Plan Review Details - Permit 21061694
Plan Review Stops For Permit 21061694
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2021-07-19 Cont ID  
Sent By rrossano Date 2021-07-19 Time   Rev Time  
Received By rrossano Date 2021-07-19 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2021-08-04 Time   Rev Time 0.00
Received By bdolan Date 2021-08-04 Time 13:58 Sent To  
Notes
2021-08-04 13:58:41PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
 THIS PLAN WAS REVIEWED AND APPROVED BY THE FIRE
 DEPARTMENT, WITH THE FOLLOWING COMMENTS:
  
  
 HYDROSTATIC TESTS. ALL PIPING AND ATTACHED
 APPURTENANCES SUBJECTED TO SYSTEM WORKING PRESSURE
 SHALL BE HYDROSTATICALLY TESTED AT 200 PSI (13.8 BAR)
 AND SHALL MAINTAIN THAT PRESSURE WITHOUT LOSS FOR 2
 HOURS.
  
 DO NOT COVER/BURY FIRE LINE PIPING OR PAINT BOLTS PRIOR
 TO INSPECTIONS.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-07-06 Cont ID  
Sent By   Date 2021-07-06 Time   Rev Time 0.00
Received By bdolan Date 2021-07-06 Time 12:16 Sent To  
Notes
2021-07-06 12:25:53PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
 THIS PLAN WAS REVIEWED AND APPROVED BY THE FIRE
 DEPARTMENT, WITH THE FOLLOWING COMMENTS:
  
  
 HYDROSTATIC TESTS. ALL PIPING AND ATTACHED
 APPURTENANCES SUBJECTED TO SYSTEM WORKING PRESSURE
 SHALL BE HYDROSTATICALLY TESTED AT 200 PSI (13.8 BAR)
 AND SHALL MAINTAIN THAT PRESSURE WITHOUT LOSS FOR 2
 HOURS.
  
 DO NOT COVER/BURY FIRE LINE PIPING OR PAINT BOLTS PRIOR
 TO INSPECTIONS.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-06 Cont ID  
Sent By cthroop Date 2021-08-06 Time 11:14 Rev Time 0.00
Received By cthroop Date 2021-07-20 Time 13:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-20 Cont ID  
Sent By lmarchan Date 2021-07-20 Time 09:46 Rev Time 0.00
Received By lmarchan Date 2021-06-30 Time 10:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-08-02 Cont ID  
Sent By medwards Date 2021-08-02 Time 09:01 Rev Time 0.00
Received By medwards Date 2021-08-02 Time 09:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-07-19 Cont ID  
Sent By medwards Date 2021-07-19 Time 10:08 Rev Time 0.00
Received By medwards Date 2021-07-19 Time 08:17 Sent To  
Notes
2021-07-19 10:08:401ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21061694
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET FP 1 OF 1: UNDERGROUND SYMBOLS LEGEND IS
 INDICATING AN EXISTING 4 INCH BACKFLOW PREVENTER BUT
 THE DRAWING SHOWS THE SAME SYMBOL AS A NEW 4 INCH DDCV.
 FBC 107.2.1
  
 2) IN THE MATERIALS & ABBREVIATIONS CHART IT SHOWS A
 6-INCH UNDERGROUND D.I.P. BUT THE DRAWING SHOWS IT TO
 BE A 4-INCH. PLEASE MAKE THE DRAWINGS CONSISTENT. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-08-02 Cont ID  
Sent By medwards Date 2021-08-02 Time 09:04 Rev Time 0.00
Received By medwards Date 2021-08-02 Time 09:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-07-19 Cont ID  
Sent By shill Date 2021-07-19 Time 08:56 Rev Time 0.00
Received By shill Date 2021-07-19 Time 08:56 Sent To  
Notes
2021-07-19 08:58:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC 107, BACKFLOW SPECS WERE SUBMITTED. BACKFLOW
 REQUIRES A SEPARATE PERMIT.
  
 EMAIL A PERMIT APPLICATION FOR A BACKFLOW TO
 [email protected] AND SUBMIT FOR PLAN REVIEW (PAY
 FEES, UPLOAD SPECS).
  
 WHEN YOU EMAIL [email protected], REQUEST THAT
 THEY PASS THIS REVIEW. IF ALL OTHER REVIEWS HAVE
 PASSED, THE PERMIT WILL THEN BE ISSUED.
  
  