Plan Review Details - Permit 21061357
Plan Review Stops For Permit 21061357
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2021-08-03 Cont ID  
Sent By cpuell Date 2021-08-03 Time 16:18 Rev Time 0.00
Received By cpuell Date 2021-08-03 Time 16:18 Sent To  
Notes
2021-08-03 16:19:52SPOKE WITH OWNER STATED THAT WORK WAS TO BE DONE ON THE
 REAR BUILDING ONLY WHICH HAD AN ADDRESS OF 422 1/2
 BARNETT ST, WHICH HAS BEEN CHANGED TO 424 BARNETT ST.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-07-28 Cont ID  
Sent By cpuell Date 2021-07-28 Time 08:33 Rev Time 0.00
Received By cpuell Date 2021-07-28 Time 08:32 Sent To  
Notes
2021-07-28 08:33:24THE REAR BUILDING HAS A HALF ADDRESS WHICH WILL NEED TO
 BE READDRESSED, PLEASE HAVE OWNER COORDINATE WITH
 [email protected] OR CALL 561-805-6659 FOR THE REAR
 BUILDING TO BE GIVEN A NEW ADDRESS.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-07-27 Cont ID  
Sent By cpuell Date 2021-07-27 Time 14:02 Rev Time 0.00
Received By cpuell Date 2021-07-27 Time 14:02 Sent To  
Notes
2021-07-27 14:03:19THE REAR BUILDING HAS A HALF ADDRESS WHICH WILL NEED TO
 BE READDRESSED, PLEASE HAVE OWNER COORDINATE WITH
 [email protected] OR CALL 561-805-6659 FOR THE REAR
 BUILDING TO BE GIVEN A NEW ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2021-08-06 Cont ID  
Sent By jbrooks Date 2021-08-06 Time 08:48 Rev Time 0.00
Received By jbrooks Date 2021-08-06 Time 07:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2021-07-29 Cont ID  
Sent By jbrooks Date 2021-07-29 Time 13:45 Rev Time 0.00
Received By jbrooks Date 2021-07-29 Time 07:58 Sent To  
Notes
2021-07-29 13:46:00JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL2533-R26 HAS NOT BEEN APPROVED YET. PLEASE
 PROVIDE A COMPLETE SET OF APPROVED 2020 CODE VERSION
 PRODUCT APPROVALS/NOA?S FOR THE PROPOSED FLAT/LOW ROOF
 SYSTEM USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. (OPTION
 FL2533-R25 SYSTEM W-42).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-07-23 Cont ID  
Sent By ccole Date 2021-07-23 Time 15:50 Rev Time 0.00
Received By ccole Date 2021-07-23 Time 14:58 Sent To  
Notes
2021-07-23 15:51:264TH REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1)THE NEW SELECTED W-93 SYSTEM IS FOR NON-INSULATED
 ROOFS WITH MECHANICALLY ATTACHED BASE SHEET. THE
 PREVIOUS W-4 SYSTEM WAS FOR A MIN 1.5 INCH BASE
 INSULATION SYSTEM. PLEASE CLARIFY IF THE ROOF IS
 INSULATED OR NON-INSULATED. PLEASE NOTE THAT YOU HAVE
 PREVIOUSLY SUBMITTED FL. PRODUCT APPROVAL 491-R8 FOR
 CERTAINTEED INSULATION BOARD. I HAVE LOOKED THROUGH THE
 FL. PRODUCT APPROVAL 2533-R25 AND THERE ARE INSULATED
 SYSTEMS THAT EXCEED THE REQUIRED PRESSURE FOR CAT. C-
 ZONE 3. THE PREVIOUS REVIEW COMMENTS ARE LISTED BELOW.
 PLEASE COMPLY.
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL2533-R25 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-5 TO
 INCLUDE LIMITATIONS PAGE(S).
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL2533-R25 SELECTED SYSTEM NO. W-4 DO NOT MEET
 THE EXPOSURE CATEGORY C; ZONE 3 MINIMUM DESIGN PRESSURE
 REQUIREMENT OF -108.17. PLEASE SELECT SYSTEM NO. THAT
 MEETS OR EXCEEDS REQUIREMENTS OR PROVIDE SIGNED AND
 SEALED ENGINEERED NAILING CALCULATION FOR ZONE 3. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
  
 JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS ST.
 WEST PALM BEACH, FL. 33401
 561-805-6719
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-07-16 Cont ID  
Sent By jbrooks Date 2021-07-16 Time 13:45 Rev Time 0.00
Received By jbrooks Date 2021-07-16 Time 07:55 Sent To  
Notes
2021-07-16 13:45:43JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL2533-R25 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-5 TO
 INCLUDE LIMITATIONS PAGE(S).
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL2533-R25 SELECTED SYSTEM NO. W-4 DO NOT MEET
 THE EXPOSURE CATEGORY C; ZONE 3 MINIMUM DESIGN PRESSURE
 REQUIREMENT OF -108.17. PLEASE SELECT SYSTEM NO. THAT
 MEETS OR EXCEEDS REQUIREMENTS OR PROVIDE SIGNED AND
 SEALED ENGINEERED NAILING CALCULATION FOR ZONE 3. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-07-01 Cont ID  
Sent By jbrooks Date 2021-07-01 Time 13:21 Rev Time 0.00
Received By jbrooks Date 2021-07-01 Time 07:45 Sent To  
Notes
2021-07-01 13:22:01JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. SUBMITTED PRODUCT APPROVAL FL2533-R24 HAS BEEN
 REVISED TO FL2533-R25. PLEASE PROVIDE A COMPLETE SET.
 INCLUDE EVALUATIONS REPORT PAGES 1-5 THAT INCLUDES
 LIMITATIONS PAGE(S). ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING. AS PER RULE 61G20-3. SECOND
 REQUEST.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL2533-R25 SELECTED SYSTEM NO. W-74 DO NOT
 MEET THE EXPOSURE CATEGORY C; ZONE 2 & 3 MINIMUM DESIGN
 PRESSURE REQUIREMENT. PLEASE SELECT SYSTEM NO. THAT
 MEETS OR EXCEEDS REQUIREMENTS OR PROVIDE SIGNED AND
 SEALED ENGINEERED NAILING CALCULATIONS FOR ZONE 2 & 3.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. THE
 CORRECT EXPOSURE FOR THIS ADDRESS IS EXPOSURE C.
 3. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND SHOW THE AREAS TO RECEIVE NEW
 ROOFING CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF
 SLOPE(S), ROOF HEIGHT(S). SECOND REQUEST.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-28 Cont ID  
Sent By jbrooks Date 2021-06-28 Time 10:10 Rev Time 0.00
Received By jbrooks Date 2021-06-28 Time 07:45 Sent To  
Notes
2021-06-28 10:10:59JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. SUBMITTED PRODUCT APPROVAL FL2533-R24 HAS BEEN
 REVISED TO FL2533-R25. PLEASE PROVIDE A COMPLETE SET.
 INCLUDE EVALUATIONS REPORT PAGES 1-5 THAT INCLUDES
 LIMITATIONS PAGE(S). ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING. AS PER RULE 61G20-3.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL2533-R25 COVERS MULTIPLE ROOF SYSTEMS FOR
 WOOD DECKS; SYSTEM NO. W-1 THRU W-107. PLEASE SELECT
 SYSTEM NO. THAT MEETS OR EXCEEDS EXPOSURE CATEGORY C
 ZONE 3 DESIGN PRESSURE REQUIREMENTS OR PROVIDE SIGNED
 AND SEALED ENGINEERED NAILING CALCULATION FOR ZONE 3.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 3. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND SHOW THE AREAS TO RECEIVE NEW
 ROOFING CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF
 SLOPE(S), ROOF HEIGHT(S).
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-08-06 Cont ID  
Sent By jbrooks Date 2021-08-06 Time 08:49 Rev Time 0.00
Received By jbrooks Date 2021-08-04 Time 08:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-07-29 Cont ID  
Sent By jbrooks Date 2021-07-29 Time 13:46 Rev Time 0.00
Received By jbrooks Date 2021-07-28 Time 07:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-07-23 Time   Rev Time 0.00
Received By lmarchan Date 2021-07-20 Time 09:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-07-16 Cont ID  
Sent By jbrooks Date 2021-07-16 Time 13:45 Rev Time 0.00
Received By jbrooks Date 2021-07-15 Time 10:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-01 Cont ID  
Sent By jbrooks Date 2021-07-01 Time 13:22 Rev Time 0.00
Received By jbrooks Date 2021-06-30 Time 16:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-28 Cont ID  
Sent By jbrooks Date 2021-06-28 Time 10:11 Rev Time 0.00
Received By jbrooks Date 2021-06-25 Time 06:16 Sent To  
Notes
***NONE***