Plan Review Details - Permit 21061294
Plan Review Stops For Permit 21061294
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-08-03 Cont ID  
Sent By jleahy Date 2022-08-03 Time 16:51 Rev Time 0.00
Received By jleahy Date 2022-08-03 Time 16:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-07-07 Cont ID  
Sent By jleahy Date 2021-07-07 Time 16:34 Rev Time 0.00
Received By jleahy Date 2021-07-07 Time 16:30 Sent To  
Notes
2021-07-07 16:34:35ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE IS LOW FOR SIZE INSTALLATION PLEASE SUBMIT A
 CONTRACT FOR THE GENERATOR, TRANSFER SWITCH, WIRE, AND
 LABOR.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-07-22 Cont ID  
Sent By cwalker Date 2022-07-22 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-06-28 Cont ID  
Sent By pleduc Date 2021-06-28 Time   Rev Time 0.00
Received By pleduc Date 2021-06-28 Time 13:56 Sent To  
Notes
2021-06-28 14:21:56THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS A FLOOR PLAN LAYOUT INDICATING A DIESEL
 FUELED GENERATOR; HOWEVER, THERE IS NO INDICATION F
 REFULEING/PIPING.
  
 PLEASE REVIEW AND PROVIDE DETAILES ON HOW THE GENERATOR
 WILL BE REFUELED. IF APPLICABLE PROVIDE PIPING PLAN
 DETAILS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-03 Cont ID  
Sent By jleahy Date 2022-08-03 Time 16:51 Rev Time 0.00
Received By jleahy Date 2022-07-21 Time 15:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-14 Cont ID  
Sent By medwards Date 2022-06-14 Time 14:46 Rev Time 0.00
Received By medwards Date 2021-06-25 Time 06:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-08-03 Cont ID  
Sent By jleahy Date 2022-08-03 Time 16:51 Rev Time 0.00
Received By jleahy Date 2022-08-03 Time 16:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-06-25 Cont ID  
Sent By medwards Date 2021-06-25 Time 11:53 Rev Time 0.00
Received By medwards Date 2021-06-25 Time 11:50 Sent To  
Notes
2021-06-25 11:55:05ORIGINAL SUBMITTED PAPER DRAWINGSS DO NOT HAVE THE
 ENGINEERS SIGNATURE. PLEASE PROVIDE THE ORIGINAL SIGNED
 AND SEALED PAPER DRAWINGS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2022-06-14 Cont ID  
Sent By jroach Date 2022-06-14 Time 11:13 Rev Time 0.00
Received By jroach Date 2022-06-14 Time 11:13 Sent To  
Notes
2022-06-14 11:14:28NOTE THAT THE GENERATOR HAS TO BE SCREENED IN
 ACCORDANCE WITH THE BANYAN CAY DESIGN GUIDELIENS AND
 APPROVED SITE/LANDSCAPE PLANS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved