Plan Review Details - Permit 21061022
Plan Review Stops For Permit 21061022
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-07-09 Cont ID  
Sent By cpuell Date 2021-07-09 Time 13:25 Rev Time 0.00
Received By cpuell Date 2021-07-09 Time 13:24 Sent To  
Notes
2021-07-09 13:25:43PERMIT APPLIED FOR RER UNIT SEE 21070157

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-06-25 Cont ID  
Sent By cpuell Date 2021-06-25 Time 10:32 Rev Time 0.00
Received By cpuell Date 2021-06-25 Time 10:32 Sent To  
Notes
2021-06-25 10:33:49WORK TO BE DONE ON BOTH BUILDINGS, PLEASE APPLY FOR
 ROOF PERMITS FOR 225 CORTEZ RD AND 227 CORTEZ RD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-07-13 Cont ID  
Sent By jbrooks Date 2021-07-13 Time 09:50 Rev Time 0.00
Received By jbrooks Date 2021-07-13 Time 07:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-25 Cont ID  
Sent By jbrooks Date 2021-06-25 Time 12:47 Rev Time 0.00
Received By jbrooks Date 2021-06-25 Time 07:50 Sent To  
Notes
2021-06-25 12:47:34JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1 FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL16709-R8 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-4 TO
 INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN
 BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE
 BOTTOM OF THE COVER PAGE. PRINT PAGES 1-4 ONLY.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R8 COVERS MULTIPLE ROOF SYSTEM NO. W-1
 THRU W-5. PLEASE SELECT CORRECT OPTIONS FOR SYSTEM NO
 W-4; EXPOSURE (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT
 (H<15); ULTIMATE WIND SPEED (170). ALL APPLICABLE
 DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON
 THE PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS
 NOT SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
 3. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND SHOW THE AREAS TO RECEIVE NEW
 ROOFING CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF
 SLOPE(S), ROOF HEIGHT(S).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-23 Cont ID  
Sent By jbrooks Date 2021-06-23 Time 10:49 Rev Time 0.00
Received By jbrooks Date 2021-06-23 Time 07:40 Sent To  
Notes
2021-06-23 10:50:31JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R7 HAS BEEN REVISED TO FL16709-R8.
 PLEASE PROVIDE A COMPLETE SET OF PRODUCT APPROVALS.
 INCLUDE COVER PAGE, EVALUATION REPORTS AND INSTALLATION
 INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS
 AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE
 PRODUCT APPROVAL DRAWINGS.
 2. SUBMITTED PRODUCT APPROVAL FL2569-R19 HAS BEEN
 REVISED TO FL2569-R22. PLEASE PROVIDE A COMPLETE SET.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER
 RULE 61G20-3.
 3. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 ROOF HEIGHT.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-07-13 Cont ID  
Sent By jbrooks Date 2021-07-13 Time 09:50 Rev Time 0.00
Received By jbrooks Date 2021-07-09 Time 10:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2021-06-25 Cont ID  
Sent By jbrooks Date 2021-06-25 Time 12:47 Rev Time 0.00
Received By jbrooks Date 2021-06-24 Time 11:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-23 Cont ID  
Sent By jbrooks Date 2021-06-23 Time 10:50 Rev Time 0.00
Received By jbrooks Date 2021-06-23 Time 05:24 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved