2021-07-08 08:35:05 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX. |
| |
| 1. SUBMITTED PRODUCT APPROVAL FL2533-R24 HAS BEEN |
| REVISED TO FL2533-R25. PLEASE PROVIDE A COMPLETE SET. |
| ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER |
| RULE 61G20-3. |
| 2. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL2533 R-24 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-5 TO |
| INCLUDE LIMITATIONS PAGE(S). |
| 3. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL2533-R24 SELECTED SYSTEM NO. W-64 DO NOT |
| MEET THE EXPOSURE CATEGORY C; ZONE 2 & 3 MINIMUM DESIGN |
| PRESSURE REQUIREMENT. PLEASE SELECT SYSTEM NO. THAT |
| MEETS OR EXCEEDS REQUIREMENTS OR PROVIDE SIGNED AND |
| SEALED ENGINEERED NAILING CALCULATIONS FOR ZONE 2 & 3. |
| SYSTEM MUST ALSO INCLUDE INSULATION IF USED. ALL |
| APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. THE |
| CORRECT EXPOSURE FOR THIS ADDRESS IS EXPOSURE C. |
| |