Plan Review Details - Permit 21061495
Plan Review Stops For Permit 21061495
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-11-06 Cont ID  
Sent By fgiaquin Date 2021-11-06 Time 21:47 Rev Time 0.00
Received By fgiaquin Date 2021-11-06 Time 20:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-19 Cont ID  
Sent By hmoser Date 2022-04-19 Time 09:34 Rev Time 0.00
Received By hmoser Date 2022-04-10 Time 08:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-05 Cont ID  
Sent By medwards Date 2022-04-05 Time 16:51 Rev Time 0.00
Received By medwards Date 2022-03-30 Time 07:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-06 Cont ID  
Sent By fgiaquin Date 2021-11-06 Time 21:47 Rev Time 0.00
Received By fgiaquin Date 2021-10-14 Time 09:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-04-19 Cont ID  
Sent By hmoser Date 2022-04-19 Time 09:34 Rev Time 0.00
Received By hmoser Date 2022-04-19 Time 09:15 Sent To  
Notes
2022-04-19 09:34:14PLAN DENIED
 1) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 ( SIGNATURE REQUIRED ON PLAN ) FBC 2020
 2) IS THERE A GARAGE DOOR ON THE FRONT OF THE GARAGE?
 IF SO PROVIDE
 THE DOOR SIZE AND R - VALUE.
 3) PLEASE PROVIDE A LOT SURVEY WITH THE PLAN.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-04-05 Cont ID  
Sent By medwards Date 2022-04-05 Time 16:46 Rev Time 0.00
Received By medwards Date 2022-04-05 Time 16:46 Sent To  
Notes
2022-04-05 16:50:47NEITHER THE ENERGY CALCULATIONS OR THE DRAWINGS SHOW
 THE GARAGE DOOR FOR THIS GARAGE. IS THERE A GARAGE DOOR
 IN THIS GARAGE? PLEASE PROVIDE THE ENERGY CALCULATIONS
 SHOWING THE VEHICLE GARAGE DOOR SIZE AND R-VALUE IN THE
 CALCULATIONS. PLEASE CLEAN UP THE MECHANICAL DRAWING
 AND SHOW THE LOT LINE AND THE PLACEMEN OF THE
 CONDENSING UNIT. PLEASE SHOW THE ANCHORAGE DETAILS OF
 THE CONDENSING UNIT. THE DESIGNER OF THE MECHANICAL
 DRAWING MUST INCLUDE THEIR PRINTED NAME AND THEIR
 SIGNATURE ON THE DRAWING.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-18 Cont ID  
Sent By medwards Date 2021-10-18 Time 07:14 Rev Time 0.00
Received By medwards Date 2021-10-18 Time 07:14 Sent To  
Notes
2021-10-18 07:18:09THE MINI-SPLIT IN THE GARAGE WILL NEED ENERGY
 CALCULATIONS AND MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. THE MINI SPLIT IS FOR CONDITIONING THE
 SPACE NOT JUST FOR DE-HUMITIFICATION. FBC EC
 101.5.1.1.2, FBC CE R1401.3.
 PROVIDE A DRAWING SHOWING THE LOCATION OF THE
 MINI-SPLIT AND THE CONDENSING UNIT.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-10-18 Cont ID  
Sent By medwards Date 2021-10-18 Time 07:18 Rev Time 0.00
Received By medwards Date 2021-10-18 Time 07:18 Sent To  
Notes
***NONE***