Plan Review Details - Permit 21061620
Plan Review Stops For Permit 21061620
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2021-07-13 Cont ID  
Sent By cthroop Date 2021-07-13 Time 11:44 Rev Time 0.00
Received By cthroop Date 2021-07-13 Time 11:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-07-08 Cont ID  
Sent By cthroop Date 2021-07-08 Time 10:11 Rev Time 0.00
Received By cthroop Date 2021-07-08 Time 10:11 Sent To  
Notes
2021-07-08 10:20:10PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: PLAN PAGE SP-1.01 AND ICC-ES REPORT
  
 1. SUBMIT REVISED PLAN SHEET SP-1.01 AND THE ICC-ES
 REPORT FOR THE SMART VENTS AS A REVISION TO MASTER
 PERMIT 19050988. SEND PLAN REVIEW REQUEST FORM AND
 DOC'S TO: [email protected]
  
 NOTICE: PLEASE RE-EVALUATE THE SQUARE FOOTAGE OF THE
 GARAGE. FEMA REQUIRES THE MEASUREMENTS BE TAKEN ON THE
 OUTSIDE OF THE GARAGE. PLAN PAGE S-100 SHOWS GARAGE IS
 28.25FT X 23.75FT FOR A TOTAL OF 671SF.
 NOTICE: SUBMITTAL 21061620, FOR THE FINISHED
 CONSTRUCTION EC REVIEW SHOULD INCLUDE ONLY THE EC AND A
 FINAL BOUNDRY LINE SURVEY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2021-06-28 Cont ID  
Sent By cthroop Date 2021-06-28 Time 14:39 Rev Time 0.00
Received By cthroop Date 2021-06-28 Time 13:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-07-15 Cont ID  
Sent By cthroop Date 2021-07-15 Time 08:33 Rev Time 0.00
Received By cthroop Date 2021-07-14 Time 11:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-07-13 Cont ID  
Sent By cthroop Date 2021-07-13 Time 13:22 Rev Time 0.00
Received By cthroop Date 2021-07-12 Time 10:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-08 Cont ID  
Sent By cthroop Date 2021-07-08 Time 11:06 Rev Time 0.00
Received By cthroop Date 2021-07-06 Time 16:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-28 Cont ID  
Sent By cthroop Date 2021-06-28 Time 14:39 Rev Time 0.00
Received By cthroop Date 2021-06-28 Time 09:44 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status P Date 2021-07-15 Cont ID  
Sent By cthroop Date 2021-07-15 Time 08:33 Rev Time 0.00
Received By cthroop Date 2021-07-15 Time 07:57 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2021-07-13 Cont ID  
Sent By cthroop Date 2021-07-13 Time 13:19 Rev Time 0.00
Received By cthroop Date 2021-07-13 Time 11:26 Sent To  
Notes
2021-07-13 13:22:26PLAN REVIEW / NFIP
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16
  
 3RD REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SECTION A4
 ENTER BUILDING USE.
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2021-07-08 Cont ID  
Sent By cthroop Date 2021-07-08 Time 10:20 Rev Time 0.00
Received By cthroop Date 2021-07-07 Time 07:05 Sent To  
Notes
2021-07-08 10:23:04PLAN REVIEW / NFIP
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). IT IS LOCATED IN ZONE AE WITH BASE FLOOD
 ELEVATIONS OF 6.0 FEET AND 7.0 FEET NAVD. DESIGN FLOOD
 ELEVATION SHALL BE NOT LESS THAN 9.0 FEET NAVD.
  
 1. SECTION A6 CORRECTED
  
 2. SECTION A9A)
 GARAGE SF IS INDICATED AS 572 SF. PLAN PAGE SP-1.01
 STATES GARAGE SF IS 597 SF. PLEASE CORRECT.
  
 NEW COMMENT:
 REVISED PLAN PAGE SP-1.01 SUBMITTED FOR REVIEW. SUBMIT
 CHANGES TO APPROVED PLANS AS A REVISION TO MASTER
 PERMIT 19050988.
 NOTICE: FEMA REQUIRES THE SQUARE FOOTAGE OF THE GARAGE
 TO BE MEASURED ON THE OUTSIDE OF THE GARAGE. PLEASE
 RE-EVALUATE THE SQUARE FOOTAGE. SEE COMMENTS UNDER
 BLDG. REVIEW.
  
 3. SECTION A9B) CORRECTED
  
 4. SECTION B8
 FLOOD ZONE SHOULD ONLY BE AE. (REMOVE THE REFERENCE TO
 ZONE X. ZONE X IS NOT A SPECIAL FLOOD HAZARD AREA)
  
 5. SECTION B9
 BASE FLOOD ELEVATIONS SHOULD BE 6.0 FEET AND 7.0 FEET
 NAVD. (REMOVE THE REFERENCE TO 0.2% ANNUAL CHANCE OF
 FLOOD. THIS PERTAINS TO ZONE X-500 WHICH IS NOT A
 SPECIAL FLOOD HAZARD AREA)
  
 6. SECTION D
 INCLUDE THE FUTURE GENERATOR SHOWN ON PLAN PAGE SP-1.01
 IN THE COMMENTS SECTION UNDER EQUIPMENT SERVICING THE
 BUILDING.
 (COMMENT FOR THE GENERATOR STATES "GENERATOR SLAB IS AT
 ELEVATION 9.6 NAVD AND BOTTOM OF THE GENERATOR IS AT
 ELEVATION 10.3 NAVD". PLEASE CLARIFY.
  
 NEW COMMENT:
  
 7. PROVIDE A FINAL BOUNDRY LINE SURVEY PER FEMA EC
 INSTRUCTIONS ITEM C2.
  
 NOTICE: SUBMITTAL FOR FINISHED CONSTRUCTION EC SHOULD
 INCLUDE ONLY THE EC AND A FINAL BOUNDRY LINE SURVEY.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2021-06-28 Cont ID  
Sent By cthroop Date 2021-06-28 Time 14:41 Rev Time 0.00
Received By cthroop Date 2021-06-28 Time 13:56 Sent To  
Notes
2021-06-28 14:55:20PLAN REVIEW / NFIP
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE:
  
 PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). IT IS LOCATED IN ZONE AE WITH BASE FLOOD
 ELEVATIONS OF 6.0 FEET AND 7.0 FEET NAVD. DESIGN FLOOD
 ELEVATION SHALL BE NOT LESS THAN 9.0 FEET NAVD.
  
 1. SECTION A6
 PHOTOGRAPHS MUST SHOW THE FOUNDATION WITH
 REPRESENTATIVE EXAMPLES OF THE FLOOD OPENINGS OR VENTS.
  
 2. SECTION A9A)
 GARAGE SF IS INDICATED AS 572 SF. PLAN PAGE SP-1.01
 STATES GARAGE SF IS 597 SF. PLEASE CORRECT.
  
 3. SECTION A9B)
 NUMBER OF VENTS IS INDICATED AS 2. PLAN PAGE A1.01
 STATES THERE SHALL BE 3 VENTS INSTALLED.
 REF. ICC-ES REPORT FOR THE FOLLOWING:
 SMART VENT MODEL 1540-520 (8 X 16) ONLY COVERS 200 SF
 EACH. 3 VENTS ARE REQUIRED PER APPROVED PLAN.
  
 4. SECTION B8
 FLOOD ZONE SHOULD ONLY BE AE.
  
 5. SECTION B9
 BASE FLOOD ELEVATIONS SHOULD BE 6.0 FEET AND 7.0 FEET
 NAVD
  
 6. SECTION D
 INCLUDE THE FUTURE GENERATOR SHOWN ON PLAN PAGE SP-1.01
 IN THE COMMENTS SECTION UNDER EQUIPMENT SERVICING THE
 BUILDING.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-07-15 Cont ID  
Sent By cthroop Date 2021-07-15 Time 08:33 Rev Time 0.00
Received By cthroop Date 2021-07-15 Time 07:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-07-13 Cont ID  
Sent By cthroop Date 2021-07-13 Time 13:32 Rev Time 0.00
Received By cthroop Date 2021-07-13 Time 13:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-07-08 Cont ID  
Sent By cthroop Date 2021-07-08 Time 10:11 Rev Time 0.00
Received By cthroop Date 2021-07-07 Time 07:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-06-28 Cont ID  
Sent By cthroop Date 2021-06-28 Time 14:40 Rev Time 0.00
Received By cthroop Date 2021-06-28 Time 13:56 Sent To  
Notes
***NONE***