Plan Review Details - Permit 21070181
Plan Review Stops For Permit 21070181
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-27 Cont ID  
Sent By jwitmer Date 2021-07-27 Time 14:36 Rev Time 0.00
Received By jwitmer Date 2021-07-27 Time 13:11 Sent To  
Notes
2021-07-27 14:36:24WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21070181
 ADD: 1392 7THST.
 CONT: GARDENIA CHILDREN / ST. HILAIRE MARIE
 TEL:
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 27TH/ 2021
 ACTION: DENIED
  
 1) THE ORIGINAL BUSINESS TAX LICENSE INDICATES THIS
 BUSINESS WAS ESTABLISHED 09/14/2017. YES, A BUSINESS
 TAX RECEIPT WAS ESTABLISHED BUT WE DO NOT SEE THERE WAS
 EVER A PERMIT PULLED TO CHANGE THE OCCUPANCY/ USAGE FOR
 A CHILD CARE FACILITY WITHIN A DWELLING FOR 5 OR FEWER
 PERSONS WAS EVER APPLIED FOR OR ISSUED.
 SECTION 310.5.1 OF THE 2020 FBC-BUILDING CODE
 REFERENCES THE 2020 FBC-RESIDENTIAL CODE PROVIDE AN
 AUTOMATIC SPRINKLER SYSTEM IS INSTALLED IN ACCORDANCE
 WITH SECTION 903.3.1.3 (2020 FBC-BUILDING CODE) OR
 P2904 OF THE FLORIDA BUILDING CODE, RESIDENTIAL CODE.
 THIS IS A REQUIREMENT FOR 5 OR FEWER PERSONS RECEIVING
 CARE THAT ARE WITHIN A SINGLE-FAMILY DWELLING.
  
 2) THE REQUEST TO UPGRADE THE LICENSE UP TO 12 PERSONS
 NO LONGER IS UNDER THE SINGLE-FAMILY RESIDENCE
 REQUIREMENTS. DAY CARE OCCUPANCIES ARE CONSIDERED
 SPECIAL OCCUPANCIES AND FOUND IN CHAPTER 4 SECTION
 466.1- 466.10.5.5.1 AND ARE TO BE CONSIDERED A NEW
 OCCUPANCY TYPE. PLANS WILL NEED TO BE DRAWN UP SHOWING
 HOW ALL OF THE CODE REQUIREMENTS ARE GOING TO BE MET.
  
 3) THE OTHER ISSUE WITH DAYCARE FACILITIES IS THE CODE
 REQUIREMENTS FOUND UNDER SECTION 305.2 GROUP E, DAY
 CARE FACILITIES. THIS GROUP INCLUDES BUILDINGS AND
 STRUCTURES, OR PORTION THEREOF OCCUPIED BY MORE THAN 5
 CHILDREN OLDER THAN 2 ? YEARS OF AGE WHO RECEIVE
 EDUCATIONAL, SUPERVISION OR PERSONAL CARE SERVICES FOR
 FEWER THAN 24 HOURS PER DAY. THIS SECTION WILL BRING
 YOU TO THE SPECIALTY CHAPTER 4 SECTION 468
 REQUIREMENTS.
  
 4) THE SUBMITTED PLANS THERE IS NOT SUFFICIENT
 INFORMATION TO DO A COMPLETE REVIEW. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-07-22 Cont ID  
Sent By jleahy Date 2021-07-22 Time 15:08 Rev Time 0.00
Received By jleahy Date 2021-07-22 Time 14:21 Sent To  
Notes
2021-07-22 15:08:46NO ELECTRIC WORK SHOWN JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-07-09 Cont ID  
Sent By pleduc Date 2021-07-09 Time   Rev Time 0.00
Received By pleduc Date 2021-07-09 Time 12:01 Sent To  
Notes
2021-07-09 13:09:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE NO INDICATIONS OF SMOKE ALARMS.
  
 PER NFPA 101
  
 17.6.3.4.1 SMOKE ALARMS SHALL BE INSTALLED WITHIN
 DAY-CARE HOMES IN
 ACCORDANCE WITH 9.6.2.10.
  
 AS A NEW LARGER OCCUPANCY, THE SA SHALL BE
 INTERCONNETED SO THAT
 WHEN ONE GOES OFF TEHY ALL GO OFF.
  
 PER NFPA 72
  
 29.5.1.1* WHERE REQUIRED BY OTHER GOVERNING LAWS,
 CODES, OR STANDARDS FOR A SPECIFIC TYPE OF
 OCCUPANCY, APPROVED SINGLE- AND MULTIPLE-STATION SMOKE
 ALARMS SHALL BE INSTALLED AS FOLLOWS:
 (1)* IN ALL SLEEPING ROOMS AND GUEST ROOMS
 (2)* OUTSIDE OF EACH SEPARATE DWELLING UNIT SLEEPING
 AREA, WITHIN 21 FT (6.4 M) OF ANY DOOR
 TO A SLEEPING ROOM, WITH THE DISTANCE MEASURED ALONG A
 PATH OF TRAVEL
 (3) ON EVERY LEVEL OF A DWELLING UNIT, INCLUDING
 BASEMENTS
  
 PLEASE PROVIDE SA LOCATIONS AND DETAILS OF BEING
 INTERCONNECTED. FYI THEY DO NOT NEED TO BE HARD WIRED,
 THEY MAKE BLUETOOTH SA THAT ARE BATTERY POWERED.
  
  
 2) WITH THE PROPOSED INCREASE IN CLIENTS, THE OCCUPANCY
 IS CLASSIFIED AS A GROUP DAY CARE HOME.
  
 17.6.1.4.1 SUBCLASSIFICATION OF DAY-CARE HOMES.
 SUBCLASSIFICATION
 OF DAY-CARE HOMES SHALL COMPLY WITH 17.6.1.4.1.1 AND
 17.6.1.4.1.2.
  
 17.6.1.4.1.1 FAMILY DAY-CARE HOME. A FAMILY DAY-CARE
 HOME SHALL
 BE A DAY-CARE HOME IN WHICH MORE THAN THREE, BUT FEWER
 THAN SEVEN,
 CLIENTS RECEIVE CARE, MAINTENANCE, AND SUPERVISION BY
 OTHER THAN THEIR
 RELATIVE(S) OR LEGAL GUARDIAN(S) FOR LESS THAN 24 HOURS
 PER DAY, GENERALLY
 WITHIN A DWELLING UNIT.
 17.6.1.4.1.2 GROUP DAY-CARE HOME. A GROUP DAY-CARE HOME
 SHALL
 BE A DAY-CARE HOME IN WHICH NOT LESS THAN 7, BUT NOT
 MORE THAN 12,
 CLIENTS RECEIVE CARE, MAINTENANCE, AND SUPERVISION BY
 OTHER THAN THEIR
 RELATIVE(S) OR LEGAL GUARDIAN(S) FOR LESS THAN 24 HOURS
 PER DAY, GENERALLY
 WITHIN A DWELLING UNIT.
  
 17.6.1.7 OCCUPANT LOAD.
  
 17.6.1.7.2 IN GROUP DAY-CARE HOMES, ALL OF THE
 FOLLOWING SHALL APPLY:
 (1) THE MINIMUM STAFF-TO-CLIENT RATIO SHALL BE NOT LESS
 THAN TWO STAFF
 FOR UP TO 12 CLIENTS.
 (2) THERE SHALL BE NOT MORE THAN 3 CLIENTS INCAPABLE OF
 SELF-PRESERVATION.
 (3) THE STAFF-TO-CLIENT RATIO SHALL BE PERMITTED TO BE
 MODIFIED BY THE
 AUTHORITY HAVING JURISDICTION WHERE SAFEGUARDS IN
 ADDITION TO THOSE
 SPECIFIED BY SECTION 17.6 ARE PROVIDED.
  
 IT IS THE INTENT OF THIS CODE TO CLASSIFY CHILDREN
 UNDER THE AGE OF 30 MONTHS
 AS INCAPABLE OF SELF-PRESERVATION. EXAMPLES OF DIRECT
 INTERVENTION BY
 STAFF MEMBERS INCLUDE CARRYING A CLIENT, PUSHING A
 CLIENT OUTSIDE IN A
 WHEELCHAIR, AND GUIDING A CLIENT BY DIRECT HAND-HOLDING
 OR CONTINUED
 BODILY CONTACT. IF CLIENTS CANNOT EXIT THE BUILDING BY
 THEMSELVES WITH
 MINIMAL INTERVENTION FROM STAFF MEMBERS, SUCH AS VERBAL
 ORDERS, CLASSIFICATION
 AS INCAPABLE OF SELF-PRESERVATION SHOULD BE CONSIDERED.
  
 PLEASE PROVIDE DETAILS ON THE NUMBER AND AGE OF CLIENTS
 AND WITH THE STAFF TO CLIENT RATIO THAT COMPLY WITH THE
 CODE
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-02 Cont ID  
Sent By pvalenti Date 2021-08-02 Time 07:27 Rev Time 0.00
Received By pvalenti Date 2021-07-08 Time 13:34 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-07-27 Cont ID  
Sent By jwitmer Date 2021-07-27 Time 14:37 Rev Time 0.00
Received By jwitmer Date 2021-07-27 Time 13:17 Sent To  
Notes
2021-07-27 14:36:58IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected].
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-07-21 Cont ID  
Sent By medwards Date 2021-07-21 Time 10:42 Rev Time 0.00
Received By medwards Date 2021-07-21 Time 10:42 Sent To  
Notes
2021-07-21 10:47:511) PLEASE IDENTIFY THE EXISTING OCCUPANCY AND THE NEW
 OCCUPANCY CLASSIFICATION. FBC 301
 2) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS ALONG WITH MECHANICAL DRAWINGS FOR THIS
 CHANGE OF USE. THESE DRAWINGS WOULD NEED TO SHOW HOW
 THIS STRUCTURE WOULD MEET THE MECHANICAL VENTILATION
 FOR THIS NEW CHANGE OF USE. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-07-26 Cont ID  
Sent By ccole Date 2021-07-26 Time 13:59 Rev Time 0.00
Received By ccole Date 2021-07-26 Time 13:30 Sent To  
Notes
2021-07-26 13:59:531ST REVIEW FBC-2020 PLUMBING
 PERMIT-21070181
 7/26/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION OF THE
 DAYCARE FACILITY- SECTION 302.1FRBC B.
 FBC B. BASED ON THE INCREASE TO 12 CHILDREN THIS
 APPEARS TO BE A CHANGE OF OCCUPANCY TO AN EDUCATIONAL
 (E) OCCUPANCY- SECTION 202 FBC EX AND SECTION 305.2 FBC
 B. REFER TO SECTION 1010.1 FBC EX AND PROVIDE PLUMBING
 FIXTURE CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC
 P. PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF PLUMBING FIXTURES. PLEASE NOTE THAT
 ALL NEW INSTALLATIONS OF BATHROOM PLUMBING FIXTURES
 SHALL BE IN COMPLIANCE WITH SECTION 213.1 FBC ACC. AND
 SHALL BE ACCESSIBLE. COMPLETE PLUMBING PLANS,
 ISOMETRICS, AND DETAILS IN COMPLIANCE WITH CHAPTER 6
 FBC ACC SHALL BE PROVIDED- SECTION 107.2.1 AND
 107.3.5.1.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-07-27 Cont ID  
Sent By jwitmer Date 2021-07-27 Time 14:37 Rev Time 0.00
Received By jwitmer Date 2021-07-27 Time 13:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-07-29 Cont ID  
Sent By AV Date 2021-07-29 Time 16:03 Rev Time 0.00
Received By ajones Date 2021-07-29 Time 16:03 Sent To  
Notes
2021-07-29 16:04:477/29/21- THE USE IS PERMITTED
  
 ANGELLA VANN
 5618221441
 [email protected]