Plan Review Details - Permit 21061632
Plan Review Stops For Permit 21061632
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-08-12 Cont ID  
Sent By shill Date 2021-08-12 Time 16:25 Rev Time 0.00
Received By shill Date 2021-08-12 Time 16:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-21 Cont ID  
Sent By shill Date 2021-07-21 Time 09:29 Rev Time 0.00
Received By shill Date 2021-07-21 Time 09:29 Sent To  
Notes
2021-07-21 09:30:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. NEW TILE FLOORING IS PROPOSED. PROVIDE THE FOLLOWING
 TEST REPORTS FOR THE UNDERLAYMENT:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 2. FBC 107, THE PAPER PLAN SUBMITTED WAS BLURRY.
 PROVIDE LEGIBLE DOCUMENTS. IT IS BEST IF YOU UPLOAD A
 PDF PRODUCED FROM THE ENGINEER'S CAD DRAWING. YOU CAN
 SUBMIT PAPER, BUT THE QUALITY MUST BE LEGIBLE.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-08-09 Cont ID  
Sent By jleahy Date 2021-08-09 Time 15:47 Rev Time 0.00
Received By jleahy Date 2021-08-09 Time 15:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-07-06 Cont ID  
Sent By jleahy Date 2021-07-06 Time 12:14 Rev Time 0.00
Received By jleahy Date 2021-07-06 Time 12:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-04 Cont ID  
Sent By pleduc Date 2021-08-04 Time   Rev Time 0.00
Received By pleduc Date 2021-08-04 Time 15:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-07-22 Cont ID  
Sent By pleduc Date 2021-07-22 Time   Rev Time 0.00
Received By pleduc Date 2021-07-22 Time 13:04 Sent To  
Notes
2021-07-22 13:06:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF NEW TILE, HOWEVER, NO
 SPECIFICATIONS SHEETS FOR THE FLOOR UNDERLAYMENT NOR
 PROPSED TILE THAT INDICATE MEETING THE REQUIREMENTS PER
 NFPA
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
  
 30.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7.1 OR
 10.2.7.2, AS APPLICABLE
  
 10.2.1.1 CLASSIFICATION OF INTERIOR FINISH MATERIALS
 SHALL BE IN
 ACCORDANCE WITH TESTS MADE UNDER CONDITIONS SIMULATING
 ACTUAL
 INSTALLATIONS, PROVIDED THAT THE AUTHORITY HAVING
 JURISDICTION IS
 PERMITTED TO ESTABLISH THE CLASSIFICATION OF ANY
 MATERIAL FOR WHICH
 CLASSIFICATION BY A STANDARD TEST IS NOT AVAILABLE,
 UNLESS OTHERWISE
 PROVIDED IN 10.2.1.2 OR 10.2.1.4.
 10.2.1.2 THE PROVISIONS OF 10.2.1.1 SHALL NOT APPLY TO
 MATERIALS HAVING
 A TOTAL THICKNESS OF LESS THAN 1?28 IN. (0.9 MM) THAT
 ARE APPLIED DIRECTLY
 TO THE SURFACE OF WALLS AND CEILINGS WHERE BOTH OF THE
 FOLLOWING
 CONDITIONS ARE MET:
 (1) THE WALL OR CEILING SURFACE IS A NONCOMBUSTIBLE OR
 LIMITED COMBUSTIBLE
 MATERIAL.
 (2) THE MATERIALS APPLIED MEET THE REQUIREMENTS OF
 CLASS A INTERIOR
 WALL OR CEILING FINISH WHEN TESTED IN ACCORDANCE WITH
 10.2.3,
 USING FIBER CEMENT BOARD AS THE SUBSTRATE MATERIAL.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS.
  
  
 2) THERE IS AN INDICATION OF NON-BEARING WALL BUT NONE
 FOR THE RATED TENANT SEPARATION WALL BY THE PROPOSED
 SHOWER.
  
 THE PROPOSED WORK APPEARS TO INVOLVE THE EXISTING WALL
 BOARD AND THUS THE REQUIRED FIRE RATING.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND ENSURE
 COMPLIANCE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-09-07 Time   Rev Time 0.00
Received By aoliver Date 2021-09-03 Time 16:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-08-27 Cont ID  
Sent By rmcdouga Date 2021-08-27 Time 16:47 Rev Time 0.00
Received By rmcdouga Date 2021-08-27 Time 11:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-12 Cont ID  
Sent By shill Date 2021-08-12 Time 16:34 Rev Time 0.00
Received By shill Date 2021-07-30 Time 08:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-22 Cont ID  
Sent By lmarchan Date 2021-07-22 Time 13:34 Rev Time 0.00
Received By lmarchan Date 2021-06-30 Time 15:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2021-07-06 Cont ID  
Sent By medwards Date 2021-07-06 Time 10:05 Rev Time 0.00
Received By medwards Date 2021-07-06 Time 10:05 Sent To  
Notes
2021-07-06 10:05:52NO MECHANICAL WORK SHOWN ON DRAWINGS.ME

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-08-03 Cont ID  
Sent By lcrespo Date 2021-08-03 Time 19:46 Rev Time 0.00
Received By lcrespo Date 2021-08-03 Time 19:46 Sent To  
Notes
2021-08-03 19:49:4408/03/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-07-08 Cont ID  
Sent By lcrespo Date 2021-07-08 Time 13:09 Rev Time 0.00
Received By lcrespo Date 2021-07-08 Time 13:09 Sent To  
Notes
2021-07-08 13:09:5707/08/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-09-07 Cont ID  
Sent By ccole Date 2021-09-07 Time 11:37 Rev Time 0.00
Received By ccole Date 2021-09-07 Time 11:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-08-27 Cont ID  
Sent By rmcdouga Date 2021-08-27 Time 16:44 Rev Time 0.00
Received By rmcdouga Date 2021-08-27 Time 16:44 Sent To  
Notes
2021-08-27 16:47:21THE ENGINEER'S SIGNATURE ON THE BEAM SECTION DRAWING IS
 A PHOTO COPY. THE ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE IS REQUIRED. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR
 ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE
 OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF
 DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN
 APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 487 & 61G1 OR FS 471 & 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-08-12 Cont ID  
Sent By shill Date 2021-08-12 Time 16:27 Rev Time 0.00
Received By shill Date 2021-08-12 Time 16:27 Sent To  
Notes
2021-08-12 16:34:52SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. THE DOCUMENT UPLOADED
 APPEARS TO HAVE A DIGITAL SIGNATURE BUT WHEN OPENED IN
 ADOBE THE BLUE BAR AT THE TOP DOES NOT APPEAR, THERE IS
 NO CERTIFICATE FOR THE DIGITAL SIGNATURE.
  
 IF YOU SPLIT A TWO PAGE PDF THAT WAS DIGITALLY SIGNED
 INTO TWO DIFFERENT PDFS, PLEASE UPLOAD THE ORIGINAL
 DIGITALLY SIGNED PDF INTO THE SIGNATURE FOLDER. THE
 DIGITAL SIGNATURE MAY HAVE BEEN REMOVED IF THE DOCUMENT
 WAS SPLIT.
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER AND COMPLETE THE UPLOAD TASK IN
 PROJECTDOX, OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND
 SEALED PAPER ORIGINAL WITH A WET SIGNATURE TO THE
 BUILDING DIVISION. SIGNATURE DOCUMENTS ARE TYPICALLY
 REVIEWED WITHIN TWO BUSINESS DAYS AFTER SUBMITTAL;
 DIGITALLY SIGNED DOCUMENTS ARE PREFERRED.
  
 IF THE ENGINEER NEEDS ASSISTANCE WITH THE DIGITAL
 SIGNATURE, HAVE HIM CALL ME.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-07-01 Cont ID  
Sent By medwards Date 2021-07-01 Time 15:12 Rev Time 0.00
Received By medwards Date 2021-07-01 Time 15:11 Sent To  
Notes
2021-07-01 15:13:14ENGINEER NEEDS TO SIGN HIS PAPER DRAWINGS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  