Plan Review Details - Permit 21061149
Plan Review Stops For Permit 21061149
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-11-29 Cont ID  
Sent By cthroop Date 2021-11-29 Time 10:52 Rev Time 0.00
Received By cthroop Date 2021-11-29 Time 05:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-11-17 Cont ID  
Sent By cthroop Date 2021-11-17 Time 16:15 Rev Time 0.00
Received By cthroop Date 2021-11-17 Time 14:21 Sent To  
Notes
2021-11-17 16:18:11PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 3RD REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. REVISE PLAN PAGE SP-1. IDENTIFY THE LOCATION OF THE
 6 REQUIRED FLOOD VENTS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RE-SUBMITTING, PLEASE UPLOAD YOUR DOCUMENTS TO
 PROJECT DOX.
 DO NOT E-MAIL DOCUMENTS TO THE PLANS EXAMINER.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-10-29 Cont ID  
Sent By cthroop Date 2021-10-29 Time 08:44 Rev Time 0.00
Received By cthroop Date 2021-10-26 Time 14:28 Sent To  
Notes
2021-10-29 09:04:33PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 COMMENTS FROM 1ST REVIEW:
  
 NOTICE: REVISE PLAN PAGE SP-1 TO ADDRESS THE FOLLOWING:
  
 1. SITE DATA ON PAGE SP-1 STATES GARAGE IS 1,047 SF.
 NOTE ON PAGE A-1 STATES GARAGE TOTAL AREA IS 860 SF.
 CONSTRUCTION DRAWING ELEVATION CERTIFICATE STATES
 GARAGE IS 1,047 SF. PLEASE CLARIFY. THIS WILL DETERMINE
 HOW MANY FLOOD VENTS ARE REQUIRED.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 NEW COMMENTS: 2ND REVIEW
  
 NOTICE: CLARIFICATION REQUIRED:
  
 1A) LETTER FROM ARCHITECT OF RECORD (AOR), GEORGE
 BREWER AIA, DATED 10/15/2021 TO ROBERT BROWN, B.O.
 REQUESTING THE INSTALLATION OF ONLY ONE FLOOD VENT IN
 ADJACENT WALL, WHICH WAS APPROVED BY RB, STATES THE
 SQUARE FOOTAGE OF THE GARAGE IS 930 SF.
 1B) PLAN PAGE SP-1 STATES SQUARE FOOTAGE OF GARAGE IS
 1,047 SF.
 1C) PLAN PAGE A-1 STATES SQUARE FOOTAGE OF GARAGE IS
 1,047 SF.
 1D) FINISHED CONSTRUCTION ELEVATION CERTIFICATE
 SUBMITTED FOR REVIEW STATES SQUARE FOOTAGE OF GARAGE IS
 1,047 SF.
  
 IF AOR, MR. BREWER'S STATEMENT IS CORRECT, PLEASE
 REVISE PLAN PAGES SP-1, A-1 AND ELEVATION CERTIFICATE
 TO REFLECT THE CORRECT SQUARE FOOTAGE OF GARAGE AND
 RE-SUBMIT.
  
 FINAL BUILDING REVIEW PENDING CLARIFICATION.
  
  
 OTHER 1ST REVIEW COMMENTS HAVE BEEN CORRECTED.
  
 2. N/A
  
 3. CORRECTED
  
 4. CORRECTED
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-24 Cont ID  
Sent By cthroop Date 2021-10-15 Time 10:02 Rev Time 0.00
Received By cthroop Date 2021-06-22 Time 16:03 Sent To  
Notes
2021-06-24 10:13:14PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: REVISE PLAN PAGE SP-1 TO ADDRESS THE FOLLOWING:
  
 1. SITE DATA ON PAGE SP-1 STATES GARAGE IS 1,047 SF.
 NOTE ON PAGE A-1 STATES GARAGE TOTAL AREA IS 860 SF.
 CONSTRUCTION DRAWING ELEVATION CERTIFICATE STATES
 GARAGE IS 1,047 SF. PLEASE CLARIFY. THIS WILL DETERMINE
 HOW MANY FLOOD VENTS ARE REQUIRED.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. N/A
  
  
 3. PAGE A-1 HAS A NOTE FOR ROLL DOWN ARMOUR GUARD
 CONTROLLER. PROVIDE PRODUCT APPROVALS FOR ARMOUR GUARD
 OPENING PROTECTION.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 4. PROVIDE ICC-ES REPORT AND FLORIDA PRODUCT APPROVALS
 FOR SMART VENT MODEL 1540-520.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-10-29 Cont ID  
Sent By cthroop Date 2021-10-29 Time 10:25 Rev Time 0.00
Received By cthroop Date 2021-10-26 Time 14:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-06-23 Cont ID  
Sent By cthroop Date 2021-06-23 Time 08:26 Rev Time 0.00
Received By cthroop Date 2021-06-22 Time 16:03 Sent To  
Notes
2021-06-23 08:04:17PLAN REVIEW ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: NOTE FROM ENGINEER OF RECORD (EOR) STATES NO
 CHANGES SHALL BE MADE TO PLANS WITHOUT HIS APPROVAL.
  
 1. REVISE PG E4. TO REFLECT PROPOSED CHANGES UNDER GEN
 RES PERMIT 21060873. ( REPLACE GENERAC 48KW GEN WITH
 KOHLER 100KW GEN, REMOVE LOAD SHEDDING FROM
 CALCULATIONS, CHANGE CONDUCTOR SIZING FOR GEN TO PANEL
 FROM 3 #300MCM TO 3 4/0, ATS WILL BE 400A SE, SHOW
 CONTROL CIRCUT CONDUCTOR TYPE AND SIZING).
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PLAN PAGE E-1 AND ELECTRICAL SITE PLAN SHOW STANDBY
 GENERATOR OUTSIDE GARAGE. GENERATOR LOCATION SHALL BE
 PER PERMIT 21060873 (GEN-RES). REDLINED PLANS.
  
 NOTICE: REVISED PLAN PAGE E4 WILL REQUIRE VALID DIGITAL
 SIGNATURE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-12-14 Cont ID  
Sent By dbattles Date 2021-12-14 Time 16:59 Rev Time 0.00
Received By dbattles Date 2021-11-24 Time 09:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-11-17 Cont ID  
Sent By cthroop Date 2021-11-17 Time 16:26 Rev Time 0.00
Received By cthroop Date 2021-11-01 Time 16:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-29 Cont ID  
Sent By cthroop Date 2021-10-29 Time 10:25 Rev Time 0.00
Received By cthroop Date 2021-10-19 Time 15:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-15 Cont ID  
Sent By medwards Date 2021-07-15 Time 07:48 Rev Time 0.00
Received By medwards Date 2021-06-21 Time 08:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-06-24 Cont ID  
Sent By cthroop Date 2021-06-24 Time 09:39 Rev Time 0.00
Received By cthroop Date 2021-06-22 Time 16:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-06-24 Cont ID  
Sent By cthroop Date 2021-06-24 Time 09:30 Rev Time 0.00
Received By cthroop Date 2021-06-22 Time 16:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-11-29 Cont ID  
Sent By cthroop Date 2021-11-29 Time 10:53 Rev Time 0.00
Received By cthroop Date 2021-11-29 Time 05:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-11-17 Cont ID  
Sent By cthroop Date 2021-11-17 Time 16:23 Rev Time 0.00
Received By cthroop Date 2021-11-17 Time 14:21 Sent To  
Notes
2021-11-17 16:25:50SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 2ND REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: LETTER FROM AOR, GEORG BREWER, AIA, REVISED PLAN
 PAGE A-1 AND REVISED PLAN PAGE SP-1.
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-20 Cont ID  
Sent By mpeterso Date 2021-10-20 Time 08:00 Rev Time 0.00
Received By mpeterso Date 2021-10-20 Time 08:00 Sent To  
Notes
2021-10-20 08:01:57REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS APPROVED
 AND PLANS ROUTED TO STORAGE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-06-24 Cont ID  
Sent By cthroop Date 2021-06-24 Time 09:39 Rev Time 0.00
Received By cthroop Date 2021-06-22 Time 16:03 Sent To  
Notes
2021-06-24 09:40:34PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 1ST REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop Z ZONING
Rev No 2 Status N Date 2021-12-14 Cont ID  
Sent By dbattles Date 2021-12-14 Time 16:58 Rev Time 0.00
Received By dbattles Date 2021-12-14 Time 16:58 Sent To  
Notes
2021-12-14 16:59:07DRAWING IS STAMPED BY ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2021-07-14 Cont ID  
Sent By awooten Date 2021-07-14 Time   Rev Time  
Received By awooten Date 2021-07-14 Time   Sent To  
Notes
***NONE***