Plan Review Details - Permit 21061643
Plan Review Stops For Permit 21061643
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-06-29 Cont ID  
Sent By cpuell Date 2021-06-29 Time 14:42 Rev Time 0.00
Received By cpuell Date 2021-06-29 Time 14:42 Sent To  
Notes
2021-06-29 14:42:43NORTH BUILDING HAS BEEN GIVEN AN ADDRESS OF 1111 9TH ST

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-06-29 Cont ID  
Sent By cpuell Date 2021-06-29 Time 10:12 Rev Time 0.00
Received By cpuell Date 2021-06-29 Time 10:12 Sent To  
Notes
2021-06-29 10:16:19PLEASE HAVE OWNER COORDINATE WITH [email protected] OR
 561-805-6659 FOR THE LIVABLE SPACE TO BE GIVEN AN
 ADDRESS. ALL ACCESSORY RESIDENTIAL/COMMERCIAL UNITS AND
 OR OTHER HABITABLE STRUCTURES WILL BE ISSUED A UNIQUE
 SECONDARY ADDRESS NUMBER PER CITY'S ADDRESSING POLICY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-09-10 Cont ID  
Sent By cthroop Date 2021-09-10 Time 11:02 Rev Time 0.00
Received By cthroop Date 2021-09-10 Time 09:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-27 Cont ID  
Sent By cthroop Date 2021-07-27 Time 14:22 Rev Time 0.00
Received By cthroop Date 2021-07-27 Time 13:50 Sent To  
Notes
2021-07-27 14:24:11PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: SEPERATE PERMIT FOR FRONT RESIDENCE 21061653
  
 NOTICE: VALUE ADJUSTED TO $112,000.00 BASED ON THE ICC
 BUILDING VALUATION DATA.
  
 1. PROVIDE A SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3 DRAINAGE.
  
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-08-27 Cont ID  
Sent By jleahy Date 2021-08-27 Time 16:52 Rev Time 0.00
Received By jleahy Date 2021-08-27 Time 16:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-08-09 Cont ID  
Sent By jleahy Date 2021-08-09 Time 11:16 Rev Time 0.00
Received By jleahy Date 2021-08-09 Time 11:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-07-13 Cont ID  
Sent By jleahy Date 2021-07-13 Time 14:32 Rev Time 0.00
Received By jleahy Date 2021-07-13 Time 14:25 Sent To  
Notes
2021-07-13 15:01:08ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PANEL IN FRONT BUILDING IS OVER THE KITCHEN COUNTER
 110.26 VIOLATION OG WORKING SPACE.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-09-10 Cont ID  
Sent By lmarchan Date 2021-09-10 Time 11:05 Rev Time 0.00
Received By lmarchan Date 2021-08-11 Time 14:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-10 Cont ID  
Sent By aoliver Date 2021-08-10 Time 11:01 Rev Time 0.00
Received By aoliver Date 2021-07-29 Time 17:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-29 Cont ID  
Sent By aoliver Date 2021-07-29 Time 17:03 Rev Time 0.00
Received By aoliver Date 2021-06-29 Time 08:56 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2021-09-30 Cont ID  
Sent By lmarchan Date 2021-09-30 Time 12:18 Rev Time 0.00
Received By lmarchan Date 2021-09-10 Time 11:05 Sent To  
Notes
2021-09-30 12:19:02RECEIPT MU-2021-047069 - $4304.62 PAID
2021-09-10 11:06:049/10/21 EMAILED IMPACT FOR REVIEW. LEM

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-08-21 Cont ID  
Sent By medwards Date 2021-08-21 Time 10:33 Rev Time 0.00
Received By medwards Date 2021-08-21 Time 10:33 Sent To  
Notes
2021-08-21 10:35:04APPROVED WITH PRIVISO
  
 DRYER DUCT- M1502.4.1 MATERIAL AND SIZE. EXHAUST DUCTS
 SHALL HAVE A
 SMOOTH INTERIOR FINISH AND BE CONSTRUCTED OF METAL
 HAVING A
 MINIMUM THICKNESS OF 0.0157 INCH (28 GAUGE).
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-08-06 Cont ID  
Sent By medwards Date 2021-08-06 Time 07:13 Rev Time 0.00
Received By medwards Date 2021-08-06 Time 07:12 Sent To  
Notes
2021-08-06 07:15:29APPROVED WITH PRIVISO
  
 DRYER DUCT- M1502.4.1 MATERIAL AND SIZE. EXHAUST DUCTS
 SHALL HAVE A
 SMOOTH INTERIOR FINISH AND BE CONSTRUCTED OF METAL
 HAVING A
 MINIMUM THICKNESS OF 0.0157 INCH (28 GAUGE).
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-07-08 Cont ID  
Sent By hmoser Date 2021-07-08 Time 15:09 Rev Time 0.00
Received By hmoser Date 2021-07-08 Time 14:45 Sent To  
Notes
2021-07-08 15:09:38PLAN DENIED
 PROVIDE ENERGY CALCULATIONS AND HEAT LOADS
 PER SECTION M1401.3 EQUIPMENT AND APPLIANCE SIZING.
 FLORIDA RESIDENTIAL CODE 2020.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-08-17 Cont ID  
Sent By lcrespo Date 2021-08-17 Time 12:59 Rev Time 0.00
Received By lcrespo Date 2021-08-17 Time 12:59 Sent To  
Notes
2021-08-17 13:05:2008/17/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-08-03 Cont ID  
Sent By lcrespo Date 2021-08-03 Time 18:47 Rev Time 0.00
Received By lcrespo Date 2021-08-03 Time 18:47 Sent To  
Notes
2021-08-03 18:47:3008/03/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-07-13 Cont ID  
Sent By lcrespo Date 2021-07-13 Time 14:53 Rev Time 0.00
Received By lcrespo Date 2021-07-13 Time 14:35 Sent To  
Notes
2021-07-13 14:42:2607/13/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2021-07-27 Cont ID  
Sent By cthroop Date 2021-07-27 Time 14:17 Rev Time 0.00
Received By cthroop Date 2021-07-27 Time 13:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-09-10 Cont ID  
Sent By cthroop Date 2021-09-10 Time 11:02 Rev Time 0.00
Received By cthroop Date 2021-09-10 Time 10:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-07-30 Cont ID  
Sent By medwards Date 2021-07-30 Time 15:19 Rev Time 0.00
Received By medwards Date 2021-07-30 Time 15:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-06-29 Cont ID  
Sent By medwards Date 2021-06-29 Time 13:15 Rev Time 0.00
Received By medwards Date 2021-06-29 Time 13:11 Sent To  
Notes
2021-06-29 13:15:52PLEASE PROVIDE ORIGINAL SIGNED AND SEALED MEP PAPER
 DRAWINGS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2021-07-29 Cont ID  
Sent By aaponte Date 2021-07-29 Time   Rev Time  
Received By rthermid Date 2021-07-29 Time   Sent To I
Notes
***NONE***