Plan Review Details - Permit 21061840
Plan Review Stops For Permit 21061840
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-06-30 Cont ID  
Sent By cpuell Date 2021-06-30 Time 15:08 Rev Time 0.00
Received By cpuell Date 2021-06-30 Time 15:08 Sent To  
Notes
2021-06-30 15:08:31TACO BELL HAS BEEN ASSIGNED THE ADDRESS OF 1237 PALM
 BEACH LAKES BLVD

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2021-08-24 Cont ID  
Sent By scwelter Date 2021-07-09 Time 14:36 Rev Time 0.00
Received By scwelter Date 2021-08-24 Time 16:07 Sent To  
Notes
2021-07-09 14:38:458.17.2021 PUBLIC ART REQUIREMENT COMPLETED - NO FURTHER
 ACTION REQUIRED
  
  
 PUBLIC ART REQUIREMENT:
 IF TOTAL CONSTRUCTION COSTS OF THIS DEVELOPMENT ARE
 OVER $500,000 IT WILL BE SUBJECT TO THE PUBLIC ART
 REQUIREMENT AS PER CITY ORDINANCE.
 SECTION 78-129: ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT.
 OPTION 1: INSTALL ARTWORK ON THE DEVELOPMENT SITE
 VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE
 TOTAL CONSTRUCTION COSTS; OR
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF
 ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT
 TO THE PUBLIC ART ACCOUNT.
 A COMPLETED PUBLIC ART ASSESSMENT APPLICATION IS
 REQUIRED AT TIME OF BUILDING PERMIT SUBMITTAL.
  
 PLEASE CONTACT SYBILLE WELTER AT [email protected] OR
 561.822.1521 TO OBTAIN AN APPLICATION AND REVIEW THE
 REQUIREMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-03-21 Cont ID  
Sent By rmcphers Date 2022-03-21 Time 09:56 Rev Time 0.00
Received By rmcphers Date 2022-03-21 Time 09:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-02-01 Cont ID  
Sent By rmcphers Date 2022-02-01 Time 16:26 Rev Time 0.00
Received By rmcphers Date 2022-02-01 Time 16:22 Sent To  
Notes
2022-02-01 16:26:33NEW RESTAURANT/TACO BELL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE ROOF CLADDING REQUIRED WIND DESIGN
 PRESSURES FOR THE ROOF FBC 1609
  
 FBC 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
 (5) .DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF
 (KN/M2).
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-11-23 Cont ID  
Sent By rmcphers Date 2021-11-23 Time 11:29 Rev Time 0.00
Received By rmcphers Date 2021-11-23 Time 11:02 Sent To  
Notes
2021-11-23 11:06:35NEW RESTAURANT/TACO BELL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) ROOFING PRODUCT APPROVAL - PLEASE CIRCLE THE ROOFING
 SYSTEM TO BE USED IN THE ROOFING PRODUCT APPROVAL -
 ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL MAY REQUIRE ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE
 THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL - SEE
 GENERAL LIMITATION NOTE NUMBER 7 ON THE PRODUCT
 APPROVAL.
  
 2) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING
 INFORMATION FBC WPB 107.2.5 DISTANCES FROM LOT LINES
  
 3) PLEASE SHOW CLADDING AND COMPONENT WIND DESIGN
 PRESSURES FOR WALLS AND ROOF FBC 1609
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-26 Cont ID  
Sent By rmcphers Date 2021-08-26 Time 09:24 Rev Time 0.00
Received By rmcphers Date 2021-08-25 Time 16:17 Sent To  
Notes
2021-08-26 09:24:20NEW RESTAURANT/TACO BELL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE ACCESSIBLE SEATING SPACES IN THE
 DINING ROOM PER FBC A226.1
 2) DRAWING ADA1 DETAIL NUMBER 11 SHOWS THE ACCESSIBLE
 PARKING SPACE DIMENSIONS INCORRECTLY PER FBC 502.2
 3) PLEASE PROVIDE A SOIL REPORT (GEOTECHNICAL REPORT).
 FBC 1803.1
 4) PLEASE PROVIDE COMPLETE PRODUCT APPROVALS FOR THE
 EXTERIOR WINDOWS, DOORS AND ROOFING SYSTEM AS LISTED ON
 THE DRAWINGS.
 5) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING
 INFORMATION 107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES).
 6) PLEASE PROVIDE A SURVEY.
 7) PLEASE SEPARATE THE STRUCTURAL DRAWINGS IN THE
 "DRAWINGS" FOLDER IN PROJECTDOX - THEY ARE IN A PACKAGE
 TOGETHER IN THE "DRAWINGS" FOLDER.
 8) BUILDING PERMIT APPLICATION IS CHECKED "OWNER
 BUILDER" CANNOT APPLY FOR THIS PERMIT AS AN OWNER
 BUILDER - FS - 489.103 (7)(A)
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-08-23 Cont ID  
Sent By jleahy Date 2021-08-23 Time 16:34 Rev Time 0.00
Received By jleahy Date 2021-08-20 Time 16:05 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2021-08-04 Cont ID  
Sent By rrossano Date 2021-08-04 Time   Rev Time  
Received By rrossano Date 2021-08-04 Time   Sent To  
Notes
2021-08-04 13:32:14REVEWED AS FORMAL ENG SUBMITTAL E21020005.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-01-18 Cont ID  
Sent By   Date 2022-01-18 Time   Rev Time 0.00
Received By bdolan Date 2022-01-18 Time 13:37 Sent To  
Notes
2022-01-18 13:38:18THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN
 DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH
 NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2021-11-17 Time   Rev Time 0.00
Received By jcclark Date 2021-11-17 Time 09:05 Sent To  
Notes
2021-11-15 14:58:36THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN
 DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH
 NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-07-23 Cont ID  
Sent By   Date 2021-07-23 Time   Rev Time 0.00
Received By bdolan Date 2021-07-20 Time 11:36 Sent To  
Notes
2021-07-23 14:28:00THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN
 DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH
 NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-11-30 Cont ID  
Sent By abelisle Date 2021-11-30 Time 16:22 Rev Time 0.00
Received By abelisle Date 2021-11-05 Time 17:03 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-08-19 Cont ID  
Sent By tklarge Date 2021-08-19 Time 14:32 Rev Time 0.00
Received By tklarge Date 2021-08-19 Time 14:32 Sent To  
Notes
2021-08-19 14:34:051) SUBMIT COPIES OF THE MANUFACTURER'S SPECIFICATION
 SHEETS / INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC- FUEL GAS CODE SEC. 402.2, AND 301.3.GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FBC-FUEL GAS CODE SEC.305.1.
 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-FUEL GAS CODE SEC.304.1. WHERE COMBUSTION AIR IS
 PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION
 SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED
 COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED
 VENTILATION AIR. FBC-FUEL GAS SEC.304.9.3 OR FBCR
 G2407.9.3.
 3) SUBMIT COPIES OF THE APPLICABLE SIZING TABLES USED
 TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE FBC-FUEL GAS
 SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) THRU
 402.4 (37).
 4) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED & ALL
 PIPE SIZES ON THE GAS RISER .WPB AMEND. TO FBC SEC.
 107.2.1.
 5) EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE. NFPA
 96-14. SECS. 10.4.1, 10.4.3, 10.4.4, 10.5.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-04-08 Cont ID  
Sent By vbroglia Date 2022-04-08 Time 13:19 Rev Time 0.00
Received By lcrespo Date 2022-04-04 Time 08:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-03-28 Cont ID  
Sent By vbroglia Date 2022-03-28 Time 16:58 Rev Time 0.00
Received By vbroglia Date 2022-03-03 Time 06:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-02 Cont ID  
Sent By ajones Date 2022-02-02 Time 16:49 Rev Time 0.00
Received By ajones Date 2022-01-13 Time 17:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-06 Cont ID  
Sent By vbroglia Date 2021-12-06 Time 13:35 Rev Time 0.00
Received By vbroglia Date 2021-11-04 Time 07:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-08 Cont ID  
Sent By lmarchan Date 2021-09-08 Time 08:50 Rev Time 0.00
Received By lmarchan Date 2021-07-19 Time 15:54 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-04-18 Cont ID  
Sent By lmarchan Date 2022-04-18 Time 11:16 Rev Time 0.00
Received By lmarchan Date 2022-04-13 Time 15:31 Sent To  
Notes
2022-04-18 11:16:43RECEIPT MU-2022-016955 - $0.00 DUE LEM
2022-04-13 15:31:574/13/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-08-26 Cont ID  
Sent By rmcphers Date 2021-08-26 Time 09:25 Rev Time 0.00
Received By rmcphers Date 2021-08-26 Time 09:25 Sent To  
Notes
2021-08-26 09:26:03PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-03-17 Cont ID  
Sent By medwards Date 2022-03-17 Time 13:21 Rev Time 0.00
Received By medwards Date 2022-03-17 Time 13:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-01-27 Cont ID  
Sent By medwards Date 2022-01-27 Time 11:23 Rev Time 0.00
Received By medwards Date 2022-01-27 Time 11:23 Sent To  
Notes
2022-01-27 11:23:581ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21061840
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE 2 KITCHEN CALCULATIONS ARE CONFUSING AS THEY
 HAVE DIFFERENT SQUARE FOOTAGE. IT APPEARS THAT THE TOP
 KITCHEN CALCULATION IS FOR THE OUTDOOR AIR AND THE
 LOWER CALCULATION IS FOR THE REQUIRED EXHAUST
 CALCULATION. PLEASE MAKE SURE THAT THE SQUARE FOOTAGE
 IS THE SAME FOR BOTH CALCULATIONS. IT ALSO APPEARS THAT
 THE OUT DOOR AIR TABLE IS TITLED 2020 FLMC VENTILATION
 CALCULATIONS BUT IT APPEARS THAT THE CALCULATIONS HAVE
 ASHRAE REFERENCE NUMBERS. PLEASE REMOVE ALL REFERENCE
 TO ASHRAE AS THE TITLE REFLECTS THE USE OF THE 2020
 FLORIDA MECHANICAL CODE. YOU CAN NOT MIX AND MATCH. FBC
 M403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-11-18 Cont ID  
Sent By medwards Date 2021-11-18 Time 06:31 Rev Time 0.00
Received By medwards Date 2021-11-18 Time 06:31 Sent To  
Notes
2021-11-18 06:36:25PLEASE SHOW THE REQUIRED OUTDOOR AIR FOR THE KITCHEN.
 2020 FBC M TABLE 403.3.1.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-20 Cont ID  
Sent By medwards Date 2021-08-20 Time 09:42 Rev Time 0.00
Received By medwards Date 2021-08-20 Time 09:42 Sent To  
Notes
2021-08-20 09:42:131ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21061840
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A NOTE ON THE PLANS STATING THAT THE HOOD
 SYSTEM WILL REQUIRE A SEPARATE PERMIT APPLICATION,
 DRAWINGS AND REVIEW. THE HOOD SYSTEM WILL NOT BE
 REVIEWED UNDER THIS PERMIT.
  
 2) PLEASE ADD A NOTE ON THE PLANS STATING THAT THE
 REFRIGERATION SYSTEMS WILL REQUIRE A SEPARATE PERMIT
 APPLICATION, DRAWINGS AND REVIEW. THE REFRIGERATION
 SYSTEMS WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 3) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC
 C402.1
  
 4) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC C403.2.1
  
 5) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS PER FBC
 403.3.1.1 AND TABLE 403.3.1.1
  
 6) PLEASE SHOW THE CLEARANCE TO THE ROOF EDGE OR THE
 GUARDS. FBC M 304.11
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-11-30 Cont ID  
Sent By abelisle Date 2021-11-30 Time 16:11 Rev Time 0.00
Received By abelisle Date 2021-11-05 Time 17:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-08-19 Cont ID  
Sent By tklarge Date 2021-08-19 Time 14:32 Rev Time 0.00
Received By tklarge Date 2021-08-16 Time 09:30 Sent To  
Notes
2021-08-18 10:03:511) SHTS. A1.0 & A8.1 - THE DOOR IN THE WOMEN'S AND
 MEN'S RESTROOMS APPEAR TO BE SWINGING INTO THE CLEAR
 FLOOR SPACE FOR THE LAVATORY.COMPLY WITH FBC-ACCESS.
 SEC.603.2.3 EXCEPTION #2. SHOW THE CLEAR FLOOR SPACE
 BEYOND THE ARC OF THE DOOR SWING COMPLYING WITH
 FBC-ACCESS. SEC.305.3.
 2) SHT.A3.0 - PROVIDE COMPLETE SCUPPER DIMENSIONS ON
 THE PLANS.COMPLY WITH FBC-PLUMBING SEC.1108.3.
 3) SHT. A8.1 - DETAIL "A" - ACCESSIBLE NOTE "A"
 REFERENCES THE ADA. THE STATE OF FLORIDA DOES NOT
 ENFORCE THE ADA. THE STATE OF FLORIDA ENFORCES THE
 FBC-ACCESSIBILITY WHICH IS A DEPT. OF JUSTICE COMPLIANT
 CODE. REMOVE ALL NOTES REFERRING TO ADA.
 4) SHT. A8.1 - DETAILS #1, 2, 5, 6 SHOW A VERTICAL GRAB
 BAR. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION PER FBC- ACESS. SEC.609.4.THERE IS NO
 EXCEPTION FOR VERTICAL GRAB BARS, EVEN IF THEY ARE NOT
 REQUIRED.REMOVE THE VERTICAL GRAB BARS.ALSO, SEE SHT.
 ADA 1.0.
 5) SHT. A8.1 - DETAIL # A - THERE IS A NOTE THAT REFERS
 TO ANSI A117.1. THIS STANDARD IS NOT APPLICABLE. THE
 STANDARD IS FBC-ACCESS.
 6) SHT. P1.0 - DETAIL #H - THE BACKFLOW DEVICES LISTED
 ARE FOR CARBONATED BEVERAGE MACHINES ONLY. BACKFLOW
 PREVENTERS FOR THE WATER FILTERS, REVERSE OSMOSIS
 SYSTEM AND NON-CARBONATED BEVERAGE MACHINES SHALL
 COMPLY WITH FBC-PLUMBING TABLE 608.1 AND ASSE 1024.
 7) THE MAXIMUM SIZE OF ANY SINGLE TANK FOR A GREASE
 INTERCEPTOR SHALL BE 1250 GALLONS PER CITY STANDARD
 DRAWING GS-7.
 8) A BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE MOP
 SINK DUE TO THE ECOLAB SYSTEM PER FBC-PLUMBING SEC.
 608.7 AND TABLE 608.1.
 9) TEMPERED OR COLD WATER IS REQUIRED AT THE LAVATORIES
 IN THE TOILET ROOMS PER FBC-PLUMBING SEC.419.5.
 10) CLEAR WATER WASTE SHALL NOT BE DISCHARGED TO THE
 GREASE WASTE SYSTEM PER FBC-PLUMBING SEC.1003.2.
 11) SUBMIT DETAILS OF THE GREASE INTERCEPTOR. THE
 INTERCEPTOR SHALL CCOMPLY WITH CITY STANDARD DRAWING
 GS-7 OR GS 7.1. PLEASE CONTACT THE CITY OF WEST PALM
 BEACH ENGINEERING DEPT. AT 561-494-1079 OR 561-835-7423
 FOR A COPY OF THE STANDARD DRAWING.
 12) THE SIZING OF THE GREASE INTERCEPTOR SHALL COMPLY
 WITH FBC-PLUMBING SEC.1003.3.5. THE INTERCEPTOR SHALL
 BE SIZED BASED ON PDI G101 OR RULE 64E-6, FLORIDA
 ADMINISTRATIVE CODE.
 13) SUBMIT A SITE PLAN OR CIVIL PLAN SHOWING THE
 LOCATION OF THE GREASE INTERCEPTOR ON THE PARCEL. WPB
 AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
 14) A HOT WATER RECIRCULATION LINE IS REQUIRED PER
 FBC-PLUMBBING SEC.607.2.THE RECIRCCULATION SSYTEM SHALL
 COMPLY WITH FBC-ENERGY SEC.C404.6, C404.6.1
 15) A FULL OPEN VALVE IS REQUIRED AT THE TOP OF THE
 DOWNFEED WATER PIPE FROM THE ROOF TO THE STRUCTURE PER
 FBC-PLUMBING SEC.606.1 (5).
 16) SHT. P3.0 - A SEPARATE PERMIT IS REQUIRED FOR THE
 BACKFLOW PREVENTION DEVICE AT THE WATER METER. THIS
 DEVICE SHALL BE A REDUCED PRESSURE ZONE VALVE BACKFLOW
 PREVENTER. PLACE A NOTE ON THE PLANS STATING A SEPARATE
 PERMIT IS REQUIRED AND THE DEVICE IS AN RPZ BACKFLOW.
 17) SHT P3.0 - THERE IS A NOTE AT THE BACKFLOW DEVICE
 STATING "FOR CONTINUATION, SEE CIVIL DRAWINGS." THERE
 ARE NO CIVIL DRAWINGS SHOWING THIS INFORMATION.
 CLARIFY.
 18) THE SIZING OF THE HEATED WATER SUPPLY PIPING SHALL
 BE IN ACCORDANCE WITH FBC- ENERGY SEC. C404.5.1 OR
 C404.5.2. SHOW COMPLIANCE ON THE WATER RISER.
 19) SINCE THE OCCUPANT LOAD OF THIS SPACE IS LESS THAN
 50 PERSONS IT SHALL BE CLASSIFIED AS A "B" OCCUPANCY IN
 ACORDANCE WITH FBC-BUILDING SEC.303.1.1 AND HENCE, 2
 RINKING FOUNTAINS ARE REQUIRED PER FBC-ACCESS.
 SEC.211.2 AND FBC-PLUMBING SEC.410..3.
 20) HAND SINKS SHALL NOT DISCHARGE TO THE GREASE WASTE
 SYSTEM PER FBC-PLUMBING SEC.1003.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 2 Status P Date 2021-11-30 Cont ID  
Sent By abelisle Date 2021-11-30 Time 16:22 Rev Time 0.00
Received By abelisle Date 2021-11-05 Time 17:03 Sent To  
Notes
***NONE***

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status F Date 2021-08-19 Cont ID  
Sent By tklarge Date 2021-08-19 Time 14:47 Rev Time 0.00
Received By tklarge Date 2021-08-19 Time 14:47 Sent To  
Notes
2021-08-19 14:36:191) SUBMIT DETAILS OF THE GREASE INTERCEPTOR. THE
 INTERCEPTOR SHALL COMPLY WITH CITY STANDARD DRAWING
 GS-7 OR GS 7.1. PLEASE CONTACT THE CITY OF WEST PALM
 BEACH ENGINEERING DEPT. AT 561-494-1079 OR 561-835-7423
 FOR A COPY OF THE STANDARD DRAWING.
 2) THE SIZING OF THE GREASE INTERCEPTOR SHALL COMPLY
 WITH FBC-PLUMBING SEC.1003.3.5. THE INTERCEPTOR SHALL
 BE SIZED BASED ON PDI G101 OR RULE 64E-6, FLORIDA
 ADMINISTRATIVE CODE.
 3) SUBMIT A SITE PLAN OR CIVIL PLAN SHOWING THE
 LOCATION OF THE GREASE INTERCEPTOR ON THE PARCEL. WPB
 AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
 4) THE MAXIMUM SIZE OF ANY SINGLE TANK FOR A GREASE
 INTERCEPTOR SHALL BE 1250 GALLONS PER CITY STANDARD
 DRAWING GS-7.
 5) CLEAR WATER WASTE SHALL NOT BE DISCHARGED TO THE
 GREASE WASTE SYSTEM PER FBC-PLUMBING SEC.1003.2.
 6) HAND SINKS SHALL NOT DISCHARGE TO THE GREASE WASTE
 SYSTEM PER FBC-PLUMBING SEC.1003.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2022-02-01 Cont ID  
Sent By rmcphers Date 2022-02-01 Time 16:27 Rev Time 0.00
Received By rmcphers Date 2022-02-01 Time 16:27 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-11-23 Cont ID  
Sent By rmcphers Date 2021-11-23 Time 11:30 Rev Time 0.00
Received By rmcphers Date 2021-11-23 Time 11:30 Sent To  
Notes
2021-11-23 11:30:34SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-08-26 Cont ID  
Sent By rmcphers Date 2021-08-26 Time 09:26 Rev Time 0.00
Received By rmcphers Date 2021-08-26 Time 09:26 Sent To  
Notes
2021-08-26 09:27:09SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-04-08 Cont ID  
Sent By lcrespo Date 2022-04-08 Time 13:19 Rev Time 0.00
Received By lcrespo Date 2022-04-08 Time 13:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-03-21 Cont ID  
Sent By rmcphers Date 2022-03-21 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2022-03-21 Time 10:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-02-01 Cont ID  
Sent By rmcphers Date 2022-02-01 Time 16:34 Rev Time 0.00
Received By rmcphers Date 2022-02-01 Time 16:34 Sent To  
Notes
2022-02-01 16:35:04SIGNATURE REVIEW
  
 DRAWINGS OR DOCUMENTS S3.0, S3.1, SURVEY, AND THE SOIL
 REPORT DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER
 -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-11-23 Cont ID  
Sent By rmcphers Date 2021-11-23 Time 11:54 Rev Time 0.00
Received By rmcphers Date 2021-11-23 Time 11:54 Sent To  
Notes
2021-11-23 11:59:40SIGNATURE REVIEW
  
 DRAWINGS OR DOCUMENTS S3.0, S3.1, C-10, SURVEY, AND THE
 SOIL REPORT DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE
 READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-08-26 Cont ID  
Sent By medwards Date 2021-08-20 Time 09:52 Rev Time 0.00
Received By medwards Date 2021-08-20 Time 09:52 Sent To  
Notes
2021-08-26 10:01:35S1.0 SHEET APPEARS TO HAVE A COPY OF A WET SEAL AND
 SIGNATURE. PLEASE PROVIDE A S1.0 DRAWING DIGITALLY
 SIGNED BY THE ENGINEER. FBC 471
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 5 Status P Date 2022-04-07 Cont ID  
Sent By vbroglia Date 2022-04-07 Time 13:00 Rev Time 0.00
Received By vbroglia Date 2022-04-07 Time 12:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2022-03-28 Cont ID  
Sent By vbroglia Date 2022-03-28 Time 16:54 Rev Time 0.00
Received By vbroglia Date 2022-03-28 Time 16:54 Sent To  
Notes
2022-03-28 16:55:163/28/2022 FAILED
  
 SITE PLAN DOES NOT MATCH THE MINOR AMENDMENT SUBMITTED
 TO THE PLANNING DIVISION ON MARCH 21, 2022
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2022-02-02 Cont ID  
Sent By avann Date 2022-02-02 Time 16:45 Rev Time 0.00
Received By ajones Date 2022-02-02 Time 16:45 Sent To  
Notes
2022-02-02 16:49:232/2/22- FAILED. SITE PLAN DOES NOT MATCH THE MINOR
 AMENDMENT SUBMITTED TO THE PLANNING DIVISION ON JANUARY
 27, 2022. FOR FUTURE SUBMITTIALS, PLEASE INDICATED ON
 THE SITE PLAN WHICH BUILDING THE PERMIT IS FOR.
  
 ANGELLA VANN
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2021-12-06 Cont ID  
Sent By vbroglia Date 2021-12-06 Time 13:34 Rev Time 0.00
Received By vbroglia Date 2021-12-06 Time 13:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-09-07 Cont ID  
Sent By rthermid Date 2021-09-07 Time   Rev Time  
Received By rthermid Date 2021-09-07 Time   Sent To I
Notes
***NONE***