUPANCY AS MERCANTILE "B".
 THERE IS NO SUCH OCCUPANCY CLASSIFICATION IN THE
 BUILDING CODE. THIS SPACE WAS PREVIOUSLY CLASIFIED AS
 AN A-2 OCCCUPANCY ACORDING TO CITY RECORDS. SEC.
 303.1.1 OF THE FBC-BUILDING STATES A BUILDING OR TENANT
 SPACE USED FOR ASSEMBLY PURPOSES WITH AN OCCUPANT LOAD
 OF LESS THAN 50 PERSONS SHALL BE CLASSIFIED AS A GROUP
 "B" OCUPANCY.CLARIFY.
 2) SHT. S-1 HAS THE OCUPANT LOAD OF THIS SPACE AS 32
 PERSONS. IF THIS OCCUPANT LOAD IS CORRECT, THEN TWO
 SEPARATE TOILET ROOMS ARE REQUIRED PER
 FBC-PLUMBING-TABLE 403.1 AND SEC. 403.2.
 3) THE DOOR TO THE ACCESSIBLE TOILET ROOM CANNOT SWING
 INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY.FBC-ACCESS.
 SEC.603.2.3. (SEE EXCEPTION #2). THE PREVIOUS PLANS ON
 FILE SHOW THE DOOR WINGING OUT.CLARIFY.
 4) SHOW THE FIXTURE CLEARANCES OF THE TOILET FIXTURES
 ON THE FLOOR PLAN FOR THE TOILET ROOM. COMPLY WITH
 FBC-ACCESS. SEC.604.2, FBC-PLUMBING SEC.405.3.1.
 5) THE WALL FINISH AROUND THE MOP SINK SHALL COMPLY
 WITH FBC-BUILDING SEC. 1210.2.2.
 6) SHT. S-1 -SHOW THE REQUIRED CLEAR FLOOR SPACES FOR
 THE HANDICAPPED ACCESSIBLE PLUMBING FIXTURES ON THE
 PLAN AND SHOW THE DIMENSIONS OF THE CLEAR FLOOR SPACES
 ON THE PLANS. COMPLY WITH FBC - ACCESS. SECS.604.3..1,
 606.2.
 7) THE HEIGHT OF THE SERVICE COUNTER SHALL COMPLY WITH
 FBC-ACCESS. SEC.904.4.1.
 8) INDICATE ON THE PLAN IF THERE WILL BE ANY SEATING AT
 THE EXTERIOR PATIO AREA AND COVERED WALWAY ASSOCIATED
 WITH THIS BUSINESS. IF SO, THE OCCUPANT LOAD MUST BE
 INCLUDED IN THE TOTAL OCCUPANT LOAD. FBC-PLUMBING SEC.
 403.1.
 9) A DRINKING FOUNTAIN IS REQUIRED PER FBC-PLUMBING
 SEC.410.3 AND TABLE 403.1. A MINIMUM OF 2 DRINKING
 FOUNTAINS ARE REQUIRED. FBC-ACCESS. SEC.211.1,
 10) SHT. S-1 - OCUPANCY CLASSIFICATION NOTE REFERS O
 THE 2010 EDITION OF THE FBC. THE 2020 CODE IS IN
 EFFECT.
 11) THE EXISTING PLANS FOR THIS SPACE ON FILE WITH THE
 CITY SHOW THE GREASE INTERCEPTOR AS A 100 GPM UNIT BUT
 THE EQUIPMENT SCHEDULE ON SHT. S-2 SHOWS THE GREASE
 INTERCCEPTOR AS 1250 GALLONS. CLARIFY.
 12) INDIATE THE CLASSIFICATION OF WORK ON THE PLANS PER
 FBC-EXISTING BUILDING SEC.601.1. ALSO, INDICATE THE
 COMPLIANCE METHOD PER FBC-EXISTING SEC.301.3.
 13) IT APPEARS THAT A HAND SINK HAS BEEN REMOVED AND
 THE SERVICE SINK RELOCATED BASED ON PLANS FROM THE
 PREVIOUS OCCUPANCY. SUBMIT A WATER AND SANITARY RISER
 DIAGRAM TO SHOW THE CHANGES TO THE SANITARY SYSTEM.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-08-17 Cont ID  
Sent By rmcphers Date 2021-08-17 Time 14:10 Rev Time 0.00
Received By rmcphers Date 2021-08-17 Time 14:09 Sent To  
Notes
2021-08-17 14:11:27SIGNATURE REVIEW
 DRAWINGS DO NOT SHOW AS ELECTRONICALLY SIGNED IN ADOBE
 READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED
 TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER
 OR ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR
 - IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  