Plan Review Details - Permit 21061276
Plan Review Stops For Permit 21061276
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-08-24 Cont ID  
Sent By rmcphers Date 2021-08-24 Time 08:04 Rev Time 0.00
Received By rmcphers Date 2021-08-24 Time 08:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-28 Cont ID  
Sent By rmcphers Date 2021-07-28 Time 12:36 Rev Time 0.00
Received By rmcphers Date 2021-07-28 Time 12:36 Sent To  
Notes
2021-07-28 12:38:17TEMP. CONSTRUCTION TRAILER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) PLEASE PROVIDE A SITE PLAN SHOWING THE TRAILER
 LOCATION AND THE DISTANCES FROM THE PROPERTY LINES,
 BUILDINGS ETC. FBC WPB 107

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-10-06 Cont ID  
Sent By jleahy Date 2021-10-06 Time 09:57 Rev Time 0.00
Received By jleahy Date 2021-10-06 Time 09:52 Sent To  
Notes
2021-10-06 09:58:16CONTRACTOR TO PULL SEPARATE PERMIT FOR SERVICE JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-07-23 Cont ID  
Sent By jleahy Date 2021-07-23 Time 10:32 Rev Time 0.00
Received By jleahy Date 2021-07-23 Time 10:32 Sent To  
Notes
2021-07-23 10:33:32FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE SUBMIT A RISER DIAGRAM SHOWING THE SERVICE AND
 FEEDER SIZE. 215.5

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-13 Cont ID  
Sent By pleduc Date 2021-08-13 Time   Rev Time 0.00
Received By pleduc Date 2021-08-13 Time 10:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-07-12 Cont ID  
Sent By pleduc Date 2021-07-12 Time   Rev Time 0.00
Received By pleduc Date 2021-07-12 Time 14:10 Sent To  
Notes
2021-07-12 14:10:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO SITE PLAN SHOWING THE LOCATION OF THE
 TRAILER.
  
 INCLUDE THE PROPOSED LOCATION, WITH DISTANCES TO
 PROPERTY LINES, EXISTING BUILIDNGS AND PROPOSED
 BUILDINGS.
  
  
 1A) PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS;
 TABLE 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER.
  
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 PLEASE ENSURE COMPLIANCE
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-25 Cont ID  
Sent By lcrespo Date 2021-08-25 Time 14:12 Rev Time 0.00
Received By lcrespo Date 2021-08-12 Time 10:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-28 Cont ID  
Sent By rmcphers Date 2021-07-28 Time 12:38 Rev Time 0.00
Received By rmcphers Date 2021-07-09 Time 14:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2021-07-22 Cont ID  
Sent By medwards Date 2021-07-22 Time 13:30 Rev Time 0.00
Received By medwards Date 2021-07-22 Time 13:30 Sent To  
Notes
2021-07-22 13:31:26FBC 107.3 EXCEPTION 1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-08-25 Cont ID  
Sent By lcrespo Date 2021-08-25 Time 14:04 Rev Time 0.00
Received By lcrespo Date 2021-08-25 Time 14:04 Sent To  
Notes
2021-08-25 14:12:4008/25/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-07-19 Cont ID  
Sent By abelisle Date 2021-07-19 Time 18:19 Rev Time 0.00
Received By abelisle Date 2021-07-19 Time 18:09 Sent To  
Notes
2021-07-19 18:18:271ST REVIEW FBC-2020 PLUMBING
 PERMIT-21061276
 7/19/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1. PROVIDE DOCUMENTATION OF STATE APPROVAL FOR A
 MODULAR BUILDING. PER WEST PALM BEACH AMENDMENTS TO FBC
 107.3.
  
 2. SHOW LOCATION AND SIZE OF SANITARY HOLDING TANKS ON
 SITE PLAN. PER WEST PALM BEACH AMENDMENTS TO FBC
 107.2.1.
  
 3. PROVIDE DOCUMENTATION OF PUMPOUT SCHEDULE FOR
 SANITARY HOLING TANKS. WEST PALM BEACH AMENDMENTS TO
 FBC 107.2.1.
  
 4. SHOW LOCATION AND SIZE OF WATER SERVICE AND
 BACKFLOWS FOR EACH TRAILER. PER WPB AMEND TO FBC
 107.2.1.
  
 5. PLEASE PLACE NOTE ON SITE PLAN A BACKFLOW IS
 REQUIRED AT THE WATER METER AND SHALL HAVE SEPARATE
 PERMIT. PER WPB CROSS CONNECTION MANUAL. PER WEST PALM
 BEACH AMENDMENTS TO FBC 107.2.1.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-08-24 Cont ID  
Sent By rmcphers Date 2021-08-24 Time 08:06 Rev Time 0.00
Received By rmcphers Date 2021-08-24 Time 08:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-07-28 Cont ID  
Sent By rmcphers Date 2021-07-28 Time 12:38 Rev Time 0.00
Received By rmcphers Date 2021-07-28 Time 12:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-08-26 Cont ID  
Sent By llouie Date 2021-08-26 Time   Rev Time 0.00
Received By llouie Date 2021-08-26 Time   Sent To  
Notes
2021-08-26 14:05:32* MINIMUM OF 4 PARKING SPACES REQUIRED FOR THE
 TEMPORARY CONSTRUCTION TRAILER.

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By llouie Date 2021-07-22 Time   Rev Time  
Received By   Date 2021-07-22 Time   Sent To  
Notes
2021-07-22 13:57:13** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) A SITE PLAN SHOWING THE LOCATION OF THE PROPOSED
 CONSTRUCTION TRAILER, ACCESS AND PARKING IS REQUIRED.
 SITE PLAN MUST SHOW SETBACK DIMENSIONS FROM THE
 PROPERTY LINES AND DETAILS FOR PARKING.
  
 2.) PER ZLDR S.94-486, TEMPORARY OFFICES/FACILITIES FOR
 CONSTRUCTION REQUIRES ONE (1) PARKING SPACE PER 300 SQ.
 FT. ACCORDING TO STAFF?S CALCULATIONS, A MINIMUM OF
 FOUR (4) PARKING SPACES ARE REQUIRED FOR THE
 CONSTRUCTION TRAILER.
  
  
 NOTES:
  
 * TEMPORARY CONSTRUCTION OFFICES/TRAILERS, SHALL BE
 REMOVED WITHIN 7 DAYS OF THE FINAL CONSTRUCTION
 INSPECTION BY THE CITY PROPERTY TO THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY. [ZLDR S.94-273]
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: CPD (PALM BEACH RIVERSTONE)
  