Plan Review Details - Permit 21061218
Plan Review Stops For Permit 21061218
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-07-22 Cont ID  
Sent By cpuell Date 2021-07-22 Time 15:11 Rev Time 0.00
Received By cpuell Date 2021-07-22 Time 15:11 Sent To  
Notes
2021-07-22 15:12:104802, 4806 AND 4810 S DIXIE HWY

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-07-07 Cont ID  
Sent By cpuell Date 2021-07-07 Time 16:29 Rev Time 0.00
Received By cpuell Date 2021-07-07 Time 16:29 Sent To  
Notes
2021-07-07 16:31:16BUILDING HAS TWO ADDRESSES 4800 & 4802 S DIXIE HWY. IT
 APPEARS THAT THE WORK YOU ARE DOING IS TO THE 4800 S
 DIXIE HWY UNIT. PLEASE CONTACT [email protected] OR
 561-805-6659 TO DISCUSS ADDRESSING ISSUES.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2021-07-19 Time 15:20 Rev Time 0.00
Received By jwitmer Date 2021-07-19 Time 15:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-09-28 Cont ID  
Sent By pvalenti Date 2021-09-28 Time 13:05 Rev Time 0.00
Received By pvalenti Date 2021-09-28 Time 07:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-09-22 Cont ID  
Sent By jwitmer Date 2021-09-22 Time 15:11 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-09-22 15:10:57WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21061218
 ADD: 4806 S. DIXIE HWY.
 CONT: MAC ENTERPRISES INC.
 TEL: 561-840-0063
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. SEPT. 22ND/ 2021
 ACTION: DENIED.
  
 1) WED. SEPT. 22ND/ 2021 2:00 PM A MEETING WITH THE
 DESIGNER OF RECORD, OWNER, CONTRACTOR, ASSIST. B. O.
 RICHARD GATHRIGHT, PETER VALENTI AND MYSELF. DISCUSSED
 PROBLEM CODE AREAS CAME UP WITH RESOLUTIONS TO BE
 SUBMITTED FOR NEXT REVIEW CYCLE. WILL BE CONSIDERED AN
 A-2 OCUPANCY, BUILD CLASS MINIMUM VB UNSPRINKLERED, 2
 HR OCC. SEPARATION WALLS WITH 4 MEANS OF EGRESS.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-31 Cont ID  
Sent By jwitmer Date 2021-08-31 Time 15:53 Rev Time 0.00
Received By jwitmer Date 2021-08-31 Time 13:46 Sent To  
Notes
2021-08-31 15:53:08WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21061218
 ADD: 4806 S. DIXIE HWY.
 CONT: MAC ENTERPRISES INC.
 TEL: 561-840-0063
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 31ST/ 2021
 ACTION: DENIED.
 NOTICE ONLY!! 4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B) WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS
 IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.
 1-2) COMPLIED.
 3) SHEET T.1 TITLE SHEET: THE RESPONSE COMMENT
 INDICATES THE OCCUPANT LOAD HAS ALWAYS BEEN A B /
 BUSINESS OCCUPANCY WITH AN OCCUPANT LOAD OF 49 OR LESS.
  
 3A) 2ND REQUEST. PLEASE REFER TO THE 2020 FBC-B TABLE
 1004.5 FOR BUSINESS IT IS TAKEN AS GROSS. RESPONSE
 STATES SEE LS1. PLEASE NOTE VERSION 2 PLANS THE LOWER
 LEFT HAND OF THE PAGE THE SQ. FT. AND OCCUPANT LOAD WAS
 CHANGED, IT IS THE SAME FLOOR PLAN NOTHING MOVED, THE
 PLANS WERE VERSIONED.
 FLOOR AREA, GROSS. THE FLOOR AREA WITHIN THE INSIDE
 PERIMETER OF THE EXTERIOR WALLS OF THE BUILDING UNDER
 CONSIDERATION, EXCLUSIVE OF VENT SHAFTS AND COURTS,
 WITHOUT DEDUCTION FOR CORRIDORS, STAIRWAYS, CLOSETS,
 THE THICKNESS OF INTERIOR WALLS, COLUMNS OR OTHER
 FEATURES. THE FLOOR AREA OF A BUILDING, OR PORTION
 THEREOF, NOT PROVIDED WITH SURROUNDING EXTERIOR WALLS
 SHALL BE THE USABLE AREA UNDER THE HORIZONTAL
 PROJECTION OF THE ROOF OR FLOOR ABOVE. THE GROSS FLOOR
 AREA SHALL NOT INCLUDE SHAFTS WITH NO OPENINGS OR
 INTERIOR COURTS.
 FOR ASSEMBLY OCCUPANCIES THE OCCUPANT LOAD FACTOR IS
 TAKEN AS NET. FLOOR AREA, NET. THE ACTUAL OCCUPIED AREA
 NOT INCLUDING UNOCCUPIED ACCESSORY AREAS SUCH AS
 CORRIDORS, STAIRWAYS, TOILET ROOMS, MECHANICAL ROOMS
 AND CLOSETS.
 1ST ROUND OF COMMENTS. THE SOSO MARKET/ CAF? IS LISTED
 AS A BUSINESS OCCUPANCY. THE INTERIOR OCCUPANT LOAD IS
 CALCULATED AT 55 OCCUPANTS AND SQUARE FOOTAGE OF 1,431
 SQ. FT. THIS TENANT SPACE IS AN A2 OCCUPANCY PER
 SECTION 303.3 OF THE 2020FBC-BUILDING CODE. THE TENANT
 SPACE DOES NOT MEET THE CRITERIA FOR SMALL ASSEMBLY
 AREAS, SECTION 303.1.2.
  
  
 3B) 2ND REQUEST, SAME COMMENT. WITH THE CAFE/
 RESTAURANT MEETING THE CRITERIA FOR AN A-2 OCCUPANCY
 AND EITHER A BUSINESS, OR MERCANTILE OCCUPANCY AS THE
 OTHER MIXED-USE OCCUPANCY TABLE 508.4 FOR
 NON-SPRINKLERED BUILDING A 2 HOUR FIRE RATED FIRE
 BARRIER , NOTED ON SHEET LIFE SAFETY PLAN, NO CUT
 SECTION OF WALL NOR UL LISTING, PROVIDE THE LISTING
 DETAIL FOR ALL MATERIALS THAT MAKE UP THE ASSEMBLY.
  
 3C) 2ND ROUND OF COMMENTS. PLEASE PROVIDE A DETAIL/ CUT
 SECTION OF THE FIRE BARRIER WALL IN ACCORDANCE WITH
 SECTION 707.5 OF THE 2020FBC-BUILDING. FIRE BARRIERS
 SHALL EXTEND FROM THE TOP OF THE FINISH FLOOR TO BELOW
 TO THE UNDERSIDE OF THE ROOF SHEATHING AND CONTINUOUS
 THROUGHOUT ALL CONCEALED SPACES. JOINTS AND
 INTERSECTIONS SHALL COMPLY WITH SECTIONS 707.8 AND
 707.9.
  
 3D) 2ND REQUEST. THE CLASSIFICATION OF WORK IS STATED
 AS RETROFIT. PLEASE REFER TO THE 2020 EXISTING BUILDING
 CODE SECTION 1001.2.2.1. PARTIAL CHANGE IN OCCUPANCY.
 WHERE THE OCCUPANCY CHANGE IS MADE TO A PORTION OF AN
 EXISTING BUILDING SECTION 1012 SHALL APPLY. SEE 1012.1
 THROUGH 1012.8 ACCESSIBILITY.
 3E) SEMI-COMPLIED/ DEPENDING ON THE OCCUPANCY TYPE AND
 OCCUPANT LOAD. THE PROJECT DATA IS MISSING THE PLUMBING
 FIXTURE COUNT LOAD, PLEASE NOTE FOR THE PLUMBING
 FIXTURES THE EXTERIOR SEASONAL SEATING IS TO BE FIGURED
 BRING THE TOTAL OCCUPANT LOAD FOR THE PLUMBING FIXTURES
 TO 88 OCCUPANTS. 2020 FBC-BUILDING TABLE 2902.1.
  
 4) 2ND REQUEST. THE TITLE SHEET DECLARED THIS BUILDING
 IS NON-SPRINKLERED. SECTION 1007.1.1 REQUIRES THE (2)
 REQUIRED EXITS TO BE PLACED NOT LESS THAN ONE-HALF THE
 OF THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION
 OF THE BUILDING OR AREA SERVED. THE MEASUREMENT 72.833/
 2= 36.41 FEET APART MINIMUM BETWEEN CENTERLINE OF
 DOORWAYS. THIS REVIEW THE DESIGNER OF RECORD SHOWS THE
 HORIZONTAL SEPARATION OF EXIT DOORWAYS CENTERLINE OF
 THE FRONT DOORS AND THE REAR DOOR AT THE KITCHEN.
 PLEASE REVIEW 2020 FBC-B SECTION 1016.2.5. EGRESS SHALL
 NOT PASS THROUGH KITCHENS, STORAGE ROOMS, CLOSETS OR
 SPACES USED FOR SIMILAR PURPOSES.
 1ST ROUND OF COMMENTS. SHEET LS-1 SHOW THE DIAGONAL
 DISTANCE FOR THE CAFE TO BE 72 FT. 10 INCHES. THE TITLE
 SHEET DECLARED THIS BUILDING IS NON-SPRINKLERED.
 SECTION 1007.1.1 REQUIRES THE (2) REQUIRED EXITS TO BE
 PLACED NOT LESS THAN ONE-HALF THE OF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA SERVED. THE MEASUREMENT 72.833/ 2= 36.41 FEET
 APART MINIMUM. THE PLAN STATES 31FEET 10 INCHES APART.
 WHEN CALIBRATING THE PLAN FROM THE FURTHEST POINT ON
 BOTH PAIRS OF EXIT DOORS THE MEASUREMENT IS 35.75 FEET
 APART.
  
 4A) THE PLAN DOES NOT INDICATE THAT THERE IS 2
 ACCESSIBLE MEANS OF EGRESS, EXITING. THE FLOOR PLAN
 SHOWS WHAT APPEARS TO BECOME A ACCESSIBLE RAMP, IT
 APPEARS TO LEAD TO A PUBLIC WAY. THE FLOOR PLAN DOES
 NOT SHOW IF THE FRONT DOORS ARE ACCESSIBLE FOR EGRESS
 AND EXITING CAN A PERSON IN A WHEELCHAIR MAKE IT TO THE
 PUBLIC WAY. SEE CHANGES IN LEVEL 2020 ACCESS. CODE 303.
 2. FLORIDA ACCESSIBILITY CODE SECTION: DISPROPORTIONATE
 COST 202.4.1. PLEASE REVIEW HOW YOU ARE TO MEET
 DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR THE
 DESIGNER OF RECORD ON THEIR LETTERHEAD NEED TO SHOW HOW
 THEY ARE GOING TO SPEND UP TO THE 20% DISPROPORTIONATE
 FUNDS ($13,240.00 DOLLARS) LISTED FOR EACH ELEMENT
 WHERE THE FUNDS ARE BEING SPENT AND IN THE ORDER LISTED
 IN SECTION 202.4.1 DISPROPORTIONATE COST OF THE 2020
 ACCESSIBILITY CODE.
  
 1ST ROUND OF COMMENTS. 2020 FBC-ACCESSIBILITY CODE
 SECTION 207.1 MEANS OF EGRESS SHALL COMPLY WITH SECTION
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE (2000
 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF THE
 INTERNATIONAL BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 4B) COMPLIED. SHEET LS- 1 AND A.1 BOTH SHOW A NEW
 ACCESSIBLE RAMP. A.1 AND A.4 DETAIL 7 BOTH SHOW THE
 UPPER AND LOWER LANDING TO BE 4 FEET LONG. THE 2020
 FBC-B SECTION 1012.6.3 STATES THE RAMP LANDING LENGTH
 IS REQUIRED TO BE 60 INCHES IN LENGTH. PLEASE NOTE THE
 RAMP IS PART OF THE REQUIRED ACCESSIBLE ROUTE (2ND
 MEANS OF EGRESS).
  
 4C) COMPLIED. PLEASE PROVIDE A SITE PLAN SHOWING THE
 NEW ACCESSIBLE RAMP THE L. S. PLAN IT DOES NOT APPEAR
 TO SHOW THE BOTTOM LANDING WHERE AS THE FLOOR PLAN
 SHOWS A SHORT LANDING, IT IS UNKNOWN IF THE RAMP LEADS
 TO THE PUBLIC WAY AND CLEAR OF ANY PARKING SPACES. 2020
 FBC-B SECTION 1028.5 ACCESS TO THE PUBLIC WAY.
  
 5) NEW COMMENT. THE LIFE SAFETY SHEET DOES NOT SHOW
 COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY CODE.
  
 5A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 5B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 5C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 5D) 902.1. DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORKSTATIONS.
  
 5E)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 5E)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-03 Cont ID  
Sent By jwitmer Date 2021-08-03 Time 10:14 Rev Time 0.00
Received By jwitmer Date 2021-07-19 Time 15:14 Sent To  
Notes
2021-08-03 10:14:12WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21061218
 ADD: 4802 S. DIXIE HWY.
 CONT: MAC ENTERPRISES INC.
 TEL: 561-840-0063
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 03RD/ 2021
 ACTION: DENIED
 1) PLEASE NOTE ADDRESSING CONCERN ABOUT THE ADDRESS
 GIVEN FOR THE PROJECT, PERMIT APPLICATION AND THE TITLE
 BLOCK OF THE PLANS OF 4802 S. DIXIE HWY. BETWEEN THE
 DEMO PLAN AND THE A.1 FLOOR PLAN IT APPEARS WORK IS
 BEING COMPLETED THROUGH OUT THE WHOLE BUILDING WITH THE
 TENANT TO THE RIGHT SIDE OF THE PLANS TO BE CONSIDERED
 A SHELL SPACE.
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
 2020 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 CITY MUNI CODE SEC.78-6 (1-7)(2) LOCATION, BUILDINGS
 CONTAINING MORE THAN ONE ADDRESS. ALL ADDRESSES SHALL
 BE POSTED ON THAT PORTION OF THE STRUCTURE FRONTING OR
 FACING UPON THE STREET OR PRINCIPAL VEHICULAR ACCESS TO
 THE PREMISES, SO AS TO BE READILY VISIBLE TO
 APPROACHING VEHICLES.
  
 2) THERE SEEMS TO BE A DISCREPANCY BETWEEN GOOGLE MAPS
 FRONT ELEVATIONS AND THE DEMO SHEET FRONT OF THE
 BUILDING. IN THE DEMO FLOOR PLAN AT THE FRONT OF THE
 BUILDING THERE IS A SET OF DOUBLE DOORS AND TO THE
 RIGHT OF THE DOUBLE DOORS THE DEMO FLOOR PLAN INDICATES
 ONLY 2 DOORS. WHEREAS GOOGLE MAPS SHOWS 3 EXIT DOORS.
 THE DEMO PLAN ALSO INDICATES ACROSS THE FRONT OF THE
 BUILDING A GLASS FRONT (WINDOWS & DOORS) WITH EXCEPTION
 OF STRUCTURAL COLUMNS. GOOGLE MAPS STREET VIEW ( APRIL
 2019) SHOWS THE DOUBLE FRONT DOORS, TO THE RIGHT OF THE
 DOUBLE DOORS STOREFRONT WINDOWS THEN A ANOTHER GLASS
 STOREFRONT DOOR. TO THE RIGHT OF THE SINGLE STOREFRONT
 DOOR THERE IS WHAT APPEARS TO BE TEXTURE 1-11 VERTICAL
 PLYWOOD THE REMAINDER OF THE BUILDING WITH 2 MORE DOORS
 IN THE BLUE TEXTURE 1-11 PLYWOOD SIDING. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED WHY THE DIFFERENCE
 IN THE PLANS AND GOOGLE STREET VIEW.
  
 3) SHEET T.1 TITLE SHEET:
  
 3A) THE SOSO MARKET/ CAF? IS LISTED AS A BUSINESS
 OCCUPANCY. THE INTERIOR OCCUPANT LOAD IS CALCULATED AT
 55 OCCUPANTS AND SQUARE FOOTAGE OF 1,431 SQ. FT. THIS
 TENANT SPACE IS AN A2 OCCUPANCY PER SECTION 303.3 OF
 THE 2020FBC-BUILDING CODE. THE TENANT SPACE DOES NOT
 MEET THE CRITERIA FOR SMALL ASSEMBLY AREAS, SECTION
 303.1.2.
  
 3B) WITH THE CAF?/ RESTAURANT MEETING THE CRITERIA FOR
 AN A-2 OCCUPANCY AND EITHER A BUSINESS, OR MERCANTILE
 OCCUPANCY AS THE OTHER MIXED-USE OCCUPANCY TABLE 508.4
 FOR NON-SPRINKLERED BUILDING A 2 HOUR FIRE RATED FIRE
 BARRIER , NOTED ON SHEET LIFE SAFETY PLAN, NO CUT
 SECTION OF WALL NOR UL LISTING, PROVIDE THE LISTING
 DETAIL FOR ALL MATERIALS THAT MAKE UP THE ASSEMBLY.
  
 3C) PLEASE PROVIDE A DETAIL/ CUT SECTION OF THE FIRE
 BARRIER WALL IN ACCORDANCE WITH SECTION 707.5 OF THE
 2020FBC-BUILDING. FIRE BARRIERS SHALL EXTEND FROM THE
 TOP OF THE FINISH FLOOR TO BELOW TO THE UNDERSIDE OF
 THE ROOF SHEATHING AND CONTINUOUS THROUGH OUT ALL
 CONCEALED SPACES. JOINTS AND INTERSECTIONS SHALL COMPLY
 WITH SECTIONS 707.8 AND 707.9.
  
 3D) THE CLASSIFICATION OF WORK IS STATED AS RETROFIT.
 PLEASE REFER TO THE 2020 EXISTING BUILDING CODE SECTION
 1001.2.2.1. PARTIAL CHANGE IN OCCUPANCY. WHERE THE
 OCCUPANCY CHANGE IS MADE TO A PORTION OF AN EXISTING
 BUILDING SECTION 1012 SHALL APPLY. SEE 1012.1 THROUGH
 1012.8 ACCESSIBILITY.
 3E) THE PROJECT DATA IS MISSING THE PLUMBING FIXTURE
 COUNT LOAD, PLEASE NOTE FOR THE PLUMBING FIXTURES THE
 EXTERIOR SEASONAL SEATING IS TO BE FIGURED BRING THE
 TOTAL OCCUPANT LOAD FOR THE PLUMBING FIXTURES TO 88
 OCCUPANTS. 2020 FBC-BUILDING TABLE 2902.1.
  
 4) SHEET LS-1 SHOW THE DIAGONAL DISTANCE FOR THE CAF?
 TO BE 72 FT. 10 ? INCHES. THE TITLE SHEET DECLARED THIS
 BUILDING IS NON-SPRINKLERED. SECTION 1007.1.1 REQUIRES
 THE (2) REQUIRED EXITS TO BE PLACED NOT LESS THAN
 ONE-HALF THE OF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL DIMENSION OF THE BUILDING OR AREA SERVED. THE
 MEASUREMENT 72.833/ 2= 36.41 FEET APART MINIMUM. THE
 PLAN STATES 31FEET 10 ? INCHES APART. WHEN CALIBRATING
 THE PLAN FROM THE FURTHEST POINT ON BOTH PAIRS OF EXIT
 DOORS THE MEASUREMENT IS 35.75 FEET APART.
  
 4A) 2020 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 4B) SHEET LS- 1 AND A.1 BOTH SHOW A NEW ACCESSIBLE
 RAMP. A.1 AND A.4 DETAIL 7 BOTH SHOW THE UPPER AND
 LOWER LANDING TO BE 4 FEET LONG. THE 2020 FBC-B SECTION
 1012.6.3 STATES THE RAMP LANDING LENGTH IS REQUIRED TO
 BE 60 INCHES IN LENGTH. PLEASE NOTE THE RAMP IS PART OF
 THE REQUIRED ACCESSIBLE ROUTE (2ND MEANS OF EGRESS).
  
 4C) PLEASE PROVIDE A SITE PLAN SHOWING THE NEW
 ACCESSIBLE RAMP THE L. S. PLAN IT DOES NOT APPEAR TO
 SHOW THE BOTTOM LANDING WHERE AS THE FLOOR PLAN SHOWS A
 SHORT LANDING, IT IS UNKNOWN IF THE RAMP LEADS TO THE
 PUBLIC WAY AND CLEAR OF ANY PARKING SPACES. 2020 FBC-B
 SECTION 1028.5 ACCESS TO THE PUBLIC WAY.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-09-29 Cont ID  
Sent By jleahy Date 2021-09-29 Time 10:26 Rev Time 0.00
Received By jleahy Date 2021-09-29 Time 10:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-09-22 Cont ID  
Sent By jleahy Date 2021-09-22 Time 15:20 Rev Time 0.00
Received By jleahy Date 2021-09-22 Time 15:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-08-31 Cont ID  
Sent By jleahy Date 2021-08-31 Time 16:28 Rev Time 0.00
Received By jleahy Date 2021-08-31 Time 16:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-07-06 Cont ID  
Sent By jleahy Date 2021-07-06 Time 16:26 Rev Time 0.00
Received By jleahy Date 2021-07-06 Time 14:32 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-11-16 Cont ID  
Sent By jleahy Date 2021-11-16 Time 16:09 Rev Time 0.00
Received By jleahy Date 2021-11-16 Time 16:08 Sent To  
Notes
2021-11-16 16:09:42VOICE , DATA, TV JLEAHY

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2021-08-04 Cont ID  
Sent By mgonzale Date 2021-08-04 Time 09:20 Rev Time 0.00
Received By dbattles Date 2021-08-04 Time 09:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2021-09-29 Cont ID  
Sent By   Date 2021-09-29 Time   Rev Time 0.00
Received By bdolan Date 2021-09-29 Time 10:54 Sent To  
Notes
2021-09-29 10:56:45PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-09-20 Cont ID  
Sent By   Date 2021-09-20 Time   Rev Time 0.00
Received By bdolan Date 2021-09-20 Time 11:26 Sent To  
Notes
2021-09-20 11:27:25THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN
 DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 ANY LIFE SAFETY SYSTEMS, SPRINKLER AND/OR FIRE ALARM
 SYSTEMS PRESENT, SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER,
 HOOD/SUPPRESSION SYSTEMS, AND/OR FIRE ALARM SYSTEMS
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS
 BY CERTIFIED CONTRACTORS.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-26 Cont ID  
Sent By   Date 2021-08-26 Time   Rev Time 0.00
Received By   Date 2021-08-26 Time   Sent To  
Notes
2021-08-26 14:22:05THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN
 DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 ANY LIFE SAFETY SYSTEMS, SPRINKLER AND/OR FIRE ALARM
 SYSTEMS PRESENT, SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER,
 HOOD/SUPPRESSION SYSTEMS, AND/OR FIRE ALARM SYSTEMS
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS
 BY CERTIFIED CONTRACTORS.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-07-08 Cont ID  
Sent By   Date 2021-07-08 Time   Rev Time 0.00
Received By bdolan Date 2021-07-08 Time 12:42 Sent To  
Notes
2021-07-08 12:53:47THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN
 DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH
 FIRE RESCUE.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 ANY LIFE SAFETY SYSTEMS, SPRINKLER AND/OR FIRE ALARM
 SYSTEMS PRESENT, SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER,
 HOOD/SUPPRESSION SYSTEMS, AND/OR FIRE ALARM SYSTEMS
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS
 BY CERTIFIED CONTRACTORS.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-07-13 Cont ID  
Sent By lcrespo Date 2021-07-13 Time 16:36 Rev Time 0.00
Received By lcrespo Date 2021-07-13 Time 16:36 Sent To  
Notes
2021-07-13 16:37:4707/13/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-09-29 Cont ID  
Sent By lmarchan Date 2021-09-29 Time 11:57 Rev Time 0.00
Received By lmarchan Date 2021-09-27 Time 16:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-09-22 Cont ID  
Sent By jleahy Date 2021-09-22 Time 15:21 Rev Time 0.00
Received By jleahy Date 2021-09-15 Time 06:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-03 Cont ID  
Sent By lcrespo Date 2021-09-03 Time 17:03 Rev Time 0.00
Received By lcrespo Date 2021-08-25 Time 15:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-04 Cont ID  
Sent By dbattles Date 2021-08-04 Time 09:20 Rev Time 0.00
Received By dbattles Date 2021-07-01 Time 09:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-09-20 Cont ID  
Sent By medwards Date 2021-09-20 Time 09:57 Rev Time 0.00
Received By medwards Date 2021-09-20 Time 09:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-08-30 Cont ID  
Sent By medwards Date 2021-08-30 Time 07:51 Rev Time 0.00
Received By medwards Date 2021-08-30 Time 07:32 Sent To  
Notes
2021-08-30 07:51:402ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21061218
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-3: A/C UNIT SCHEDULE INDICATES RTU-1A,
 RTU-1B, RTU-2A, RTU-2B. SHEET M-1 DOES NOT SHOW THESE
 UNITS. WHERE ARE THESE UNITS LOCATED?
  
 2) SHEET M-3: WHY ARE RTU-3 AND RTU-4 COUNTED IN THE
 AIR BALANCE SCHEDULE AS THEY ARE NOT IN THE A-2 TENANT
 SPACE?
  
 3) PLEASE ADD A NOTE ON THE MECHANICAL DRAWING STATING
 THE HOODS WILL REQUIRE A SEPARATE PERMIT APPLICATION,
 DRAWINGS AND REVIEW. THE HOOD WILL NOT BE REVIEWED
 UNDER THIS PERMIT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-07-07 Cont ID  
Sent By medwards Date 2021-07-07 Time 13:31 Rev Time 0.00
Received By medwards Date 2021-07-02 Time 07:52 Sent To  
Notes
2021-07-07 13:32:021ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21061218
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 A COMPLETE REVIEW CANNOT BE COMPLETED UNTIL THE
 INFORMATION IS CLEARER AS TO WHAT THIS PERMIT SHALL
 INCLUDE. THERE ARE CONFLICTING DOCUMENTS.
  
  
 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED ON THE
 2020 FBC M 403.3.1.1 AND TABLE 403.3.1.1 AND NOT THE
 ARCHITECTURAL OCCUPANT LOAD. THE OUTDOOR AIR
 CALCULATIONS MUST BE CALCULATED BASED ON THE USE OF
 SPACE. ( RTU-1 KITCHEN SHOULD HAVE 182 CFM OF OUTDOOR
 AIR WITH 473 CFM OF EXHAUST; THE TOTAL CFM?S OF OUTDOOR
 AIR FOR RTU-1 SHOULD BE 204 CFM, WHICH IS LESS THAN THE
 600 CFM PROVIDED BUT THE NUMBERS SHOULD BE RIGHT. RTU-2
 DINING-BAR OUTDOOR AIR SHOULD BE 973 CFM, WHICH IS MORE
 THAN THE TOTAL OUTDOOR AIR SHOWN. RTU-3&4 ENERGY
 SUMMARY REPORT PAGE 20 INDICATES THE USE OF EACH SPACE.
 PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED ON EACH
 USE OF SPACE. FBC 403.3.1.1 AND TABLE 403.3.1.1. BASED
 ON THE ENERGY SUMMARY REPORT AND TABLE 403.3.1.1 THE
 OUTDOOR AIR REQUIRED FOR THIS TENANT SPACE WOULD BE
 1,100 CFM.
  
 2) THE ENERGY SUMMARY REPORT IS FOR A RESTAURANT AND
 FOR THE TENANT UPFIT, IT SHOWS THE USE OF SPACE IN THE
 FUTURE TENANT UPFIT. THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS DOES NOT SHOW THE SAME SPACES. THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS SHOWS THE
 FUTURE TENANT SPACE AS A SHELL .
  
 3) THE EQUIPMENT SIZING CALCULATIONS LISTS RTU-3 AND
 RTU-4 AS PROJECT NAME: S DIXIE CAF? RESTAURANT WPB. THE
 DRAWINGS SHOW THESE TWO UNITS ARE FOR THE FUTURE
 TENANT. PLEASE CLEAR UP THIS PROJECT AND ONLY SHOW THE
 RESTAURANT IN THIS PROJECT.
  
 4) PLEASE PROVIDE STRUCTURAL DRAWINGS FOR THIS PROJECT
 SHOWING HOW THE NEW RTU?S WILL BE SUPPORTED ON THE
 EXISTING ROOF. FBC 107.2.1
  
 5) SHEET M-3: THE RTU-4 IS NOT SHOWN ON THE OUTDOOR AIR
 CALCULATIONS. PLEASE INCLUDE RTU-4 IN THIS TABLE. FBC
 107.2
  
 6) PLEASE SHOW THAT THE NEW RTU?S WILL MEET THE
 CLEARANCE AND FALL PROTECTION. FBC M 304.11
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-09-03 Cont ID  
Sent By lcrespo Date 2021-09-03 Time 16:59 Rev Time 0.00
Received By lcrespo Date 2021-09-03 Time 16:14 Sent To  
Notes
2021-09-03 16:59:3709/03/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-07-13 Cont ID  
Sent By lcrespo Date 2021-07-13 Time 16:30 Rev Time 0.00
Received By lcrespo Date 2021-07-09 Time 15:58 Sent To  
Notes
2021-07-13 16:29:4007/13/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A-1;
  
 A. IN RESTROOM 109, THE LAV INS ENCROACHING IN THE
 CLEAR FLOOR SPACE FOR THE CLEAR FLOOR SPACE SHALL BE
 60" INCHES MINIMUM MEASURED PERPENDICULAR FROM THE
 SIDEWALL, AND 56? INCHES MINIMUM MEASURED PERPENDICULAR
 FROM THE REAR WALL PER THE 2020 FBC ACC. SEC. 604.3.1.
  
 B. PLEASE DETAIL OR SHOW ACCESSIBLE DIMENSIONS FOR
 FIXTURE CLEARANCES PER THE FLORIDA BUILDING CODE AND
 FLORIDA ACCESSIBILITY CODE.
  
 2. ON SHEET A-3;
 A. THE PLANS ARE CUT OFF ON THE TOP PART. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. PLEASE SHOW THE TURNING SPACE DIAMETER- SPACE THAT
 SHALL BE A SPACE OF 60 INCHES DIAMETER MINIMUM PER THE
 2020 FBC ACC SEC. 304.3.
  
 C. THE MIRROR'S REFLECTIVE PART NEEDS TO BE 40 INCHES
 TO THE REFLECTIVE SIDE PER THE 2020 FBC ACC SEC. 603.3.
  
 D. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER
 2020 FBC P 425.3 WATER CLOSET SEATS.
  
 E. PLEASE PROVIDE DETAIL ON HOW GRAB BARS REINFORCE IN
 WALLS. WOULD YOU PLEASE SHOW THE MINIMUM AND MAXIMUM
 DISTANCE FROM THE FLOOR PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. ON SHEET P-1;
 STANDARDS FOR ONSITE SEWAGE TREATMENT AND DISPOSAL
 SYSTEMS. A. THE HAND SINKS ARE NOT ALLOWED TO GO INTO
 THE GREASE INTERCEPTOR. PLEASE REFER TO 64E-6, FLORIDA
 ADMINISTRATIVE CODE FOR PROPER DISPLACEMENT TO THE
 SANITARY OR GREASE INTERCEPTOR PER THE 64E-6. THE MOP
 SINK SHALL GO INTO THE GREASE INTERCEPTOR.
  
 B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. WOULD YOU PLEASE MAKE A NOTE ON REMARKS?
  
 4. ON SHEET P-2;
 STANDARDS FOR ONSITE SEWAGE TREATMENT AND DISPOSAL
 SYSTEMS. A. PLEASE SHOW THE MOP SINK GOING INTO THE
 GREASE INTERCEPTOR, REFER TO 64E-6, FLORIDA
 ADMINISTRATIVE CODE FOR PROPER DISPLACEMENT TO THE
 SANITARY OR GREASE INTERCEPTOR PER THE 64E-6. THE MOP
 SINK SHALL GO INTO THE GREASE INTERCEPTOR.
  
 B. HAND SINK IN THE KITCHEN AREA ARE SHOWN GOING INTO
 GREASE INTERCEPTORS WHICH ARE NOT ALLOWED; REFER TO
 64E-6, FLORIDA ADMINISTRATIVE CODE FOR PROPER
 DISPLACEMENT TO THE SANITARY OR GREASE INTERCEPTOR PER
 THE 64E-6. STANDARDS FOR ONSITE SEWAGE TREATMENT AND
 DISPOSAL SYSTEMS.
  
 5. ON SHEET P-3;
  
 A. THE RECIRCULATING MANIFOLD TO THE HOT WATER LINES
 MAY NEED TO BE CLOSER TO THE OUTLET SOURCE; PLEASE
 REFER TO THE 2020 FBC ENERGY CODE TABLE C404.5.1.
  
 B. PLEASE PROVIDE A SHUTOFF VALVE ON BOTH SIDES OF THE
 RECIRCULATING PUMP PER THE 2020 FBC SEC. P 606.2 #3.
 ALSO, SHOW ON HEATER DETAIL P-700 #11.
  
 C. PLEASE PROVIDE A HAMMER ARRESTOR ON THE WARE-WASHER
 AND ANY OTHER QUICK CLOSING VALVE PER THE 2020 FBC SEC.
 604.9.
  
 D. WATER TO EACH STRUCTURE SHALL HAVE A SUPPLY PIPE AT
 THE ENTRANCE INTO THE SHUT-OFF VALVE PER THE 2020 FBC
 606.1 #2 LOCATION OF FULL-OPEN VALVES.
  
 6. ON SHEET P-4, UNDER PLUMBING FIXTURE SCHEDULE FOR
 INLINE BACKFLOW PREVENTER, 1022 ARE FOR SODA MACHINES
 AND WITH A CARBONATION WATER OVERFLOW AND REQUIRE A
 DRAIN PER THE 2020 FBC SEC. 608.17.1.1., THE 1024
 INLINE BACKFLOW PREVENTER ARE FOR ICEMAKER AND COFFEE
 MAKER PER THE 2020 FBC SEC. 608.17.1.2. WOULD YOU
 PLEASE CORRECT WHICH WILL BE USED?
  
 7. ON SHEET P-5; PLEASE PROVIDE DETAIL FOR THE
 MULTIPLE-COMPARTMENT SINK SHOWING THE DISCHARGE
 INDEPENDENTLY TO A WASTE RECEPTOR PER THE 2020 FBC P
 802.1.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status N Date 2021-09-03 Cont ID  
Sent By lcrespo Date 2021-07-13 Time 16:30 Rev Time 0.00
Received By lcrespo Date 2021-07-13 Time 16:30 Sent To  
Notes
2021-09-03 16:59:01NOTE: A SEPARATE PERMIT APPLICATION AND REVIEW ARE
 REQUIRED FROM ENGINEERING FOR THE GREASE INTERCEPTOR.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-09-29 Cont ID  
Sent By jleahy Date 2021-09-29 Time 10:26 Rev Time 0.00
Received By jleahy Date 2021-09-29 Time 10:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-09-22 Cont ID  
Sent By jwitmer Date 2021-09-22 Time 15:11 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-09-03 Cont ID  
Sent By lcrespo Date 2021-09-03 Time 17:03 Rev Time 0.00
Received By lcrespo Date 2021-09-03 Time 17:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-08-03 Cont ID  
Sent By jwitmer Date 2021-08-03 Time 10:20 Rev Time 0.00
Received By jwitmer Date 2021-07-19 Time 15:14 Sent To  
Notes
2021-08-03 10:20:21FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  