Plan Review Details - Permit 21070174
Plan Review Stops For Permit 21070174
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-02-07 Cont ID  
Sent By cpuell Date 2022-02-07 Time 15:05 Rev Time 0.00
Received By cpuell Date 2022-02-07 Time 15:05 Sent To  
Notes
2022-02-07 15:05:24ADDRESS APPROPRIATE FOR PROJECT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-05-16 Cont ID  
Sent By jleahy Date 2022-05-16 Time 13:45 Rev Time 0.00
Received By jleahy Date 2022-05-16 Time 13:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-02-25 Cont ID  
Sent By mpeterso Date 2022-02-25 Time 15:02 Rev Time 0.00
Received By mpeterso Date 2022-02-25 Time 15:02 Sent To  
Notes
2022-02-25 15:03:19ELECTRIC REVIEW FAILED
 1) NO CONDUIT, CONDUCTORS, OR OVERCURRENT PROTECTION
 DETAILED. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2022-04-19 Cont ID  
Sent By gpatrie Date 2022-04-19 Time 14:19 Rev Time 0.00
Received By gpatrie Date 2022-04-19 Time   Sent To  
Notes
2022-04-19 14:19:00CONTRACTOR NEEDS TO SUBMIT A RIGHT-OF-WAY PERMIT.
  
 CONTACT [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-05-18 Cont ID  
Sent By aoliver Date 2022-05-18 Time 06:56 Rev Time 0.00
Received By aoliver Date 2022-04-28 Time 14:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-20 Cont ID  
Sent By jgomez Date 2022-04-20 Time 10:14 Rev Time 0.00
Received By jgomez Date 2022-02-06 Time 08:52 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2021-07-13 Cont ID  
Sent By shill Date 2021-07-13 Time 11:51 Rev Time 0.00
Received By shill Date 2021-07-13 Time 11:08 Sent To  
Notes
2021-07-13 11:53:20****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SCOPE OF WORK IS NOT CLEAR.
  
 THREE APPLICATIONS WERE SUBMITTED, STATING THE WORK IS
 IN THE ROW. 21070174, 21070015, 21070017. IT IS NOT
 CLEAR WHERE THE WORK IS TO BE DONE. THE WORK IS SHOWN
 IN THE RIGHT OF WAY (ONE PERMIT REQUIRED FOR ROW WORK),
 AT 303 BANYAN (BUT THAT APPLICATION GIVES THE PARCEL ID
 FOR 345 BANYAN, SO NOT CLEAR WHERE YOU ARE WORKING).
 THERE IS AN ISSUED BUILDING PERMIT FOR 345 BANYAN, BUT
 WORK IS SHOWN AT THAT LOCATION. IS THAT WORK SHOWN ON
 THE BUILDING PERMIT PLANS? IF NOT, THAT SHOULD BE A
 REVISION TO THE BUILDING PERMIT. WORK IS SHOWN AT 303
 BANYAN, AS WELL AS THE ROW. HAS A PERMIT BEEN APPLIED
 FOR AT THAT LOCATION?
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-05-20 Cont ID  
Sent By jleahy Date 2022-05-20 Time 08:00 Rev Time 0.00
Received By jleahy Date 2022-05-20 Time 07:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-05-16 Cont ID  
Sent By jleahy Date 2022-05-16 Time 13:46 Rev Time 0.00
Received By jleahy Date 2022-05-16 Time 13:46 Sent To  
Notes
2022-05-19 18:53:41ELECTRICAL SITE PLANS ARE JUST COPIES OF THE ORIGINALS,
 NEED ORIGINAL SIGNATURES FOR PERMITING. JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-04-20 Cont ID  
Sent By jgomez Date 2022-04-20 Time 10:09 Rev Time 0.00
Received By jgomez Date 2022-04-20 Time 08:55 Sent To  
Notes
2022-04-20 10:14:45SIGNATURE REVIEW:
  
 1- DRAWING E1.0.1 WAS NOT SIGNED AND SEALED BY THE
 ENGINEER OF RECORD. ALL DRAWINGS NEED TO BE SIGNED AND
 SEALED AS REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
  
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH DIGITAL
 SIGNATURE OR PROVIDE HARD COPY WITH ORIGINAL SEAL AND
 SIGNATURE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2022-02-14 Cont ID  
Sent By ckimmerl Date 2022-02-14 Time 16:11 Rev Time 0.00
Received By ckimmerl Date 2022-02-14 Time 16:11 Sent To  
Notes
2022-02-14 16:11:34PROVISO: STREET LIGHTING SHALL MATCH CITY STANDARD FOR
 DMP:
  
 (S55-007)-35W32LED4K-T-GL-LE3-UNV-DMG-SFOK-RCD7-TN3-COL
 TX
  
 VICTORIAN STYLE II POLE 13' TO 20' IN HEIGHT AND BLACK
 IN COLOR.